Vous êtes sur la page 1sur 4

TYPE 4X STAINLESS STEEL

PANELBOARDS

SS316L Construction with continuously


welded seams ground smooth

Top or Bottom Fed 1-Phase 3-Wire 120/240 Volt, 3-Phase 4-Wire


120/208 Volt, 3-Phase 4-Wire 277/480 Volt

Gland Plates top & bottom with Breather Drains Eaton Pow-R-Line C 1a & 2a Panelboards
(bolt-on breakers)

100 or 225 Amp Copper Bus Ground Bar and Isolated Neutral Bus 10kA Interrupting Capacity (Sym.)
TECH SPECS INSIDE!

18-42 Circuit Main Lug Only 18-24 Circuit Back Fed Main Breaker (100A max)

316L STAINLESS STEEL

N4XPBHSERIES
TYPE 4X, 12 & 13 ENCLOSED PANELBOARD
Top and Bottom Fed models available (Top Fed model shown below)
1.66 1.66 16.69 (GLAND PLATE OPENING) .14 8.00 4.69 (G.P. OPENING) SS316L TYPE 4X/IP66 BREATHER/DRAIN 20.00 14.00 (MOUNTING CENTER) .44 ENCLOSURE NAMEPLATE PADLOCK PROVISION CIRCUIT DIRECTORY NAMEPLATE(S) MAIN BREAKER LABEL (FOR BACK FEED MAIN BREAKER PANELBOARDS)
ON OFF RESET ON CIRC
1

STAINLESS STEEL

B (MOUNTING CENTER)

10.52

CIRC
2

ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET

AMP CIRC
3

AMP CIRC
4

MAIN
OFF RESET ON OFF RESET

AMP CIRC
5

AMP CIRC
6

AMP CIRC
7

AMP CIRC
8

BRANCH CIRCUIT BREAKER HANDLES WITH PADLOCK PROVISIONS & BREAKER RATING LABELS

ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET ON OFF RESET

AMP CIRC
9

AMP CIRC
10

AMP CIRC
11

AMP CIRC
12

AMP CIRC
13

AMP CIRC
14

AMP CIRC
15

AMP CIRC
16

AMP CIRC
17

AMP CIRC
18

AMP CIRC
19

AMP CIRC
20

AMP CIRC
21

AMP CIRC
22

AMP CIRC
23

AMP CIRC
24

AMP CIRC
25

AMP CIRC
26

AMP CIRC
27

AMP CIRC
28

AMP CIRC
29

AMP CIRC
30

AMP CIRC
31

AMP CIRC
32

AMP CIRC
33

AMP CIRC
34

AMP CIRC
35

AMP CIRC
36

AMP

AMP

GROUND BAR

VIEW SHOWN WITHOUT DEADFRONT .44 SLOT TWO CONDUCTOR GROUND LUG #14~2/0 1/4-20 GROUND STUD

TWO CONDUCTOR GROUND LUG #14~2/0 SS316L TYPE 4X/IP66 BREATHER/DRAIN

N4XPBH SERIES PANELBOARDS (Top Fed)


Catalog # # of Avail. Poles Electrical Rating (see Note 3) Buss Amp Panelboard A B

BRANCH BREAKERS
PRL1A
Type Poles Ampacity Type

PRL2A
Poles Ampacity

N4XPBH1-121-L1 N4XPBH1-181-L1 N4XPBH1-241-L1 N4XPBH1-241-L2 N4XPBH1-301-L2 N4XPBH1-361-L2 N4XPBH1-421-L2 N4XPBH1-123-L1 N4XPBH1-183-L1 N4XPBH1-243-L1 N4XPBH1-243-L2 N4XPBH1-303-L2 N4XPBH1-363-L2 N4XPBH1-423-L2 N4XPBH2-123-L1 N4XPBH2-183-L1 N4XPBH2-243-L1 N4XPBH2-243-L2 N4XPBH2-303-L2 N4XPBH2-363-L2 N4XPBH2-423-L2 N4XPBH1-161-B1 N4XPBH1-221-B1 N4XPBH1-153-B1 N4XPBH1-213-B1 N4XPBH2-153-B1 N4XPBH2-213-B1

