Académique Documents
Professionnel Documents
Culture Documents
>
Jos Rodas Utani Jefe de Servicios & Soporte Tcnico Per, Ecuador y Bolivia
Slide 2 of 23 29.04.2013
Generation 4
Slide 3 of 23 29.04.2013
Generation 4
FP2 2000 FP2 1800
20W/in3
15W/in3
Generation 3
Flatpack 1800 Flatpack 1500
10W/in3
5W/in3
SMPS 60/20 Generation Saves the customer money by :
SMPS 1000
More space for customer equipment and/or batteries Thus less cabinets and less footprint in the location
Slide 4 of 23 29.04.2013
Dimensions Modular Configuration 48 VDC 167A Maximum Per Shelf 125A Redundant With four rectifiers installed
17.5 Wide
brackets mount 19, 21 or 23 14.5 Deep 1U 1.75 Height
Slide 5 of 23 29.04.2013
Dimensions Modular Configuration 48 VDC 250A Maximum Per Shelf 187,5A Redundant With four rectifiers installed
17.5 Wide
brackets mount 19, 21 or 23 17 Deep 1U 1.75 Height
Slide 6 of 23 29.04.2013
2. Pequeo y ligero
Personal de mantenimiento - especialmente como repuestos Logstica - un peso ms ligero, significa menos costos de envo
Slide 7 of 23 29.04.2013
Evitar las salidas de llamadas de prioridad (fuera de horas normales) Da una alta eficacia del rectificador
Slide 8 of 23 29.04.2013
4. Controles digitales
2 controlador digital : Dan mas supervisin y control.
Dando al operadores una informacin ms en tiempo real del sistema El personal de mantenimiento sabe exactamente qu necesita hacer con las ayudas.
Slide 9 of 23 29.04.2013
5. Edge connectors
Communications AC Input DC Output
Edge-connector technology
Slide 10 of 23 29.04.2013
Nominal Input
85V 185
Yellow LED Green LED
0W 290 300
Red LED Red LED
Slide 11 of 23 29.04.2013
Mains derating
120
100 80 60 40 20 0 0 50 100 150 200 250 300 350 Voltage (Vac) FP2 48/2000 FP2 48/3000
> Derating below 176Vac (185Vac on 2kW module) > 1382W (46%) at 85Vac
Slide 12 of 23 29.04.2013
7. Temperatura De-rating
2000W 1800W
1400W 1200W 0W
+75
Yellow LED
Red LED
Slide 13 of 23 29.04.2013
7. Temperature De-rating
Temperature derating
120
Slide 14 of 23 29.04.2013
Varistor across the lines for transient protection Hi -ohmic disconnect above 290V / 300V AC
(with auto reconnect when in range)
DC Output
Short circuit proof (constant current) Single or double fan blockage/failure
9. Highly Efficient 2 KW
2000W rectifier : Efficiency at 230Vac input
93
92,5
92
91,5
91
90,5
Eff.(%)
Slide 16 of 23 29.04.2013
90
9. Highly Efficient 3 KW
> Efficiency above 93% at 40-80% load, 92.4% at 100% load > 10% loss reduction on system level
Efficiency (%)
94
93
92
91
90
89
88
86 Load (% )
Slide 17 of 23 29.04.2013
9. Highly Efficient 2 KW HE
Slide 18 of 23 29.04.2013
Slide 19 of 23 29.04.2013
Slide 20 of 23 29.04.2013
Slide 21 of 23 29.04.2013
Slide 22 of 23 29.04.2013
Slide 23 of 23 29.04.2013
Procedimiento de instalacin
Slide 24 of 23 29.04.2013
Panel Frontal
Slide 25 of 23 29.04.2013
Panel Frontal
Power (green)
ON
Rectifier is powered
Flashing
OFF
Slide 26 of 23 29.04.2013
Panel Frontal
Warning (yellow)
ON
Rectifier is in Derating Mode (reduced output power) high internal temperature (+65 to 70 C) or low input voltage (lower than 176VAC) or single fan failure The remote Battery Current Limit is activated AC input voltage is out of range Rectifier in stand-alone mode (or loss of communication with the Smartpack controller
Rectifier is in Over-voltage Protection Mode
Flashing
OFF
Slide 27 of 23 29.04.2013
Panel Frontal
Alarm (red) ON
Rectifier is in Shut-down Mode due to low mains (0 85VAC) or high internal temperature (+75 C or higher) or high output voltage (higher than 59.5 VDC) Internal rectifier failure (malfunction) Fan failure (double fan malfunction) Low output voltage (0 to 43.5VDC) CAN bus failure No alarm situation is present
OFF
Slide 28 of 23 29.04.2013
Unidad de Control
> Scaleable y modular, control flexible para la gama entera de productos Eltek
Slide 29 of 23 29.04.2013
Unidad de Control
>
> > > > > > > >
>
>
Slide 30 of 23 29.04.2013
< 300g
44mm
144 mm
109 mm
Slide 31 of 23 29.04.2013
Alarm LED (red) = Major Alarm active Warning LED (yellow) = Minor Alarm active Power LED (green) = Normal status active
Panel Trasero
CAN Bus
CAN bus
Max 8 Smartpack
Part No : 242100.110
(RoHS compliant)
Max 50 Rectifiers
Slide 33 of 23 29.04.2013
Panel Trasero
Monitoreo de Bateras
Monitoreo de Bateras
Con 4 : Standard Con 3 : Extended
Symmetry measurement 8 strings mid point or 2 strings 12V block Sensor de Temp.
