SISTEMA DE ILUMINACION EXTERIOR DEL CAMPAMENTO CRUSEHER CONVEYOR (CC

Campamento del Crusher Conveyor (CC) Proyecto Las Bambas


OT9108

CONTRATO : 25635-220-HC1-AKBP-00006
XSTRATA BECHTEL

12-12-2012

Emitido para Revisin

REV

FECHA

RAZON PARA REVISION

J. Estocalenko J. Miranda
POR

REV

E. Lovon
APROB

JOB N

Bechtel

XSTRATA

Pg.
25635-220-HC1-AKBP-00006

Cdigo EMSA N
EM-OT9108-ET020

1/30
Rev.
A

Cdigo BECHTEL N

Pg. 1

MEMORIA DE CLCULO
SISTEMA DE ILUMINACION CAMPAMENTO DEL CRUSER CONVEYOR

INDICE
1.

GENERALIDADES... 3

2.

CRITERIOS DE DISEO ELECTRICO..3

3.

4.

2.1

Calculo de Conductores

2.2

Calculo de Alimentadores

2.3

Calculo de Iluminacin

2.4

Calculo del Sistema de Puesta a Tierra.

CRITERIOS DE DISEO MECANICO..4


3.1

Objeto

3.2

Factores de Seguridad

3.3

Formulas Aplicables

3.4

Simbologa

3.5

Cimentacin de Postes

3.6

Calculo de Retenidas

3.7

Criterios de Diseo de retenidas

3.8

Calculo de Retenidas

3.9

Calculo del Bloque de Retenidas.

PLANOS DE OBRA...7

Pg. 2

SISTEMA DE ILUMINACION CAMPAMENTO DEL CRUSER CONVEYOR


1.0 GENERALIDADES
El proyecto al que se refiere este documento, corresponde y describe los En el
presente documento se presenta los Clculos Justificativos de las Redes de
Alumbrado para el Campamento del Crusher Conveyor (CC) Proyecto Las
Bambas, las cuales cumplen las normas y disposiciones legales como:
o

Cdigo Nacional de Electricidad Suministro 2011.

Reglamento de la Ley de Concesiones Elctricas N 25844.

Norma DGE/MEM.

2.0 SELECCION DE LOS CONDUCTORES ALIMENTADORES


Se va a utilizar conductores de autoportantes de seccin para la redes
secundaria en 0.38/0.22 kV, estas secciones se han determinado realizando
los clculos de cada de tensin y la capacidad trmica de los conductores de
las secciones consideradas.
2.1 CLCULO DE CONDUCTORES AUTOSOPORTADOS
Clculos por capacidad de corriente. Los clculos se han hecho con la
siguiente frmula:
I

MDTOTAL
KxVx cos

Dnde:
K = 1.73 para circuito trifsico
K = 2 para circuito monofsico
a) Clculos por Cada de tensin
Los clculos de Cada de tensin se han realizado con la siguiente
frmula:
xL
V KxI
x cos
S

Pg. 3

V = FCT * L * I*10-3
Dnde:
I
V
MDTOTAL
Cos
V
L

:
:
:
:
:
:
:

S
K

:
:

Corriente en Amperios
Tensin de servicio en voltios
Mxima demanda total en Watts.
Factor de potencia, 0.85
Cada de tensin en voltios, 2.5%.
Longitud en mts.
Resistencia especfica o coeficiente de resistividad
del cobre para el conductor en Ohm-mm/m. Para
el cobre = 1/44 Ohm-mm2/m a 90 C.
Seccin del conductor en mm
Constante que depende del sistema.
para
Circuito trifsico, 2 para circuito monofsico.

Clculos de Prdidas de Potencia por Efecto Joule


El clculo de las prdidas de potencia se calcular empleando la siguiente
frmula:
P =

P(R)L
, en Kw.
1000VL (cos)

Dnde:
L
= Longitud del tramo de lnea en km.
P
= Potencia en kW
R
= Resistencia de operacin del conductor en Ohm/km.
Cos = Factor de potencia: Fdp = 0,9
VL
=Tensin entre fases en kV.
Los resultados de los clculos se muestran en el siguiente cuadro:

Pg. 4

SISTEMA DE ALUMBRADO PUBLICO 380/220 V CAMPAMENTO LAS BAMBAS.

S.E.Dp N :
POTENCIA S.E.D.p (KVA):
Fecha :

500

CALCULO DE CAIDA TENSION

feb-13

ALUMBRADO PUBLICO

Localidad

LAS BAMBAS

Distrito

CHALHUAHUACHO

Provincia

COTABAMBAS

Dpto.

APURIMAC

RESUMEN :
HORAS DE FUNCIONAMIENTO AL AO

==

FACTOR DE SIMULTANEIDAD :

FACTOR DE POTENCIA :

FACTOR DE CARGA

FACTOR DE PERDIDAS

TENSION NOMINAL DEL SISTEMA

==

RESUMEN SED

4380
1.00
0.85
0.50
0.30
380 V

MAXIMA POTENCIA(Pmx)

2.62

[Kw]

% PERDIDA DE POTENCIA

0.76

[%]

ENERGIA VENDIDA ANUAL

2872 [KW-h]

PERDIDA ENERGIA ANUAL

13.15 [KW-h]

% PERDIDA ENERGIA ANUAL

0.46

[%]

Punto

ANTERIOR

CIRCUITO 01:
LAMPARAS

Long.

POT. S POT.

No. de Lmparas

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

I
[A]

1.22

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

[ m]

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

1.90E-03

1.90E-03

1.90E-03

1.90E-03

1.90E-03

1.90E-03

SI
[A]

Fase 1 Fase 2 Fase 3


[V]

[V]

[V]

PERDIDAS

Total

de

Potencia Energa

[V]

[ kW ]

[ kW-h ]

0.1293 0.1293 0.1293 0.3878 0.102

0.002

1.09

1.90E-03

0.1847 0.1847 0.1847 0.9419 0.248

0.002

1.34

1.90E-03

1.90E-03

0.1539 0.1539 0.1539 1.4036 0.369

0.001

0.93

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 1.7730 0.467

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 2.0501 0.539

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 2.2347 0.588

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 2.3271 0.612

0.000

0.04

0.61

3.79

0 7

0.175

1.224

0.54

3.789

18

0.175

1.049

0.54

3.248

30

0.175

0.874

0.54

2.707

30

0.175

0.699

0.54

2.165

30

0.175

0.525

0.54

1.624

30

0.175

0.350

0.54

1.083

30

0.175

0.175

0.54

0.541

30

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

0.01 4.48

CIRCUITO 02:
LAMPARAS
Punto

Long.

POT. S POT.

No. de Lmparas

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

0 11

I
[A]

1.40

SI
[A]

[ m]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

Fase 1 Fase 2 Fase 3


[V]

[V]

[V]

PERDIDAS

Total

de

Potencia Energa

[V]

[ kW ]

[ kW-h ]

1.07

4.33

0.175

1.399

0.54

4.331

30

0.175

1.224

0.54

3.789

30

0.175

1.049

0.54

3.248

30

0.175

0.874

0.54

2.707

30

0.175

0.699

0.54

2.165

30

0.175

0.525

0.54

1.624

30

0.175

0.350

0.54

1.083

30

0.175

0.699

0.54

2.165

30

0.175

0.525

0.54

1.624

30

10

0.175

0.350

0.54

1.083

30

11

0.175

0.175

0.54

0.541

29

11

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

1.90E-03

1.90E-03

1.90E-03

0.2463 0.2463 0.2463 0.7388 0.194

0.004

2.38

1.90E-03

1.90E-03

1.90E-03

0.2155 0.2155 0.2155 1.3852 0.365

0.003

1.82

1.90E-03

1.90E-03

1.90E-03

0.1847 0.1847 0.1847 1.9392 0.510

0.002

1.34

1.90E-03

1.90E-03

1.90E-03

0.1539 0.1539 0.1539 2.4010 0.632

0.001

0.93

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 2.7703 0.729

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 3.0474 0.802

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 3.2321 0.851

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 3.6014 0.948

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 3.8785 1.021

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 4.0632 1.069

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0298 0.0298 0.0298 3.3213 0.874

0.000

0.04

0.01 8.67

Pg. 5

SISTEMA DE ALUMBRADO PUBLICO 380/220 V CAMPAMENTO LAS BAMBAS.

