SHORT CIRCUIT CALCULATIONS PRIMARY SUBSTATION

BOWSHER S/S 33kV Bus-1 33kV Bus-2

1Run 3Cx300sqmm 11km

AL-ANSAB STP TR-1 20MVA 33/6.6kV %Z=12.5%

TR-2 20MVA 33/6.6kV %Z=12.5%

AL-ANSAB STP

6.6kV Bus-1

6.6kV Bus-2

To Capacitor

To SS-1

To SS-2

To SS-3

SPARE-1 SPARE-2

SPARE-3

To SS-1

To SS-2

To SS-3

To STP

Fault Current at 33kV in Bowsher S/S Fault Level at 33kV in Bowsher S/S System Voltage Source Impedance at Bowsher S/S Total number of Feeders Feeding Number of Transformer Feeders The distance from the BOWSHER substation The size of the Cable Single core Impedance of the Cable per km Total Impedance at STP S/S Fault Level at Al-Ansab 33kV side of Transformer

19 kA 1085.96 MVA 33 kV 1.0027994 Ohms 2 No. 2 Nos. 11 km 3Cx300 sq.mm 0.123 Ohms 2.356 Ohms 462.22 MVA

Fault Current at 33kV side of Trafo. in Al-Ansab S/S Tansformer HV side Voltage Tansformer LV side Voltage % Impedance of the Transformer Rated Apparent power of the Transformer Base Fault MVA Base Fault Impedance Impedance of the Cable upto 33kv SWGR. Total Impedance upto 33kv SWGR. Impedance of the Transformer at HV side Total Impedance upto Transformer Impedance on LV side of the Transformer Fault Level on LV side of the Transformer Fault Current at LV side of the Transformer Impedance of 6.6kV Cable Length of cable Impedance of Cable Upto 6.6kV SWGR. No. of Runs per phase Fault Impedance with 4 cables paralled Fault Impedance at 6.6kV Bus Fault Level at 6.6kV Bus Fault Current at 6.6kV Bus

8.08699 kA 33 kV 6.6 kV 12.5 % 20 MVA 1085.96 MVA 1.0027994 Ohms 1.353 Ohms 2.3557994 Ohms 6.80625 Ohms 9.1620494 Ohms 0.366482 Ohms 118.85987 MVA 10.397847 KA 0.505 Ohms/KM 0.03 KM 0.01515 Ohms 4 Nos. 8.693E-07 Ohms 0.3664828 Ohms 118.85959 MVA 10.397822 KA

Fault Level as per SLD: Case-A - Fault at Bowsher S/S Case-B - Fault Level at 33kV Al-Ansab STP S/S Incomer-1 Case-C - Fault Level at 33kV Al-Ansab STP S/S Incomer-2 Case-D - Fault at 6.6kV Incomer-1 Bus side Case-E - Fault at 6.6kV Incomer-2 Bus side Case-F - Fault at 6.6kV side I/C-1 & I/C-2 Parallel condition

Impedance Fault Level Fault Current in Ohms in MVA in KA 1.0027994 1085.960 19 2.356 462.224 8.087 2.356 462.224 8.087 0.3664828 118.860 10.398 0.3664828 118.860 10.398 0.1832414 237.719 20.796

To Capacitor

SHORT CIRCUIT CALCULATIONS Headworks Substation-1


Incomer-1 From Primary SS Bus-1 *A Incomer-2 From Primary SS Bus-2 *A

6.6kV 1.4MVA Generator Xd"=0.171(Subtransient reactance) (No Parallel Operation)

6.6kV Bus-1

*B

*D B/C

*C 6.6kV Bus-2

TR-3 1MVA 6.6/0.433kV %Z=4.75%

TR-4 1MVA 6.6/0.433kV %Z=4.75%

*E

0.433kV Bus-1

*G

0.433kV Bus-2

*F

To Cap.

To DB-P1

To MCC-5

To DB

To MCC-1

To MCC-3

To MCC-2

To To DB-P1 MCC-4

To Cap.