Part No : 242100.110
(RoHS compliant)
Slide 34 of 23 29.04.2013
Conectividad
Batera
Pin
1
2 3 4 5
Function
Symmetry I/P 1
Symmetry I/P 2 Symmetry I/P 3 Symmetry I/P 4 Symmetry I/P 5 Symmetry I/P 6 Symmetry I/P 7 Symmetry I/P 8 Con 3 : Temp sense 2 Con 4 : Temp sense 1
6 7 8 9-10
11 - 14
Slide 35 of 23 29.04.2013
Conectividad - Batera
> CON3 & CON4 Conexin de batera
Slide 36 of 23 29.04.2013
Conectividad
Symmetry
Slide 37 of 23 29.04.2013
Panel Trasero
Sistema interno
Sistema Interno
System measurements Unit Power 2xLVD control (Latched)
Part No : 242100.110
(RoHS compliant)
Slide 38 of 23 29.04.2013
Conectividad Sistema
> CON5 Conexin del sistema
Pin
1 2 3 4 5 6 7 8 9 10 11
Function
Positive Input Negative Input Batt Current +ve Batt Current -ve Batt Fuse +ve Batt Fuse -ve Load Fuse Fail LVD1 Active LVD1 Common LVD2 Active LVD2 Common
Conectividad
Sistema
JP1 -48v system = 1-2 +24v system = 2-3 JP2 -48v system = Neg +24v system = Pos
Slide 40 of 23 29.04.2013
Panel Trasero
Alarmas I/O
Alarma I/O
Con 1 (standard):2 + 2 relay input / output Con 2 (extended):4 + 4 relay input / output
Part No : 242100.110
(RoHS compliant)
Slide 41 of 23 29.04.2013
Conectividad
Externa y Alarm I/O
Pin
1-2 34 5-7 8 - 10 1-2 3-4 5-6 7-8 9 - 11 12 - 14
Function
Alarm input 1 ( + / -) Alarm input 2 ( + / -) Alarm output 1 ( NO /C / NC) Alarm output 2 ( NO /C / NC) Alarm input 3 ( + / -) Alarm input 4 ( + / -) Alarm input 5 ( + / -) Alarm input 6 ( + / -) Alarm output 3 ( NO /C / NC) Alarm output 4 ( NO /C / NC) Alarm output 5 ( NO /C / NC) Alarm output 6 ( NO /C / NC)
15 - 17 18 - 20
RS-232 Opciones
RS-232 mounted
Enables connection of Standalone Webpower or modem
Slide 43 of 23 29.04.2013
Smartpack
Slide 44 of 23 29.04.2013
Panel Trasero
Webpower incluido
Embedded
WebPower
Part No : 242100.113
(RoHS compliant)
Ethernet interface of remote monitoring of Smartpack Is possible to tunnel Powersuite remotely also.
Slide 45 of 23 29.04.2013
Smartpack
Smartpack SNMP/Webpower
Slide 46 of 23 29.04.2013
Escalabilidad
CAN/Power bus
Smartpack Master
Smartpack Slave 1
Smartpack Slave n
System functionality
Voltage input
Symmetry inputs Current inputs Temperature inputs
System functionality
Voltage inputs
Symmetry inputs Current inputs Temperature inputs
1
8 (2x4x12V) 2 2
2
16 (4x4x12V) 4 4
8
64 (16x4x12V) 2x8 2x8
2
6 2+
4
12 4+
2x8
6x8 2+x8
Slide 47 of 23 29.04.2013
Conectividad
Latched Contactors
A latching contactor changes state only when a reversed pulse voltage is applied to the coil.