S.E.Dp N :
POTENCIA S.E.D.p (KVA):
Fecha :

500

CALCULO DE CAIDA TENSION

feb-13

ALUMBRADO PUBLICO

Localidad

LAS BAMBAS

Distrito

CHALHUAHUACHO

Provincia

COTABAMBAS

Dpto.

APURIMAC

RESUMEN :
HORAS DE FUNCIONAMIENTO AL AO

==

FACTOR DE SIMULTANEIDAD :

FACTOR DE POTENCIA :

FACTOR DE CARGA

FACTOR DE PERDIDAS

TENSION NOMINAL DEL SISTEMA

==

RESUMEN SED

4380
1.00
0.85
0.50
0.30
380 V

MAXIMA POTENCIA(Pmx)

3.50

[Kw]

% PERDIDA DE POTENCIA

1.29

[%]

ENERGIA VENDIDA ANUAL

3829 [KW-h]

PERDIDA ENERGIA ANUAL

29.62 [KW-h]

% PERDIDA ENERGIA ANUAL

0.77

[%]

Punto

ANTERIOR

CIRCUITO 01:
LAMPARAS
No. de Lmparas

POT.

Long.
S POT.

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

I
[A]

2.10

S I
[A]

[ m]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

PERDIDAS

de

Cond.

Fase 1

Fase 2

Fase 3

Fase 1

Fase 2

Fase 3

Total

de

Potencia Energa

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

[V]

[V]

[V]

[V]

[ kW ]

[ kW-h ]

1.78

6.50

0 12

0.175

2.098

0.54

6.496

18

0.175

1.923

0.54

5.955

30

0.175

1.749

0.54

5.413

30

0.175

1.574

0.54

4.872

30

0.175

1.399

0.54

4.331

30

0.175

1.224

0.54

3.789

30

0.175

1.049

0.54

3.248

30

0.175

0.874

0.54

2.707

30

0.175

0.699

0.54

2.165

30

10

0.175

0.525

0.54

1.624

30

11

10

0.175

0.350

0.54

1.083

30

12

11

0.175

0.175

0.54

0.541

30

12

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

1.90E-03

1.90E-03

1.90E-03

0.2216 0.2216 0.2216 0.6649

0.175

0.005

3.21

1.90E-03

1.90E-03

1.90E-03

0.3386 0.3386 0.3386 1.6807

0.442

0.007

4.50

1.90E-03

1.90E-03

1.90E-03

0.3078 0.3078 0.3078 2.6041

0.685

0.006

3.72

1.90E-03

1.90E-03

1.90E-03

0.2770 0.2770 0.2770 3.4352

0.904

0.005

3.01

1.90E-03

1.90E-03

1.90E-03

0.2463 0.2463 0.2463 4.1740

1.098

0.004

2.38

1.90E-03

1.90E-03

1.90E-03

0.2155 0.2155 0.2155 4.8204

1.269

0.003

1.82

1.90E-03

1.90E-03

1.90E-03

0.1847 0.1847 0.1847 5.3745

1.414

0.002

1.34

1.90E-03

1.90E-03

1.90E-03

0.1539 0.1539 0.1539 5.8362

1.536

0.001

0.93

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 6.2056

1.633

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 6.4826

1.706

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 6.6673

1.755

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 6.7596

1.779

0.000

0.04

0.03 22.04

CIRCUITO 02:
LAMPARAS
Punto

No. de Lmparas

POT.

Long.
S POT.

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

I
[A]

1.40

S I
[A]

[ m]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

PERDIDAS

de

Cond.

Fase 1

Fase 2

Fase 3

Fase 1

Fase 2

Fase 3

Total

de

Potencia Energa

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

[V]

[V]

[V]

[V]

[ kW ]

[ kW-h ]

0.87

4.33

0.175

1.399

0.54

4.331

30

0.175

1.224

0.54

3.789

30

0.175

1.049

0.54

3.248

30

0.175

0.874

0.54

2.707

30

0.175

0.699

0.54

2.165

30

0.175

0.525

0.54

1.624

30

0.175

0.350

0.54

1.083

30

0.175

0.175

0.54

0.541

30

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

1.90E-03

1.90E-03

1.90E-03

0.2463 0.2463 0.2463 0.7388

0.194

0.004

2.38

1.90E-03

1.90E-03

1.90E-03

0.2155 0.2155 0.2155 1.3852

0.365

0.003

1.82

1.90E-03

1.90E-03

1.90E-03

0.1847 0.1847 0.1847 1.9392

0.510

0.002

1.34

1.90E-03

1.90E-03

1.90E-03

0.1539 0.1539 0.1539 2.4010

0.632

0.001

0.93

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 2.7703

0.729

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 3.0474

0.802

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 3.2321

0.851

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 3.3244

0.875

0.000

0.04

0.01 7.59

Pg. 6

SISTEMA DE ALUMBRADO PUBLICO 380/220 V CAMPAMENTO LAS BAMBAS.

S.E.Dp N :
POTENCIA S.E.D.p (KVA):
Fecha :

500

CALCULO DE CAIDA TENSION

feb-13

ALUMBRADO PUBLICO

Localidad

LAS BAMBAS

Distrito

CHALHUAHUACHO

Provincia

COTABAMBAS

Dpto.

APURIMAC

RESUMEN :
HORAS DE FUNCIONAMIENTO AL AO

==

FACTOR DE SIMULTANEIDAD :

FACTOR DE POTENCIA :

FACTOR DE CARGA

FACTOR DE PERDIDAS

TENSION NOMINAL DEL SISTEMA

==

RESUMEN SED

4380
1.00
0.85
0.50
0.30
380 V

MAXIMA POTENCIA(Pmx)

1.57

[Kw]

% PERDIDA DE POTENCIA

0.55

[%]

ENERGIA VENDIDA ANUAL

1723 [KW-h]

PERDIDA ENERGIA ANUAL

5.70 [KW-h]

% PERDIDA ENERGIA ANUAL

0.33

[%]

Punto

ANTERIOR

CIRCUITO 01:
LAMPARAS

Long.

POT. S POT.

No. de Lmparas

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

I
[A]

1.57

SI
[A]

[ m]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

Fase 1 Fase 2 Fase 3


[V]

[V]

[V]

PERDIDAS

Total

de

Potencia Energa

[V]

[ kW ]

[ kW-h ]

0.61

4.87

0 9

0.175

1.574

0.54

4.872

18

0.175

1.399

0.54

4.331

30

0.350

1.224

1.08

3.789

30

0.175

0.525

0.54

1.624

30

0.175

0.350

0.54

1.083

30

0.175

0.175

0.54

0.541

30

3.1

0.175

0.350

0.54

1.083

30

3.2

3.1

0.175

0.175

0.54

0.541

30

3x35+N/25
3x35+N/25
3x35+N/25
3x35+N/25
3x35+N/25
3x35+N/25

3x35+N/25
3x35+N/25

1.61E-03

1.61E-03

1.61E-03

0.1409 0.1409 0.1409 0.4228 0.111

0.002

1.53

1.61E-03

1.61E-03

1.61E-03

0.2088 0.2088 0.2088 1.0491 0.276

0.003

2.02

1.61E-03

1.61E-03

1.61E-03

0.1827 0.1827 0.1827 1.5972 0.420

0.002

1.55

1.61E-03

1.61E-03

1.61E-03

0.0783 0.0783 0.0783 1.8321 0.482

0.000

0.28

1.61E-03

1.61E-03

1.61E-03

0.0522 0.0522 0.0522 1.9886 0.523

0.000

0.13

1.61E-03

1.61E-03

1.61E-03

0.0261 0.0261 0.0261 2.0669 0.544

0.000

0.03

1.61E-03

1.61E-03

1.61E-03

0.0522 0.0522 0.0522 2.2235 0.585

0.000

0.13

1.61E-03

1.61E-03

1.61E-03

0.0261 0.0261 0.0261 2.3018 0.606

0.000

0.03

0.01 5.70

Pg. 7

SISTEMA DE ALUMBRADO PUBLICO 380/220 V CAMPAMENTO LAS BAMBAS.

