STARTING SEQUENCE FOR HYDROGEN DRYER.

Hydrogen Dryer Reactivation Temp should be more than 460C. Before starting Dryer, ensure its condensate Drain Manual Valve Close condition and trap should be in service. Open Hydrogen Dryer Cooling Water line Inlet and outlet valve. Check SOV Line Isolation and Local Rota meter isolation valve is open condition. Make power Supply ON on local PLC. Hydrogen Inlet and Outlet valve open manually. Start Hydrogen Dryer on local PLC. In normal condition hydrogen drayer run 8 hrs in 24 hrs. But incase Reactivation temp >1670 C then stop drayer.

SHUT-DOWN SEQUENCE OF HYDROGEN DRYER.


Stop Hydrogen dryer on local PLC. And power supply also stop on local PLC.

Wait some time then after hydrogen line inlet and outlet to be closed. After Hydrogen dryer stopping, keep its water cooling line open for more than o1hrs.Then after cooling down valves may be isolated.