Fault Level at 6.6kV in Primary S/S Fault Current at 6.6kV in Primary S/S System Voltage Source Impedance at Primary S/S

118.8596 MVA 10.3980 kA 6.6 kV 0.3665 Ohms

Total number of Feeders Feeding Number of Transformer Feeders The distance from the Primary SS to Headworks SS-1 The size of the Cable Single core Impedance of the Cable per km Fault Impedance at Headworks S/S-1 Fault Level at 6.6kV Headworks SS-1 Fault Current at 6.6kV Headworks S/S-1 Tansformer HV side Voltage Tansformer LV side Voltage % Impedance of the Transformer Rated Apparent power of the Transformer Impedance of the Transformer at HV side Total Impedance upto Transformer Impedance on LV side of the Transformer Fault Level on LV side of the Transformer Fault Current at LV side of the Transformer Fault Impedance at 0.433kV Bus Fault Level at 0.433kV Bus Fault Current at 0.433kV Bus

2 No. 2 Nos. 0.6600 km 3Cx400 sq.mm 0.5050 Ohms 0.7 Ohms 62.23 MVA 5.4438729 kA 6.6 kV 0.433 kV 4.75 % 1 MVA 2.0691 Ohms 2.7691 Ohms 0.0119186 Ohms 15.730743 MVA 20.975554 KA 0.0119186 Ohms 15.730743 MVA 20.975554 KA

Fault Level as per SLD: Case-A - Fault at Primary S/S Case-B - Fault Level at 6.6kV Headworks S/S-1 Incomer-1 Case-C - Fault Level at 6.6kV Headworks S/S-1 Incomer-2 Case-D - Fault at 6.6kV side I/C-1 & I/C-2 Parallel condition Case-E - Fault at 0.433kV Incomer-1 Bus side Case-F - Fault at 0.433kV Incomer-2 Bus side
Case-G - Fault at 0.433kV side I/C-1 & I/C-2 Parallel condition

Impedance Fault Level Fault Current in Ohms in MVA in KA 0.3664828 118.8596 10.398 0.7 62.2286 5.444 0.7 62.2286 5.444 0.35 124.4571 10.887 0.0119186 15.7307 20.976 0.0119186 15.7307 20.976 0.0059593 31.4615 41.951

Since the Generator is not in parallel Operation, we assumed that the EB supply is Maximum fault level.

ransient reactance)

SHORT CIRCUIT CALCULATIONS


Biological Treatment SS-2 Incomer-1 From Primary SS *A Incomer-2 From Primary SS *A *E

6.6kV 3.2MVA Generator Parallel Operation-YES Xd"=0.137(Subtransient reactance)

*F

*G 6.6kV Bus-1 *B *D B/C 6.6kV Soft Starter *C 6.6kV Bus-2 *H

SPARE TR-5 2MVA 6.6/0.433kV %Z=4.75% TR-6 2MVA 6.6/0.433kV %Z=4.75%

6.6KV MOTOR

0.433kV Bus-1

*I

*K

*J

To CAP.

To To DB-P1 MCC-7 MCC-9

To MCC-8

To SMDB DB

To DB-P1

Fault Level at 6.6kV in Primary S/S Fault Current at 6.6kV in Primary S/S System Voltage

118.8596 MVA 10.3980 kA 6.6 kV

Source Impedance at Primary S/S Total number of Feeders Feeding Number of Transformer Feeders
The distance from the Primary SS to Biological Treatment SS-2

0.3665 Ohms 2 No. 2 Nos. 0.99 km 3Cx400 sq.mm 0.505 Ohms 0.866 Ohms 50.3 MVA 4.4002379 kA 6.6 kV 0.433 kV 4.75 % 2 MVA 1.03455 Ohms 1.90055 Ohms 0.0081803 Ohms 22.919681 MVA 30.561368 KA 0.0081803 Ohms 22.919681 MVA 30.561368 KA 0.137 Ohms 3.2 MVA 6.6 kV 0.137 Ohms 317.9562 MVA 27.81477 KA

The size of the Cable Single core Impedance of the Cable per km Fault Impedance at Biological Treatment S/S-2 Fault Level at 6.6kV Biological Treatment SS-2 Fault Current at 6.6kV Biological Treatment S/S-2 Tansformer HV side Voltage Tansformer LV side Voltage % Impedance of the Transformer Rated Apparent power of the Transformer Impedance of the Transformer at HV side Total Impedance upto Transformer Impedance on LV side of the Transformer Fault Level on LV side of the Transformer Fault Current at LV side of the Transformer Fault Impedance at 0.433kV Bus Fault Level at 0.433kV Bus Fault Current at 0.433kV Bus Sub-Transient Reactance of the Generator Rated Apparent power of the Generator Rated Voltage of the Generator Source Impedance of the Generator-1 Fault Level at Generator side Fault Current at Generator side Incase of 2 Generators Parallel condition Source Impedance of the Generators Fault Level at Generator bus side Fault Current at Generator bus side