S.E.Dp N :
POTENCIA S.E.D.p (KVA):
Fecha :

500

CALCULO DE CAIDA TENSION

feb-13

ALUMBRADO PUBLICO

Localidad

LAS BAMBAS

Distrito

CHALHUAHUACHO

Provincia

COTABAMBAS

Dpto.

APURIMAC

RESUMEN :
HORAS DE FUNCIONAMIENTO AL AO

==

FACTOR DE SIMULTANEIDAD :

FACTOR DE POTENCIA :

FACTOR DE CARGA

FACTOR DE PERDIDAS

TENSION NOMINAL DEL SISTEMA

=
=

RESUMEN SED

4380
1.00
0.85
0.50
0.30
380 V

MAXIMA POTENCIA(Pmx)

5.07

% PERDIDA DE POTENCIA

1.54

[%]

ENERGIA VENDIDA ANUAL

5552

[KW-h]

PERDIDA ENERGIA ANUAL

51.40

[KW-h]

% PERDIDA ENERGIA ANUAL

0.93

[Kw]

[%]

Punto

ANTERIOR

CIRCUITO 01:
LAMPARAS
S POT.

S I

50 W 70 W 100 W 150 W 250 W [ kW ]

[ kW ]

[A]

[A]

Seccin de

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

Fase 1

Fase 2

Fase 3

Total

de

Potencia

Energa

[ m]

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

[V]

[V]

[V]

[V]

[ kW ]

[ kW-h ]

1.75

1.90E-03

1.90E-03

1.90E-03

0.1847

0.1847

0.1847

0.5541

0.146

0.003

2.23

1.90E-03

1.90E-03

1.90E-03

0.2770

0.2770

0.2770

1.3852

0.365

0.005

3.01

1.90E-03

1.90E-03

1.90E-03

0.2463

0.2463

0.2463

2.1239

0.559

0.004

2.38

1.90E-03

1.90E-03

1.90E-03

0.2155

0.2155

0.2155

2.7703

0.729

0.003

1.82

1.90E-03

1.90E-03

1.90E-03

0.1847

0.1847

0.1847

3.3244

0.875

0.002

1.34

1.90E-03

1.90E-03

1.90E-03

0.1539

0.1539

0.1539

3.7861

0.996

0.001

0.93

1.90E-03

1.90E-03

1.90E-03

0.1231

0.1231

0.1231

4.1555

1.094

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923

0.0923

0.0923

4.4325

1.166

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616

0.0616

0.0616

4.6172

1.215

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308

0.0308

0.0308

4.7096

1.239

0.000

0.04

0.175

1.749

0.54

5.413

18

0.175

1.574

0.54

4.872

30

0.175

1.399

0.54

4.331

30

0.175

1.224

0.54

3.789

30

0.175

1.049

0.54

3.248

30

0.175

0.874

0.54

2.707

30

0.175

0.699

0.54

2.165

30

0.175

0.525

0.54

1.624

30

0.175

0.350

0.54

1.083

30

10

0.175

0.175

0.54

0.541

30

10

PERDIDAS

1.24

5.41

0 10
0

Cdigo

Long.

POT.

No. de Lmparas

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

0.02 12.83

CIRCUITO 02:
LAMPARAS
S POT.

S I

50 W 70 W 100 W 150 W 250 W [ kW ]

[ kW ]

[A]

[A]

No. de Lmparas

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

Fase 1

Fase 2

Fase 3

Total

de

Potencia

Energa

[ m]

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

[V]

[V]

[V]

[V]

[ kW ]

[ kW-h ]

1.90E-03

1.90E-03

1.90E-03

0.4925

0.4925

0.4925

1.4775

0.389

0.017

11.30

1.90E-03

1.90E-03

1.90E-03

0.4617

0.4617

0.4617

2.8627

0.753

0.015

10.04

1.90E-03

1.90E-03

1.90E-03

0.3386

0.3386

0.3386

3.8785

1.021

0.009

5.73

1.90E-03

1.90E-03

1.90E-03

0.2770

0.2770

0.2770

4.7096

1.239

0.005

3.01

1.90E-03

1.90E-03

1.90E-03

0.2463

0.2463

0.2463

5.4483

1.434

0.004

2.38

1.90E-03

1.90E-03

1.90E-03

0.2155

0.2155

0.2155

6.0947

1.604

0.003

1.82

1.90E-03

1.90E-03

1.90E-03

0.1847

0.1847

0.1847

6.6488

1.750

0.002

1.34

1.90E-03

1.90E-03

1.90E-03

0.1539

0.1539

0.1539

7.1105

1.871

0.001

0.93

1.90E-03

1.90E-03

1.90E-03

0.1231

0.1231

0.1231

7.4799

1.968

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923

0.0923

0.0923

7.7570

2.041

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616

0.0616

0.0616

7.9416

2.090

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308

0.0308

0.0308

8.0340

2.114

0.000

0.04

1.90E-03

1.90E-03

1.90E-03

0.0923

0.0923

0.0923

3.1397

0.826

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616

0.0616

0.0616

3.3244

0.875

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308

0.0308

0.0308

6.7412

1.774

0.000

0.04

1.90E-03

1.90E-03

1.90E-03

0.0308

0.0308

0.0308

3.9708

1.045

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308

0.0308

0.0308

4.0632

1.069

0.000

0.11

1.90E-03

1.90E-03

1.90E-03

0.0308

0.0308

0.0308

4.1555

1.094

0.000

0.07

1.90E-03

1.90E-03

1.90E-03

0.0308

0.0308

0.0308

7.5723

1.993

0.000

0.04

Long.

POT.

Punto

3.32

PERDIDAS

2.11

8.66

0 19

0.175

3.322

0.54

8.661

30

0.175

3.147

0.54

8.120

30

0.175

2.448

0.54

5.955

30

0.175

1.574

0.54

4.872

30

0.175

1.399

0.54

4.331

30

0.175

1.224

0.54

3.789

30

0.175

1.049

0.54

3.248

30

0.175

0.874

0.54

2.707

30

0.175

0.699

0.54

2.165

30

10

0.175

0.525

0.54

1.624

30

11

0.175

0.350

0.54

1.083

30

12

0.175

0.175

0.54

0.541

30

2.1

0.175

0.525

0.54

1.624

30

2.2

0.175

0.350

0.54

1.083

30

2.3

0.175

0.175

0.54

0.541

30

3.1

0.175

0.699

0.54

0.541

30

3.2

0.175

0.525

0.54

0.541

30

3.3

0.175

0.350

0.54

0.541

30

3.4

0.175

0.175

0.54

0.541

30

19

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

3x35/25
3x35/25
3x35/25

3x35/25
3x35/25
3x35/25
3x35/25

0.06 38.56

Pg. 8

SISTEMA DE ALUMBRADO PUBLICO 380/220 V CAMPAMENTO LAS BAMBAS.

S.E.Dp N :
POTENCIA S.E.D.p (KVA):
Fecha :

500

CALCULO DE CAIDA TENSION

feb-13

ALUMBRADO PUBLICO

Localidad

LAS BAMBAS

Distrito

CHALHUAHUACHO

Provincia

COTABAMBAS

Dpto.

