Académique Documents
Professionnel Documents
Culture Documents
TRIATEK, Inc. 2976 Pacific Drive Norcross, GA 30071 Phone 770-242-1922 fax 770-242-1944
Copyright 1997 by TRIATEK, Inc. All rights reserved The information contained in this publication is intended for use as guidelines in designing airflow controls for isolation rooms. TRIATEK is not liable for damages or other consequences which may result from designs that may have used information provided in this publication
page 2 of 2
Contents
Air Supply and Exhaust Design Requirements
Page
Introduction .................................................................................................................... 4
Pressurization .................................................................................................. 5 Clean-Room or Positive Isolation .................................................................... 5 Containment or Negative Isolation .................................................................. 5 Air Changes Per Hour ........................................................................................ 6 Room Air Control .............................................................................................. 6 Summary ........................................................................................................... 7 Control Sequence of Supply and Exhaust Air .............................................................. 8 Data Communications ................................................................................................... 9 FMS/HMS PK .................................................................................................... 9 Building Automation Systems .......................................................................... 9 Engineering Specifications for TRIATEK Room Pressure Monitors ..................... 10-13 FMS-1630 Series Questions & Answers .................................................................14-20
page 3 of 3
page 4 of 4
page 5 of 5
more
page 6 of 6
SUMMARY
By using measurement of space pressure to obtain a single-point summation of supply air and general exhaust air (accomplished through the FMS-1630), the air control will be efficient and stable, while maintaining design room pressure and air changes per hour. This design provides the fast response time of standalone controllers that do not depend upon large network responses, and yet provide means for direct-link communications to a Building Automation System that performs full-facility monitoring. The monitoring can include datalogging of facility conditions, including fume hood face velocity of each and every fume hood and the lab space pressure of all laboratories virtually concurrently. Both the Triatek HMS-1600 and FMS-1630 have direct connection compatibility to the Metasys N2 bus, requiring neither a gateway nor protocol converter. As a result, this package offers the most comprehensive solution to accurate control of air in Laboratories, fume hoods, and reporting capability available today.
page 7 of 7
23-
4-
56-
7-
8-
9-
page 8 of 8
FMS/HMS PK
The FMS/HMS-PK Setup Kit is available from TRIATEK for a nominal one-time office site fee. The program may be installed on multiple computers at the site. It is convenient for use in setting up units in advance of installing them. Typical setup includes setting room numbers and alarm setpoints. The FMS/HMS-PK can also be used to perform centralized monitoring of a network of FMS-1630 and/or HMS-1600 units in those installations where the units are not interfaced to a building automation system. When operating in the Monitor mode, all connected units will be indicated on the monitor screen, along with the status of each in real-time. If a unit goes into alarm, the indication on the screen will change, showing which unit is in alarm. With the FMS/HMS-PK connected to multiple units in operation, the program provides the means for selecting a single unit by its address and viewing the complete setup details. Any of the parameters for the addressed unit can be changed using the computer keyboard, in the same manner as if the computer were connected to a single device.
ENGINEERING SPECIFICATIONS
Specifications that can be used in preparing bids for air control of isolation rooms or clean rooms are provided in the following pages.
page 9 of 9
B. Acceptable Manufacturers 1. The Isolation Room Pressure Monitor design shall be field proven with at least four (4) years of successful operation in room pressurization applications.
2. The Isolation Room Monitor shall be the FMS-1630 Series from TRIATEK INC., 2976 Pacific Drive, Norcross, GA 30071, Telephone (770) 242-1922, Fax (770) 242-1944, Web Site http://www.ttk.com C. Performance Requirements 1. The Isolation Room Pressure Monitor shall be capable of measuring ultra low pressures or flows with both positive and negative standard pressure calibration ranges of 0 to 0.010"WC, 0 to 0.050"WC, 0 to 0.100"WC or 0 to 0.200"WC. The Room Pressure Monitor shall be factory calibrated with NIST traceable standards and shall have an accuracy as follows: PRESSURE RANGE 0 to .01000"WC 0 to .05000"WC 0 to .10000"WC 0 to .20000"WC ACCURACY @ 72 F +5 F + .0001"WC + .0005"WC + .0010"WC + .0020"WC
page 10 of 10
5. The Isolation Room Pressure Monitor shall have an analog output which is field selectable as either a linear signal directly relating to pressure or as a PID floating point control output. Output shall be selectable as either mADC or voltage. This output shall be field scaleable to provide the exact offset and span required to yield the best operating results, i.e., compressed span for
page 11 of 11
page 12 of 12
12.