0.0685 Ohms 635.91241 MVA 55.629541 KA

Impedance Fault Level Fault Current in Ohms in MVA in KA Case-A - Fault at Primary S/S 0.3664828 118.8596 10.398 Case-B - Fault Level at 6.6kV Headworks S/S-1 Incomer-1 0.866 50.3002 4.4 Case-C - Fault Level at 6.6kV Headworks S/S-1 Incomer-2 0.866 50.3002 4.4 Case-D - Incomer-1 & 2 Parallel condition 0.433 100.6005 8.801 Case-E - Fault Level at 6.6kV Generator-1 in service 0.137 317.9562 27.815 Case-F - Fault Level at 6.6kV Generator-2 in service 0.137 317.9562 27.815 Case-G - Fault Level at 6.6kV Generator-1 & 2 in Parallel 0.0685 635.9124 55.63 Case-H - Fault Level at 6.6kV Generator-1 & 2 and I/C-2 Parallel 0.0591436 736.5129 64.43 Case-I - Fault at 0.433kV Incomer-1 Bus side 0.0081803 22.9197 30.561 Case-J - Fault at 0.433kV Incomer-2 Bus side 0.0081803 22.9197 30.561 Case-K - Fault at 0.433kV side I/C-1 & I/C-2 Parallel condition 0.0040901 45.8394 61.123

Fault Level as per SLD:

Parallel Operation-YES ransient reactance)

0.433kV Bus-2

To SMDB

To CAP.

SHORT CIRCUIT CALCULATIONS TE Substation-3


6.6kV Incomer-1 From Primary SS *A Incomer-2 From Primary SS *A 2.5MVA Generator Xd"=0.171(Subtransient reactance) (No Parallel Operation)

6.6kV Bus-1

*B

*D B/C

*C

6.6kV Bus-2

Spare 6.6kV VFD TR-7 1MVA 6.6/0.433kV %Z=4.75% TR-8 1MVA 6.6/0.433kV %Z=4.75%

*E

0.433kV Bus-1

*G

0.433kV Bus-2

*F

To Cap.

To MCC-12

To MCC-11

To DB

Spare

To DB

To DB-P1

To DB-21

To Cap.

Fault Level at 6.6kV in Primary S/S Fault Current at 6.6kV in Primary S/S System Voltage Source Impedance at Primary S/S

118.8596 MVA 10.3980 kA 6.6 kV 0.3665 Ohms

Total number of Feeders Feeding Number of Transformer Feeders The distance from the Primary SS to TE SS-3 The size of the Cable Single core Impedance of the Cable per km Fault Impedance at TE S/S-3 Fault Level at 6.6kV TE SS-3 Fault Current at 6.6kV TE S/S-3 Tansformer HV side Voltage Tansformer LV side Voltage % Impedance of the Transformer Rated Apparent power of the Transformer Impedance of the Transformer at HV side Total Impedance upto Transformer Impedance on LV side of the Transformer Fault Level on LV side of the Transformer Fault Current at LV side of the Transformer Fault Impedance at 0.433kV Bus Fault Level at 0.433kV Bus Fault Current at 0.433kV Bus

2 No. 2 Nos. 0.115 km 3Cx400 sq.mm 0.505 Ohms 0.425 Ohms 102.49 MVA 8.9658129 kA 6.6 kV 0.433 kV 4.75 % 1 MVA 2.0691 Ohms 2.4941 Ohms 0.010735 Ohms 17.465218 MVA 23.288323 KA 0.010735 Ohms 17.465218 MVA 23.288323 KA

Impedance Fault Level Fault Current Fault Level as per SLD: in Ohms in MVA in KA Case-A - Fault at Primary S/S 0.3664828 118.8596 10.398 Case-B - Fault Level at 6.6kV Headworks S/S-1 Incomer-1 0.425 102.4941 8.966 Case-C - Fault Level at 6.6kV Headworks S/S-1 Incomer-2 0.425 102.4941 8.966 Case-D - Fault at 6.6kV side I/C-1 & I/C-2 Parallel condition 0.2125 204.9882 17.932 Case-E - Fault at 0.433kV Incomer-1 Bus side 0.010735 17.4652 23.288 Case-F - Fault at 0.433kV Incomer-2 Bus side 0.010735 17.4652 23.288 Case-G - Fault at 0.433kV side I/C-1 & I/C-2 Parallel condition 0.0053675 34.9304 46.577 Case-H - Fault at 0.433kV Incomer- Bus side 0.010735 17.4652 23.288 Since the Generator is not in parallel Operation, we assumed that the EB supply is Maximum fault level.

ransient reactance)

TR-9 1MVA 6.6/0.433kV %Z=4.75%

0.433kV Bus *H

To To SMDB-GG SMDB-GF

To DB-3

To DB-4

To Cap.