APURIMAC

RESUMEN :
HORAS DE FUNCIONAMIENTO AL AO

==

FACTOR DE SIMULTANEIDAD :

FACTOR DE POTENCIA :

FACTOR DE CARGA

FACTOR DE PERDIDAS

TENSION NOMINAL DEL SISTEMA

==

RESUMEN SED

4380
1.00
0.85
0.50
0.30
380 V

MAXIMA POTENCIA(Pmx)

1.57

[Kw]

% PERDIDA DE POTENCIA

0.27

[%]

ENERGIA VENDIDA ANUAL

1723 [KW-h]

PERDIDA ENERGIA ANUAL

2.79 [KW-h]

% PERDIDA ENERGIA ANUAL

0.16

[%]

Punto

ANTERIOR

CIRCUITO 01:
LAMPARAS
No. de Lmparas

POT.

Long.
S POT.

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

I
[A]

0.87

S I
[A]

[ m]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

PERDIDAS

de

Cond.

Fase 1

Fase 2

Fase 3

Fase 1

Fase 2

Fase 3

Total

de

Potencia Energa

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

[V]

[V]

[V]

[V]

0.175

0.874

0.54

2.707

18

0.175

0.699

0.54

2.165

30

0.175

0.525

0.54

1.624

30

0.175

0.350

0.54

1.083

30

0.175

0.175

0.54

0.541

30

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 0.2770

0.073

0.001

0.56

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 0.6464

0.170

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 0.9234

0.243

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 1.1081

0.292

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 1.2005

0.316

0.000

0.04

8944560

No. de Lmparas

POT.

Long.
S POT.

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

I
[A]

0.70

S I
[A]

[ m]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

PERDIDAS

de

Cond.

Fase 1

Fase 2

Fase 3

Fase 1

Fase 2

Fase 3

Total

de

Potencia Energa

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

[V]

[V]

[V]

[V]

0.175

0.699

0.54

2.165

30

0.175

0.525

0.54

1.624

30

0.175

0.350

0.54

1.083

30

0.175

0.175

0.54

0.541

30

3x35/25
3x35/25
3x35/25
3x35/25

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 0.3694

0.097

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 0.6464

0.170

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 0.8311

0.219

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 0.9234

0.243

0.000

0.04

8944560

No. de Lmparas

POT.

Long.
S POT.

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

[ kW-h ]

0.00 1.12

LAMPARAS

[ kW ]

1.90E-03

CIRCUITO 03:

0.24

2.17

Punto

[ kW-h ]

0.00 1.67

LAMPARAS

[ kW ]

1.90E-03

CIRCUITO 02:
Punto

0.32

2.71

I
[A]

0.70

S I
[A]

[ m]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

PERDIDAS

de

Cond.

Fase 1

Fase 2

Fase 3

Fase 1

Fase 2

Fase 3

Total

de

Potencia Energa

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

[V]

[V]

[V]

[V]

[ kW ]

[ kW-h ]

0.24

2.17

0.175

0.699

0.54

2.165

30

3x35/25

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 0.3694

0.097

0.001

0.60

0.175

0.525

0.54

1.624

30

3x35/25

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 0.6464

0.170

0.001

0.33

0.175

0.350

0.54

1.083

30

3x35/25

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 0.8311

0.219

0.000

0.15

0.175

0.175

0.54

0.541

30

3x35/25

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 0.9234

0.243

0.000

0.04

1.1

0.175

0.350

0.54

1.083

30

3x35/25

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 0.5541

0.146

0.000

0.15

1.2

1.1

0.175

0.175

0.54

0.541

30

3x35/25

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 0.6464

0.170

0.000

0.04

0.00 1.30

Pg. 9

SISTEMA DE ALUMBRADO PUBLICO 380/220 V CAMPAMENTO LAS BAMBAS.

S.E.Dp N :
POTENCIA S.E.D.p (KVA):
Fecha :

500

CALCULO DE CAIDA TENSION

feb-13

ALUMBRADO PUBLICO

Localidad

LAS BAMBAS

Distrit o

CHALHUAHUACHO

Provincia

COTABAMBAS

Dpto.

APURIMAC

RESUMEN :
HORAS DE FUNCIONAMIENTO AL AO

==

FACTOR DE SIMULTANEIDAD :

FACTOR DE POTENCIA :

FACTOR DE CARGA

FACTOR DE PERDIDAS

TENSION NOMINAL DEL SISTEMA

==

RESUMEN SED

4380
1.00
0.85
0.50
0.30
380 V

MAXIMA POTENCIA(Pmx)

1.57 [Kw]

% PERDIDA DE POTENCIA

0.27 [%]

ENERGIA VENDIDA ANUAL

1723 [KW-h]

PERDIDA ENERGIA ANUAL

2.81 [KW-h]

% PERDIDA ENERGIA ANUAL

0.16 [%]

Punto

ANTERIOR

CIRCUITO 01:
LAMPARAS

Long. Cdigo

POT. S POT.

No. de Lmparas

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ] [ A ]

SI
[A]

[ m]

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

Fase 1 Fase 2 Fase 3 Total


[V]

[V]

[V]

[V]

0.70

2.17

0.175 0.699

0.54

18

2.165

PERDIDAS

de

Potencia Energa

[ kW ] [ kW-h ]

0.16

0 4

Seccin de

0.175 0.525

0.54 ##### 30

0.175 0.175

0.54

0.541

30

1.1

1.1

0.175 0.175

0.54

0.541

30

3x35/25
3x35/25
3x35/25

3x35/25

1.90E-03

1.90E-03

1.90E-03

0.0739 0.0739 0.0739 0.2216 0.058

0.001

0.36

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 0.4987 0.131

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 0.5910 0.156

0.000

0.04

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 0.5910 0.156

0.000

0.04

0.00 0.77

CIRCUITO 02:
LAMPARAS
Punto

Long. Cdigo

POT. S POT.

No. de Lmparas

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ] [ A ]

0 5

0.87

SI
[A]

[ m]

Seccin de

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

Fase 1 Fase 2 Fase 3 Total


[V]

[V]

[V]

[V]

PERDIDAS

de

Potencia Energa

[ kW ] [ kW-h ]

0.36

2.71

0.175 0.874

0.54

2.707

30

0.175 0.699

0.54

2.165

30

0.175 0.525

0.54

1.624

30

0.175 0.350

0.54

1.083

30

0.175 0.175

0.54

0.541

30

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

1.90E-03

1.90E-03

1.90E-03

0.1539 0.1539 0.1539 0.4617 0.122

0.001

0.93

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 0.8311 0.219

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 1.1081 0.292

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 1.2928 0.340

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 1.3852 0.365

0.000

0.04

0.00 2.05

Pg. 10

SISTEMA DE ALUMBRADO PUBLICO 380/220 V CAMPAMENTO LAS BAMBAS.

9 - PTAR

S.E.Dp N :
POTENCIA S.E.D.p (KVA):
Fecha :

500

CALCULO DE CAIDA TENSION

feb-13

ALUMBRADO PUBLICO

Localidad

LAS BAMBAS

Distrito

CHALHUAHUACHO

Provincia

COTABAMBAS

Dpto.

APURIMAC

RESUMEN :
HORAS DE FUNCIONAMIENTO AL AO

==

FACTOR DE SIMULTANEIDAD :

FACTOR DE POTENCIA :

FACTOR DE CARGA

FACTOR DE PERDIDAS

TENSION NOMINAL DEL SISTEMA

==

RESUMEN SED

4380
1.00
0.85
0.50
0.30
380 V

MAXIMA POTENCIA(Pmx)

2.62

[Kw]

% PERDIDA DE POTENCIA

0.61

[%]

ENERGIA VENDIDA ANUAL

2872 [KW-h]

PERDIDA ENERGIA ANUAL

10.43 [KW-h]
0.36

% PERDIDA ENERGIA ANUAL

[%]

Punto

ANTERIOR

CIRCUITO 01:
LAMPARAS

Long.

POT. S POT.