12 18 24 24 30 36 42 12 18 24 24 30 36 42 12 18 24 24 30 36 42 16 22 15 21 15 21

1-3W 1-3W 1-3W 1-3W 1-3W 1-3W 1-3W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 1-3W 1-3W 3-4W 3-4W 3-4W 3-4W

120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120-208V 120-208V 120-208V 120-208V 120-208V 120-208V 120-208V 277-480V 277-480V 277-480V 277-480V 277-480V 277-480V 277-480V 120/240V 120/240V 120/208V 120/208V 277/480V 277/480V

100 100 100 225 225 225 225 100 100 100 225 225 225 225 100 100 100 225 225 225 225 100 100 100 100 100 100

PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL2A PRL2A PRL2A PRL2A PRL2A PRL2A PRL2A PRL1A PRL1A PRL1A PRL1A PRL2A PRL2A

16.00 24.00 24.00 30.00 30.00 36.00 36.00 16.00 24.00 24.00 30.00 30.00 36.00 36.00 16.00 24.00 24.00 30.00 30.00 36.00 36.00 24.00 24.00 24.00 24.00 24.00 24.00

18.13 26.13 26.13 32.13 32.13 38.13 38.13 18.13 26.13 26.13 32.13 32.13 38.13 38.13 18.13 26.13 26.13 32.13 32.13 38.13 38.13 26.13 26.13 26.13 26.13 26.13 26.13

BAB

QBGF QBGFEP

1 2 3 1 2 1 2

10-70 & 100 10-125 10-100 15-40 15-50 15-40 15-50

GHB

NO. OF AVAILABLE POLES ISOLATED NEUTRAL

1 2 3

15-100 15-100 15-100

Main Lug Only

BRANCH CIRCUIT OPERATING HANDLES & PLUGS


Catalog # Description

100A Back Fed Main Breaker

N4XPB1-H1 N4XPB1-H2 N4XPB1-H3 N4XPB1-H N4XPB1-GL N4XPB1-GR N4XPB1-GL2 N4XPB1-GR2 N4XPB-HP

Single Pole PL1A Breaker Handle Two Pole PL1A Breaker Handle Three Pole PL1A Breaker Handle PL2A Breaker Handle (ALL POLES) Single Pole PL1A GFI/EPD Breaker Handle - Left Hand Single Pole PL1A GFI/EPD Breaker Handle - Right Hand Two Pole PL1A GFI/EPD Breaker Handle - Left Hand Two Pole PL1A GFI/EPD Breaker Handle - Right Hand Unused Operator Hole Plug

N OT E S:
1. For Bottom Fed Model add suffix -BF 2. For fast operating lever door clamps add suffix -LC 3. 10kA Interrupting Capacity (Sym.)

316L STAINLESS STEEL

N4XPBSERIES
TYPE 4X, 12 & 13 ENCLOSED PANELBOARD
Top and Bottom Fed models available (Top Fed model shown below)
16.69 (GLAND PLATE OPENING) .14 8.00 4.69 (G.P. OPENING) SS316L TYPE 4X/IP66 BREATHER/DRAIN 20.00 14.00 (MOUNTING CENTER) .44 ENCLOSURE NAMEPLATE PADLOCK PROVISION 9.29 1.66 1.66

GROUND BAR

ISOLATED NEUTRAL VIEW SHOWN WITHOUT DEADFRONT & SWING PANEL TWO CONDUCTOR GROUND LUG #14~2/0 1/4-20 GROUND STUD

.44 SLOT

TWO CONDUCTOR GROUND LUG #14~2/0 SS316L TYPE 4X/IP66 BREATHER/DRAIN

BRANCH BREAKERS
PRL1A
Type Poles Ampacity Type

N4XPB SERIES PANELBOARDS (Top Fed)


PRL2A
Poles Ampacity Catalog # # of Avail. Poles Electrical Rating (see Note 3) Buss Amp Panelboard A B

BAB

QBGF QBGFEP

1 2 3 1 2 1 2

10-70 & 100 10-125 10-100 15-40 15-50 15-40 15-50

GHB

1 2 3

15-100 15-100 15-100

N OTES:
1. For Bottom Fed Model add suffix -BF 2. For fast operating lever door clamps add suffix -LC 3. 10kA Interrupting Capacity (Sym.)