Protection Diode
Slide 48 of 23 29.04.2013
PowerSuite
Slide 49 of 23 29.04.2013
Slide 50 of 23 29.04.2013
Niveles de acceso
> Smartpack/PowerSuite password
4 digit pin-code
No password
Password:
> Si perdi la contrasea de servicio, enve el numero de serie a fabrica, para poder enviar PUK-code de retorno.
Slide 51 of 23 29.04.2013
NomVolt
BoostVolt
LowBatt1
LowBatt2
HighBatt1
HighBatt2
LVBD
LVLD 1.1
Slide 52 of 23 29.04.2013
NoOfRects.
RectCurrent
Rectifier current
RectSerialNumber
Rect.PrimaryVolt
Rectifier Status
Rectifier status
Rectifier Temp
Rectifier temperature
Slide 53 of 23 29.04.2013
Slide 54 of 23 29.04.2013
Entradas programables
> 6 entradas digitales programables.
Slide 55 of 23 29.04.2013
Entradas programables
> Input Monitor
Slide 56 of 23 29.04.2013
Log de Eventos
> Smartpack front: DisplayMessages > PowerSuite: Event Log
> El Smartpack controlador puede almacenar hasta 1000 eventos cronolgicos. Cuando el registro esta lleno, se sobre escribe el ms viejo evento.
> El registro se almacena en EEPROME Ejemplo
Slide 57 of 23 29.04.2013
27-09-2005 (Date dd-mm-yyyy) 17:15 (Time hh:mm) Battery Voltage (Monitor name/Description) MinorLow: ON (Event status in monitor)
> Volver a conectar se toma cuando el sistema NO es crtico y: - El voltaje de la batera est sobre lmite.
Slide 58 of 23 29.04.2013
Normal usa la tabla de batera Simplificado usa el voltaje final y el tiempo a criterio
- Si se alcanza el tiempo de la prueba las bateras son buenas - Si se alcanza el voltaje final de las bateras primero son malas
> Tres diferentes modos de test son posibles (para ambos tipos)
Manual: Empiezo y parada por una entrada manual Peridico/Intervalo: Programado por tiempo, fecha y el intervalo de periodos.
Slide 59 of 23 29.04.2013
>
>
Slide 60 of 23 29.04.2013
Tiempo [min] Corriente de Bateria 1.9V/cell Voltaje final alto [A] Corriente de Bateria 1.75V/cell Voltaje final bajo [A]
> NOTE. Muchas tablas de batera pueden ser almacenadas en la PC y facil de uploaded al Smartpack con PowerSuite > What is Eltek Std?
Slide 61 of 23 29.04.2013
Slide 62 of 23 29.04.2013
Slide 63 of 23 29.04.2013
Slide 64 of 23 29.04.2013
55,5
Output Voltage [Vdc]
55 54,5 54
Slope
53,5 53 52,5
Min Comp, volt
Temperature T [ C]
Slide 65 of 23 29.04.2013
Load current
Mains
Slide 66 of 23 29.04.2013
Slide 68 of 23 29.04.2013
Soluciones de Sistemas
Cuanta potencia usted necesita ?
>
1U
Slide 70 of 23 29.04.2013
Montaje Flexible
Smartpack in PR
Smartpack in Distribtuion
Slide 71 of 23 29.04.2013
Soluciones Integradas
Soluciones Integradas 2U
5 kg
(exc rectifiers)
1U Distribucion + 1 PR 8000W (166A@48V) Smartpack 2 x 100A Breakers de Bateria 6 x 232A Breakers de Carga 2 x LVD (150A)
Slide 72 of 23 29.04.2013
Soluciones Integradas
Solucion Integrada 5 - 8U
Incluye (up to) :
8 kg
(exc rectifiers)
4U Distribucion + 1-4 PR 32000W (660A@48V) Smartpack 6 x 100A Breakers de Bateria* 18 x 263A Breakers de carga* 2 x LVD (up to 600A)
* Verficar en datasheet por otra for otra configuracion disponible
Slide 73 of 23 29.04.2013
Soluciones Integradas
FP2NX-48-9U power system block
Battery Tray #3
Battery Disconnect #2
Battery Tray #2
Battery Disconnect #1
Battery Tray #1
Slide 74 of 23 29.04.2013
Gabinetes
Slide 76 of 23 29.04.2013
Gracias!!
Slide 77 of 23 29.04.2013