No. de Lmparas

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

I
[A]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

[ m]

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

1.90E-03

1.90E-03

1.90E-03

1.90E-03

1.90E-03

1.90E-03

SI
[A]

[V]

[V]

[V]

PERDIDAS

Total

de

Potencia Energa

[V]

[ kW ]

[ kW-h ]

0.1478 0.1478 0.1478 0.4433 0.117

0.002

1.43

1.90E-03

0.2155 0.2155 0.2155 1.0897 0.287

0.003

1.82

1.90E-03

1.90E-03

0.1847 0.1847 0.1847 1.6437 0.433

0.002

1.34

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 1.8284 0.481

0.000

0.15

1.90E-03

1.90E-03

1.90E-03

0.0308 0.0308 0.0308 1.9208 0.505

0.000

0.04

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 1.9208 0.505

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 2.1055 0.554

0.000

0.15

0.55

0 8

1.40

0.175 1.399

0.54

4.331

18

Fase 1 Fase 2 Fase 3

4.33

0.175 1.224

0.54

3.789

30

0.175 1.049

0.54

3.248

30

0.175 0.350

0.54

1.083

30

0.175 0.175

0.54

0.541

30

3.1

0.175 0.525

0.54

1.624

30

3.2 3.1

0.350 0.350

1.08

1.083

30

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

3x35/25
3x35/25

0.01 5.26

CIRCUITO 02:
LAMPARAS
Punto

Long.

POT. S POT.

No. de Lmparas

50 W 70 W 100 W 150 W 250 W [ kW ] [ kW ]

0 7

1.22

I
[A]

SI
[A]

[ m]

Cdigo

Seccin de

F.C.T.

F.C.T.

F.C.T.

de

Cond.

Fase 1

Fase 2

Fase 3

cable

[mm]

[V/A-m]

[V/A-m]

[V/A-m]

Fase 1 Fase 2 Fase 3


[V]

[V]

[V]

PERDIDAS

Total

de

Potencia Energa

[V]

[ kW ]

[ kW-h ]

0.66

3.79

0.175 1.224

0.54

3.789

30

0.175 1.049

0.54

3.248

30

0.175 0.874

0.54

2.707

30

0.175 0.699

0.54

2.165

30

0.175 0.525

0.54

1.624

30

0.350 0.350

1.08

1.083

30

3x35/25
3x35/25
3x35/25
3x35/25
3x35/25
3x35/25

1.90E-03

1.90E-03

1.90E-03

0.2155 0.2155 0.2155 0.6464 0.170

0.003

1.82

1.90E-03

1.90E-03

1.90E-03

0.1847 0.1847 0.1847 1.2005 0.316

0.002

1.34

1.90E-03

1.90E-03

1.90E-03

0.1539 0.1539 0.1539 1.6622 0.437

0.001

0.93

1.90E-03

1.90E-03

1.90E-03

0.1231 0.1231 0.1231 2.0316 0.535

0.001

0.60

1.90E-03

1.90E-03

1.90E-03

0.0923 0.0923 0.0923 2.3086 0.608

0.001

0.33

1.90E-03

1.90E-03

1.90E-03

0.0616 0.0616 0.0616 2.4933 0.656

0.000

0.15

0.01 5.17

Pg. 11

2.2 CALCULO ALIMENTADORES DEL TABLERO GENERAL "TG"


Los alimentadores para los equipos de alumbrado del campamento
CCCAM,
se
instalaran
desde
los
Tableros Generales ubicados en cada una de las Subestaciones que a
continuacin indicamos: SEDp N 01 (850 KVA), SEDp N 02 (600 KVA),
SEDp N 03 (650 KVA), SEDp N 06 (1000 KVA), SEDp N 07 (750 KVA)
y SEDp N 08 (1400 KVA), desde las cuales se alimentaran el sistema de
alumbrado. Para la seleccin del conductor se ha tenido en cuenta el
mnimo calibre comercial existente as como la necesidad de nuestro
cliente de la calidad de producto obtenindose perfiles de tensin
adecuada. Los conductores indicados en el cuadro adjunto se instalaran
en tuberas de 2" (80mm) PVC-P.
CALCULO DE ALIMENTADORES SUBTERRANEO
TENSION (KV) = 0.38

Cos = 0.85

ALIMENTADO R

DEMANDA
MAX IMA DEL
TABLERO

CO RRIENTE
NO MINAL DE
CARG A

KW

KW

"IC"

SEDp

(A)

CO RRIENTE DE
DIS EO

S ECCIO N DEL CABLE N2 X O H o


RZK1

"IC"

"S"

(A)

(mm )

CO RRIENTE
NO MINAL DEL
CABLE

"Inc"
(A)

C1

1.22

2.18

2.73

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C2

1.40

2.50

3.13

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C1

2.10

3.75

4.69

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C2

1.40

2.50

3.13

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C1

1.57

2.81

3.51

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C1

1.75

3.13

3.91

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C2

3.32

5.93

7.42

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C1

0.70

1.25

1.56

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C2

0.70

1.25

1.56

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C3

1.05

1.88

2.35

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C1

0.70

1.25

1.56

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

C2

0.87

1.56

1.94

3 - 1 x 6 + 1 x 6 +1 x 6

68.00

3
6

NOTA: LOS CABLES HAN SIDO SELECCIONADO POR CAIDA DE TENSION MAS QUE POR CARGA Y TENIENDO EN
CONSIDERACION LA SECCION MINIMA COMERCIAL DEL CABLE N2XOH o RZK1. PERMITIENDOSE PERFILES DE TENSION

Pg. 12

2.3 CALCULO DE ILUMINACION


Para el clculo de iluminacin, se ha utilizado el software DIALUX. Se
emple la luminaria hermtica Josfel AHR 2TL36, y se obtuvo los
siguientes resultados:
TIPO DE
ALUMBRADO

LUMINANCIA
MEDIA
REVESTIMIENTO
SECO

III

0.5 - 1.0

Iluminancia Media
(lux)
CALZADA
CLARA

CALZADA
CLARA

5-10

10-20

INDICE DE CONTROL
DE
DESLUMBRAMIENTO

5-6

Estos valores son admisibles con los niveles de iluminacin recomendados


para el tipo de alumbrado seleccionado para el rea del proyecto.
2.4

CALCULO DEL SISTEMA DE PUESTA A TIERRA


GENERALIDADES
Para hacer el clculo correspondiente de la resistencia de puesta a tierra, se
tomara en cuenta el valor medio de la resistividad correspondiente a la clase
de suelo del campamento el cual es 500 Ohm-m.
Para el clculo de la resistencia de la malla, se aplicarn las ecuaciones de
Schwarz, las cuales establecen que la resistencia de una malla compuesta,
est dada por las siguientes expresiones:

R * R R2
1 2
12
R
R R 2 *R
1
2
12
Dnde:
R1
R2
R12

: Resistencia del reticulado


: Resistencia de las barras
: Resistencia mutua entre el reticulado y las barras

Para calcular cada una de las resistencias se utilizan las siguientes ecuaciones:

R1

4xL

K 1 * L1 K 2
x Ln
* L1 dxh
A

R2

2 * K 1 * L2
4xL2

x Ln
* n 1
1
2 * n * L2 r
A

Pg. 13

R12

2*L K1*L

x Ln
K 2 1

*L l
A

Dnde:
d: dimetro del conductor (m)
h: Profundidad de enterramiento de la malla (m)
A: rea total de la malla (m)
L1: Longitud total de los conductores de la malla (m)
: Resistividad del terreno
L2: Longitud total de los electrodos verticales (m)
n : Cantidad de electrodos
r : Radio de los electrodos verticales (m)
l : Longitud de la barra (m)
Los factores K1 y K2 se calculan de acuerdo con las siguientes expresiones:

K1 1.43

K 2 5. 5

a
0.044 *
S
b

2.3xh

8xh
S

0.15

a
*
S b

Dnde:
a: Ancho de la malla (m)
b: Largo de la malla (m)
h: Profundidad de enterramiento de la malla (m)
S: rea total de la malla (m)

CALCULO DE LA RESISTENCIA DE LA MALLA (BT)


El valor de la resistividad equivalente se deber determinar a partir de las
mediciones obtenidas del suelo y la configuracin de malla propuesta.
Malla Propuesta
Se considerar una malla que cubra una superficie de acuerdo a lo
proyectado.
Por lo tanto, se propone para el anlisis, un sistema compuesto por un
enmallado de las siguientes caractersticas:

Pg. 14

Dnde:
Conductor

= 70mm

a: Ancho de la malla (m)

= 28m

b: Largo de la malla (m)

= 40m

A: rea total de la malla (m2)

= 1120m

d: dimetro del conductor (m)

= 0.019m

h: Profundidad de enterramiento de la malla (m)

= 0.60m

L1: Longitud total de los conductores de la malla (m)

= 164m
= 500

Resistividad del terreno

L2: Longitud total de los electrodos verticales (m)

= 14.4m

n : Cantidad de electrodos

= 6

r : Radio de los electrodos verticales (m)

= 10.5/1000

l : Longitud de la barra (m)

= 2.4m

CALCULO DE LA MALLA:
Clculo de los factores k1 y K2
28
0.044 x 1.36
1120
40

2.3x0.60

K 1 1.43

K 2 5.5

8x0.60

Se tiene:

0.15

1120

K1: 1.36,

28
x 5.49
1120 40

0.60

K2: 5.49

Clculo de la resistencia del reticulado:


R1

9.6 Ohms.

Clculo de la resistencia de las barras


R2

34.4 Ohms.

Clculo de la resistencia mutua entre el reticulado y las barras


R12 = 6.9 Ohms.
Clculo de la resistencia compuesta:

Pg. 15

Tenemos:
R1 = 9.6
R2 = 34.4
R12 = 6.9

12.5*35.2 8.8 2
12.5 35.2 2 *8.8

R = 9.35
CONCLUSION:
La malla propuesta ms los contrapesos da una resistencia equivalente de
9.35 Ohms, cumple con el Proyecto y las Normas del Cdigo Nacional
Utilizacin - Electricidad.

3.0

CRITERIOS DE DISEOS MECNICO


Diseo Mecnico del Conductor
Sobre la base de las prescripciones de la Normas y las condiciones
climatolgicas del rea del proyecto se han definido las siguientes hiptesis de
trabajo para los clculos mecnicos de los conductores:
Hiptesis I: Condicin de mayor duracin (EDS inicial - Templado)
Temperatura
Velocidad de viento
Espesor del Hielo
Esfuerzo EDS inicial
Para conductores de 35 mm2

:
:
:
:
:

10 [C]
0 [km/h]
0 [mm]
18 [%]
53,24N/mm2

Hiptesis II: Mnima Temperatura


Temperatura
Velocidad de viento
Espesor del Hielo
% Tiro de Seguridad

:
:
:
:

-10 [C]
0 [km/h]
0 [mm]
60 [%]

Hiptesis III: Mxima Velocidad de Viento (Mximo Esfuerzo).

Pg. 16

Temperatura
Velocidad de viento
Espesor del Hielo
% Tiro de Seguridad

:
:
:
:

0 [C]
113 [km/h]
0 [mm
60 [%]

Hiptesis IV: Mxima Temperatura (Flecha Mxima)


Temperatura
Velocidad de viento
Espesor del Hielo
% Tiro de Seguridad

:
:
:
:

50 [C] (*)
0 [km/h]
0 [mm*]
60 [%]

Hiptesis V: Mxima Carga de Hielo (Condicin de Falla)


Temperatura
:
-5 [C]
Velocidad de viento
:
35 [km/h]
Espesor del Hielo
:
3 [mm]
% Tiro de Seguridad
:
60 [%]
(*): En los anlisis se han considerado un Creep equivalente a 10.
* En este proyecto se consideran los siguientes esfuerzos de trabajo para el
conductor: 95 mm
Esf. Horizontal en la condicin EDS Inicial
:
18%
Esf. Horizontal en la condicin EDS Final
:
15%
Esfuerzo tangencial mximo
:
60% de la rotura
del conductor.

Pg. 17

ANEXO N 3.1.6
CLCULO MECNICO DE CONDUCTORES AUTOPORTANTES
3x16+N25, EDS - 18%
Conductor 3x16 + N25
Seccin 25,00mm2
Diametro Exterior 16,5mm
Peso Unitario 2,440 N/m
Tiro de Rotura 7356,86 N

Vano
[m]
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100

H (N)
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324

Hiptesis I :
Hiptesis II :
Hiptesis III :
Hiptesis IV :
Hiptesis V :

HIPOTESIS I
T (N)
1,324
1,324
1,325
1,325
1,325
1,325
1,325
1,326
1,326
1,326
1,327
1,327
1,327
1,328
1,328
1,329
1,329
1,330

F (m)
0.05
0.09
0.14
0.21
0.28
0.37
0.47
0.58
0.70
0.83
0.97
1.13
1.30
1.47
1.67
1.87
2.08
2.31

Templado (Condicion de Mayor Duracion) 10C, S/V, EDS 18% Trotura


Minima Temperatura -10C, S/V , 60% Trotura
Mximo Esfuerzo (Maxima Velocidad del Viento) 0C, C/V 113 km/h, 60% Trotura
Flecha Mxima (maxima Temperatura) 50C, S/V, 60 % Trotura
Condicin de Falla (Maxima Carga de Hielo) -5C, C/V 35 km/h, e=3mm, 60 % Trotura

H (N)
1,858
1,894
1,935
1,976
2,019
2,060
2,100
2,137
2,173
2,207
2,238
2,268
2,295
2,321
2,344
2,366
2,387
2,406

HIPOTESIS II
T (N)
F (m)
1,859
0.08
1,895
0.13
1,936
0.20
1,978
0.29
2,020
0.38
2,062
0.49
2,103
0.61
2,141
0.73
2,178
0.87
2,212
1.02
2,244
1.18
2,275
1.36
2,303
1.54
2,329
1.73
2,354
1.93
2,377
2.15
2,399
2.37
2,419
2.61

H (N)
668
726
780
828
871
910
945
977
1,005
1,031
1,053
1,074
1,093
1,110
1,125
1,139
1,152
1,163

HIPOTESIS III
T (N)
F (m)
669
0.10
727
0.17
780
0.24
829
0.33
872
0.43
912
0.54
947
0.65
979
0.78
1,007
0.92
1,033
1.07
1,056
1.22
1,078
1.39
1,097
1.57
1,114
1.76
1,130
1.96
1,144
2.17
1,157
2.39
1,170
2.62

H (N)
1,331
1,336
1,341
1,347
1,352
1,358
1,363
1,368
1,372
1,376
1,380
1,384
1,387
1,389
1,392
1,394
1,396
1,398

HIPOTESIS IV
T (N)
F (m)
1,331
0.06
1,336
0.10
1,341
0.15
1,347
0.22
1,353
0.30
1,359
0.39
1,364
0.49
1,369
0.60
1,374
0.72
1,379
0.86
1,383
1.00
1,387
1.16
1,390
1.33
1,393
1.51
1,396
1.70
1,399
1.90
1,402
2.12
1,404
2.34

Pg. 18

ANEXO N 3.1.10
CLCULO MECNICO DE CONDUCTORES AUTOPORTANTES
3x35+N25, EDS - 18%
Conductor 3x25 + N25
Seccin 25,00mm2
Diametro Exterior 20mm
Peso Unitario 3,293 N/m
Tiro de Rotura 7356,86 N

Vano
[m]
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100

H (N)
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324
1,324

Hiptesis I :
Hiptesis II :
Hiptesis III :
Hiptesis IV :
Hiptesis V :

HIPOTESIS I
T (N)
1,325
1,325
1,325
1,326
1,326
1,327
1,327
1,328
1,329
1,330
1,331
1,332
1,333
1,334
1,336
1,337
1,339
1,340

F (m)
0.09
0.16
0.24
0.35
0.47
0.62
0.79
0.97
1.17
1.40
1.64
1.90
2.18
2.48
2.80
3.14
3.50
3.88

