Dimension of Insulator Wind Load Short Circuit Current (I) Max.

Unsupported Span of IPS Tube Phase to Phase Spacing (a) Factor of Safety under S.C Condition Value of Factor M Value of Factor N Value of Factor K Daiameter of Al. Tube 1 Kgf Calculations

0.25 100 40000 7 4 2 8 0.4 1 0.0889 0.0098

Mtr. Dia Kg/Sq.Mtr. Amperes Mtr. Mtr.

2.3 Mtr. Ht

Mtr. kN

Cantilever Strength = ( Wind Load on tube + Wind Load on Post Insulator) X F.O.S + (Short Circuit Force) Wind Load on Post Insulator = = Wind Load on Tubular Busbar = = Short Circuit Force on Post Insulator = = Therefore, Cantilever Strenght = = = Dia x Height x Wind Load/2 28.75 (1)

Span (L1+L2)/2 x Dia. Of Pipe x Wind Load 62.23 (2)

N x M x K x 2.05 x I x 10-8 x L/a 183.68 (1+2) x F.O.S + 3 365.64 Kgf 3.58 KN (3)