page 13 of 13
page 14 of 14
3. What is the purpose of the Buzzer Delay and how should it be set? When an isolation room door is opened the pressure will drop causing the FMS-1630 to alarm. Such alarms, when unnecessary, are irritating to patients and staff alike. By setting a buzzer delay, the FMS-1630 will only alarm after the pressure drop exists for a programmable amount of time. For instance, by setting a ten second buzzer delay the FMS-1630 would not alarm until the pressure drop has existed continuously for a full ten seconds. Since many pressure drops caused by opened doors last approximately five seconds, the ten second buzzer delay setting on the FMS-1630 should prevent unnecessary alarms. If this delay does not work with your staff, they should probably be retrained as to the importance of a quick opening and closing of the door so as to not spread infection to staff or to other patients by not following good protocol. Remember that the FMS-1630 has great flexibility and that necessary delays can be programmed into the unit but that the time must be kept short for good practice. 4. What is the purpose of the "NO ISOLATION" touchpad? Putting a room in the "NO ISOLATION" mode turns off the status lights and disables the audible alarm. This mode is used only when no alarms are needed for a period of time while the room is occupied by patients not requiring isolation. In the NO ISOLATION mode, settings for control outputs function as setup for that mode. 5. (a) What is the keyswitch for and (b)who maintains it? a - The keyswitch is for providing security of the isolation selection. b - The responsible person in the area, e.g., the head nurse. This is an important consideration. For safety purposes only one key is delivered with the FMS-1600 unit, and it is important to know where the key is at all times. The key should be maintained by the responsible person. If additional keys are purchased and distributed to other responsible persons, they should be checked at frequent intervals to make sure that they have not been lost or fallen into the wrong hands. 6. How do I put in a password? Enter the Setup menu, then scroll to "Set Password" using the Green touchpad. Press the Red touchpad to begin the process. Decide on a sequence of " + " and " " (Green and Yellow touchpads, respectively) that will be easy to remember, and enter them very carefully, using the Green and Yellow touchpads. Watch for the "
" to
appear in the display each time a touchpad is pressed; press the key a second time if needed to produce the displayed response. It is recommended that the password code sequence be written down and kept in a secure place by the responsible person. 7. Which sensor port on the FMS-1630 points to the room? The FMS-1630 with internal sensor is delivered with the positive port P1 facing out the back of the unit and the negative port P2 inside the display unit. When the unit is
installed on the corridor side of the wall, port P1 will be directed inside the isolation room via the flow tube. If your FMS-1630 has a remote sensor, then with the sensor module installed on the wall inside the room being monitored, P1
faces the isolation room and P2 is connected to the corridor by the flow tube.
page 15 of 15
page 16 of 16
15. How long can the plastic flow tube be? It can be specially ordered to lengths up to 20 feet. The tubing length must be specified at the time the order is placed for the room monitor, because special procedures are applied for extra long tubes during factory calibration. 16. How do I connect remote alarms (engineers office, nurses station, etc.)? Make alarm connections (to a system that accepts dry contact input) to the Relay 1 or Relay 2 output terminals of the FMS unit. 17. Does the FMS-1600 series connect to building automation systems, such as Andover, Automated Logic, Johnson Controls, Landis, etc.? Yes. Contact TRIATEK for details. 18. What FMS units presently provide serial communications? FMS-1630 series provide a communications port that RS-485 serial asynchronous. Contact TRIATEK to determine what communications protocols are available for use with the FMS-1630. 19. How many control outputs does the FMS-1630 unit have? The FMS-1630 has one analog output that can be used for controlling room pressure, or when used as "direct acting" for indicating room pressure reading. There are also available two relay outputs that can be programmed to respond to specified pressure values. The contact outputs can be used for remote alarms and fan (on/off) control. 20. If the FMS-1630 has an internal sensor, is it installed inside or outside of the room to be monitored? The FMS-1630 monitors are typically mounted outside of the patient room. For applications that require the monitor to be mounted inside the patient room call TRIATEK. 21. How should the unit be mounted? The FMS display/control unit should be mounted in a location convenient for reading and operation. When wall mounted, choose a good eye-level location for the personnel who will be using the unit. 22. Glass wall procedure? A glass wall will not permit through-the-wall installation, and is accomplished by use of the Remote Sensor option, which allows the sensor to be located in the ceiling. 23. If the FMS-1600 needs to be re-calibrated, how is it done? If the unit becomes damaged, or a room pressure certification check indicates discrepancies in pressure readings and it is determined for certain that the FMS-1600 needs to be recalibrated, contact TRIATEK. It is not practical to attempt the procedure in the field. 24. How do I turn the alarm off? To turn the alarm off while it is sounding simply press the "ALARM SILENCE" touchpad. To permanently disable the alarm, enter the Setup menu, select "Relay,Status" then after entering this sequence, select "Buzzer", and select "Disable". 25. Who do I call for help? For help call TRIATEK any time Monday through Friday from 7:30AM to 7:00PM Eastern time. Phone Number is 770-242-1922, FAX 770-242-1944.
page 17 of 17
page 18 of 18
35.
36.
37.
38.
39. 40.
41.
42. 43.
page 19 of 19
45. 46.
page 20 of 20