N4XPB1-121-L1 N4XPB1-181-L1 N4XPB1-241-L1 N4XPB1-241-L2 N4XPB1-301-L2 N4XPB1-361-L2 N4XPB1-421-L2 N4XPB1-123-L1 N4XPB1-183-L1 N4XPB1-243-L1 N4XPB1-243-L2 N4XPB1-303-L2 N4XPB1-363-L2 N4XPB1-423-L2 N4XPB2-123-L1 N4XPB2-183-L1 N4XPB2-243-L1 N4XPB2-243-L2 N4XPB2-303-L2 N4XPB2-363-L2 N4XPB2-423-L2 N4XPB1-161-B1 N4XPB1-221-B1 N4XPB1-153-B1 N4XPB1-213-B1 N4XPB2-153-B1 N4XPB2-213-B1

12 18 24 24 30 36 42 12 18 24 24 30 36 42 12 18 24 24 30 36 42 16 22 15 21 15 21

1-3W 1-3W 1-3W 1-3W 1-3W 1-3W 1-3W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 3-4W 1-3W 1-3W 3-4W 3-4W 3-4W 3-4W

120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120-208V 120-208V 120-208V 120-208V 120-208V 120-208V 120-208V 277-480V 277-480V 277-480V 277-480V 277-480V 277-480V 277-480V 120/240V 120/240V 120/208V 120/208V 277/480V 277/480V

100 100 100 225 225 225 225 100 100 100 225 225 225 225 100 100 100 225 225 225 225 100 100 100 100 100 100

PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL1A PRL2A PRL2A PRL2A PRL2A PRL2A PRL2A PRL1A PRL1A PRL1A PRL1A PRL2A PRL2A

16.00 24.00 24.00 30.00 30.00 36.00 36.00 16.00 24.00 24.00 30.00 30.00 36.00 36.00 16.00 24.00 24.00 30.00 30.00 36.00 36.00 24.00 24.00 24.00 24.00 24.00 24.00

18.13 26.13 26.13 32.13 32.13 38.13 38.13 18.13 26.13 26.13 32.13 32.13 38.13 38.13 18.13 26.13 26.13 32.13 32.13 38.13 38.13 26.13 26.13 26.13 26.13 26.13 26.13

100A Back Fed Main Breaker

Main Lug Only

PANELBOARD

B (MOUNTING CENTER)

NO. OF AVAILABLE POLES

N4XPBHSERIES
Type 4X, 12 & 13 Enclosed Panelboard Circuit Breaker Operating Handlesaluminum handles (stainless
steel handle option available, consult factory) with stainless steel bushings and shafts. V-ring seals, gaskets and sealing nuts provided for water tight seal. Handles are spring loaded allowing for the door to be closed with the breaker toggle in any position. GFI/EPD handles are colored green and include external test capabilities. Lockplate provision provides padlocking for each individual breaker in either the on or off position. Individual operating labels identify breaker position (on, off, tripped) the circuit number and breaker amperages. Circuit Directory Holder Card Back Fed Main Breaker Assemblies provided with Main Nameplate. UL/cUL Listed

N4X P BHS ER IES

N4XPBSERIES
Type 4X, 12 & 13 Enclosed Panelboard Swing Panel Dead Front isolates the wiring space, wiring gutter
and termination area which would be otherwise exposed when the door is opened. Quick Release Door Clamps for fast access to interior panel (optional) UL/cUL Listed

N 4 X PB SE R I E S

How To Order:
1. Specify Catalog Number 2. Starting with Circuit #1 (Circuit #2 on back fed main breaker panelboards), specify circuit breaker type, number of poles, and ampacity. 3. For N4XPBH Series: Handles will be provided for each breaker specified. Unused spaces will be plugged. For blank spaces requiring handles, specify handle catalog number and circuit number. 4. Specify Entries, if any are r equired Attach layout sheet.

CALL ADALET at 216-267-9000


NCAT 73 REVA
ADALET 4801 West 150th Street, Cleveland, Ohio 44135 TEL 216.267.9000 FAX 216.267.1681 info@adalet.com