Templado (Condicion de Mayor Duracion) 10C, S/V, EDS 18% Trotura


Minima Temperatura -10C, S/V , 60% Trotura
Mximo Esfuerzo (Maxima Velocidad del Viento) 0C, C/V 113 km/h, 60% Trotura
Flecha Mxima (maxima Temperatura) 50C, S/V, 60 % Trotura
Condicin de Falla (Maxima Carga de Hielo) -5C, C/V 35 km/h, e=3mm, 60 % Trotura

H (N)
1,853
1,882
1,911
1,939
1,964
1,986
2,006
2,024
2,039
2,052
2,064
2,074
2,082
2,090
2,097
2,103
2,108
2,113

HIPOTESIS II
T (N)
F (m)
1,854
0.10
1,883
0.18
1,913
0.27
1,941
0.39
1,967
0.52
1,991
0.68
2,012
0.85
2,031
1.04
2,047
1.25
2,062
1.47
2,075
1.72
2,087
1.99
2,098
2.27
2,107
2.57
2,116
2.90
2,124
3.24
2,132
3.60
2,139
3.98

H (N)
782
860
925
980
1,025
1,063
1,095
1,123
1,146
1,165
1,182
1,197
1,209
1,220
1,230
1,238
1,245
1,252

HIPOTESIS III
T (N)
F (m)
783
0.15
861
0.24
927
0.35
982
0.47
1,028
0.61
1,066
0.77
1,099
0.95
1,127
1.14
1,151
1.36
1,172
1.59
1,190
1.84
1,205
2.10
1,219
2.39
1,231
2.70
1,242
3.02
1,252
3.36
1,261
3.73
1,269
4.11

H (N)
1,333
1,338
1,343
1,348
1,351
1,355
1,358
1,360
1,362
1,364
1,365
1,366
1,367
1,368
1,369
1,370
1,370
1,371

HIPOTESIS IV
T (N)
F (m)
1,334
0.09
1,339
0.16
1,344
0.25
1,349
0.36
1,354
0.48
1,358
0.63
1,361
0.80
1,364
0.98
1,367
1.19
1,370
1.41
1,372
1.65
1,374
1.91
1,377
2.20
1,379
2.50
1,381
2.82
1,383
3.16
1,385
3.52
1,387
3.90

4. CLCULOS MECNICOS DE POSTES


4.1 OBJETO
Estos Clculos tienen por objeto determinar las cargas mecnicas en postes,
cables de retenida y sus accesorios, de tal manera que en las condiciones
ms crticas, no se supere los esfuerzos mximos previstos en el Cdigo
Nacional de Electricidad Suministro y complementariamente en las Normas
Internacionales sealadas en el captulo 1.
4.2 FACTORES DE SEGURIDAD
Los factores de seguridad mnimas respecto a las cargas de rotura sern las
siguientes:
a) En condiciones normales
Poste de concreto
Mnsula de concreto

2
2.5

b) En condiciones anormales con rotura de conductor En lneas y redes


primarias de electrificacin rural, no se considera hiptesis de rotura de
conductor.

Pg. 19

4.3 FRMULAS APLICABLES

Momento debido a la carga del viento sobre los conductores:


MVC = (PV) (d) (C) (hi) Cos (/2)

Momento debido a la carga de los conductores:


MTC = 2 (TC) (hi) Sen ( /2)

Momento debido a la carga de los conductores en estructuras


terminales:
MTR = TC (hi)

Momento debido a la carga del viento sobre la estructura


MVP = [(Pv) (hl) 2 (Dm + 2 Do) ] 600

Momento debido al desequilibrio de cargas verticales


MCW = (BC) [(WC) (d) (Kr) + WCA + WAD]

Momento total para hiptesis de condiciones normales, en estructura de


alineamiento, sin retenidas:
MRN = MVC + MTC + MCW + MVP

Momento total en estructuras terminales


MRN = MTC + MVP

Esfuerzo del poste de madera en la lnea de empotramiento, en hiptesis


de condiciones normales:

Carga crtica en el poste de madera debida a cargas de compresin:

Deflexin Mxima del Poste de Madera:

Pg. 20

Carga en la punta del poste de concreto, en hiptesis de condiciones


normales:

Esfuerzo a la flexin en crucetas de madera:

4.4 SIMBOLOGA
Pv
= Presin del viento sobre superficies cilndricas, en Pa
D
= Longitud del vano-viento, en m
Tc
= Carga del conductor, en N
c
= Dimetro del conductor, en m

Angulo de desvo topogrfico, en grados


Do
= Dimetro del poste en la cabeza, en cm
Dm = Dimetro del poste en la lnea de empotramiento, en cm
Hl
= Altura libre del poste, en m
Hi
= Altura de la carga i en la estructura con respecto al terreno, en m
Bc
= Brazo de la cruceta, en m
hA
= Altura del conductor roto, respecto al terreno, en m
Bc
= Brazo de la cruceta, en m
Kr
= Relacin entre el vano-peso y vano-viento
Rc
=
Factor de reduccin de la carga del conductor por rotura: 0,5
(segn CNE)
Wc =
Peso del conductor, en N/m
WCA =
Peso del aislador tipo Pin o cadena de aisladores, en N
WAD =
Peso de un hombre con herramientas, igual a 1 000 N
C
=
Circunferencia del poste en la lnea de empotramiento en cm
E
=
Mdulo de Elasticidad del poste, en N/cm
I
=
Momento de inercia del poste, en cm
K
=
Factor que depende de la forma de fijacin de los extremos del
poste
L
=
Altura respecto al suelo del punto de aplicacin de la retenida
Hc
=
Lado de cruceta paralelo a la carga, en cm
B
=
Lado de cruceta perpendicular a la carga, en cm
QV = Sumatoria de cargas verticales, en N (incluye peso de aislador,
conductor y de 1 hombre con herramientas).
Los resultados obtenidos se presentan en los siguientes cuadros:

Pg. 21

CALCULO MECANICO DE ESTRUCTURAS EN REDES SECUNDARIAS


Datos de los Conductores:
3x35/25

Datos del Poste:

Especificacin: Armado E - 1
Tipo de Estructura: Alineamiento y Angulo 0 - 30

CONDUCTOR

Velocidad del viento:

Km/h

113

Diametro:

Presin del viento

Pv

N/m

231.76

Peso Unitario:

Wc

Angulo de retenida:

Ar

grad.

30

Vano Viento

Vv

Vv

Carga de retenida:

Crr

30920

Vano Peso:

Vp

1,1Vv

Angulo de Desvio:

Ang.

grad

Altura de aplicacin de fuerzas:

Ha

7.8

Seccin:

Longitud del poste

hp

Datos del Macizo


m

Altura

0.8

KN

1.96

arista 1

0.50

25

Esfuerzo en la punta

mm

20

Longitud de empotramiento

Le

0.8

Arista 2

N/m

0.419

Altura util del poste

6.9

Peso especifico

Kg/m3

2400

Distancia con respecto a la punta

0.3

Peso del Macizo

3682.28

Diametro en la punta

Do

0.12

Pto. De volteo

0.45

Diametro de empotramiento

Dm

0.24

Peso del Equipo

98.1

Factor de seguridad

Fs

mm

F.V.

113

339.314

Peso del poste

Pp

4508

Carga en la punta

Cr

2000

Puntos de aplicacin de las fuerzas horizontales


en el poste de CAC con respecto al macizo
Fuerzas Horizontales en el Poste

MOMENTO EN CONDICIONES NORMALES

MOMENTOS EN CONDICIONES DE ROTURA DEL CONDUCTOR

MVP

MVC

MTC

MRN

Qn

M.T.

M.f.

M.T.E.

(N-m)

M.R.F.

Qr

W.EQUIPO

W.MACIZO

W.POSTE

TOTAL

Longitud de Aplicacin
m

4.396

FVC

Variable

7.4

TC

Variable

7.4

RETENIDA

CARGAS VERTICALES

Vano Viento

287.85

MOMENTOS ACTUANTES

ANGULO
TOPOGRAFICO

0.50

FVP

V(Km/h)

MOMENTO

MOMENTO

TIRO

RESISTENTE

VOLTEO

REQUIERE HORIZONTAL VERTICAL

(m)

(N)

(N-m)

(N-m)

(N-m)

(N-m)

(N)

C.S>=2

(N-m)

(N-m)

(N-m)

(N)

CS>=2

(N)

(N)

(N)

(N)

(N-m)

(N-m)

RETENIDA

2.00

1817.96

1035.09

5.53

1046.74

2087.36

306.96

6.52

2.76

2.76

2090.12

307.37

6.51

98.10

3682.28

4508.00

8288.38

3729.77

2445.18

NO

4.00

1823.48

1035.09

11.05

1049.92

2096.06

308.24

6.49

5.53

5.53

2101.59

309.06

6.47

98.10

3682.28

4508.00

8288.38

3729.77

2454.94

NO

6.00

1832.2

1035.09

16.58

1054.94

2106.61

309.80

6.46

8.29

8.29

2114.90

311.01

6.43

98.10

3682.28

4508.00

8288.38

3729.77

2466.76

NO

8.00

1843.5

1035.09

22.10

1061.44

2118.64

311.56

6.42

11.05

11.05

2129.69

313.19

6.39

98.10

3682.28

4508.00

8288.38

3729.77

2480.25

NO

10.00

1856.72

1035.09

27.63

1069.05

2131.78

313.50

6.38

13.81

13.81

2145.59

315.53

6.34

98.10

3682.28

4508.00

8288.38

3729.77

2494.98

NO

12.00

1871.18

1035.09

33.15

1077.38

2145.63

315.53

6.34

16.58

16.58

2162.20

317.97

6.29

98.10

3682.28

4508.00

8288.38

3729.77

2510.51

NO

14.00

1886.33

1035.09

38.68

1086.10

2159.88

317.63

6.30

19.34

19.34

2179.22

320.47

6.24

98.10

3682.28

4508.00

8288.38

3729.77

2526.49

NO

16.00

1901.68

1035.09

44.20

1094.94

2174.24

319.74

6.26

22.10

22.10

2196.34

322.99

6.19

98.10

3682.28

4508.00

8288.38

3729.77

2542.59

NO

18.00

1916.89

1035.09

49.73

1103.70

2188.52

321.84

6.21

24.86

24.86

2213.39

325.50

6.14

98.10

3682.28

4508.00

8288.38

3729.77

2558.61

NO

20.00

1931.7

1035.09

55.26

1112.23

2202.58

323.91

6.17

27.63

27.63

2230.20

327.97

6.10

98.10

3682.28

4508.00

8288.38

3729.77

2574.37

NO

22.00

1945.94

1035.09

60.78

1120.43

2216.30

325.93

6.14

30.39

30.39

2246.69

330.40

6.05

98.10

3682.28

4508.00

8288.38

3729.77

2589.75

NO

24.00

1959.48

1035.09

66.31

1128.22

2229.62

327.89

6.10

33.15

33.15

2262.77

332.76

6.01

98.10

3682.28

4508.00

8288.38

3729.77

2604.69

NO

26.00

1972.28

1035.09

71.83

1135.59

2242.52

329.78

6.06

35.92

35.92

2278.43

335.06

5.97

98.10

3682.28

4508.00

8288.38

3729.77

2619.15

NO

28.00

1984.29

1035.09

77.36

1142.51

2254.96

331.61

6.03

38.68

38.68

2293.64

337.30

5.93

98.10

3682.28

4508.00

8288.38

3729.77

2633.10

NO

30.00

1995.53

1035.09

82.88

1148.98

2266.96

333.38

6.00

41.44

41.44

2308.40

339.47

5.89

98.10

3682.28

4508.00

8288.38

3729.77

2646.55

NO

32.00

2006.01

1035.09

88.41

1155.01

2278.51

335.08

5.97

44.20

44.20

2322.72

341.58

5.86

98.10

3682.28

4508.00

8288.38

3729.77

2659.51

NO

34.00

2015.76

1035.09

93.93

1160.63

2289.65

336.71

5.94

46.97

46.97

2336.62

343.62

5.82

98.10

3682.28

4508.00

8288.38

3729.77

2672.00

NO

36.00

2024.82

1035.09

99.46

1165.84

2300.40

338.29

5.91

49.73

49.73

2350.13

345.61

5.79

98.10

3682.28

4508.00

8288.38

3729.77

2684.04

NO

38.00

2033.22

1035.09

104.99

1170.68

2310.76

339.82

5.89

52.49

52.49

2363.25

347.54

5.75

98.10

3682.28

4508.00

8288.38

3729.77

2695.66

NO

40.00

2041.01

1035.09

110.51

1175.16

2320.77

341.29

5.86

55.26

55.26

2376.02

349.42

5.72

98.10

3682.28

4508.00

8288.38

3729.77

2706.89

NO

42.00

2048.22

1035.09

116.04

1179.32

2330.45

342.71

5.84

58.02

58.02

2388.46

351.24

5.69

98.10

3682.28

4508.00

8288.38

3729.77

2717.74

NO

44.00

2054.91

1035.09

121.56

1183.17

2339.82

344.09

5.81

60.78

60.78

2400.60

353.03

5.67

98.10

3682.28

4508.00

8288.38

3729.77

2728.25

NO

46.00

2061.11

1035.09

127.09

1186.74

2348.92

345.43

5.79

63.54

63.54

2412.46

354.77

5.64

98.10

3682.28

4508.00

8288.38

3729.77

2738.45

NO

48.00

2066.86

1035.09

132.61

1190.05

2357.75

346.73

5.77

66.31

66.31

2424.06

356.48

5.61

98.10

3682.28

4508.00

8288.38

3729.77

2748.35

NO

50.00

2072.2

1035.09

138.14

1193.12

2366.36

347.99

5.75

69.07

69.07

2435.42

358.15

5.58

98.10

3682.28

4508.00

8288.38

3729.77

2758.00

NO

(N)

TIRO

(N)

TIRO
CABLE
(N)

C.S>2

Pg. 22

CALCULO MECANICO DE ESTRUCTURAS EN REDES SECUNDARIAS

Especificacin: Armado E - 2
Tipo de Estructura: Fin de Lnea (Vano normal)

CONDUCTOR

Datos de los Conductores:


3x35/25

Seccin:

mm

Datos del Poste:


Longitud del poste

hp

25

Esfuerzo en la punta

Datos del Macizo


m

Altura

0.9

KN

1.96

arista 1

0.50

Velocidad del viento:

Km/h

113

Diametro:

mm

20

Longitud de empotramiento

Le

0.8

Arista 2

Presin del viento

Pv

N/m

231.76

Peso Unitario:

Wc

N/m

0.419

Altura util del poste

Peso especifico

Angulo de retenida:

Ar

grad.

30

Vano Viento

Vv

1Vv

Distancia con respecto a la punta

0.2

Carga de retenida:

Crr

30920

Vano Peso:

Vp

1,1Vv

Diametro en la punta

Do

0.12

Angulo de Desvio:

Ang.

grad

Diametro de empotramiento

Dm

0.24

Altura de aplicacin de fuerzas:

Ha

7.8

Factor de seguridad

Fs

F.V.

0.50

Kg/m3

2400

Peso del Macizo

4270.88

Pto. De volteo

0.45

Peso del Equipo

98.1

2
N

339.314

Peso del poste

Pp

4508

Carga en la punta

Cr

3000

Puntos de aplicacin de las fuerzas horizontales


en el poste de CAC con respecto al macizo
Fuerzas Horizontales en el Poste
FVP

V(Km/h)
113

4.496

FVC

Variable

7.6

TC

Variable

7.6

MOMENTOS ACTUANTES

ANGULO
MOMENTO EN CONDICIONES NORMALES

TOPOGRAFICO

MOMENTOS EN CONDICIONES DE ROTURA DEL CONDUCTOR

MVP

MVC

MTC

MRN

Qn

M.T.

M.f.

M.T.E.

M.R.F.

Qr

(N-m)

(N-m)

(N)

C.S>=2 (N-m)

(N-m)

(N-m)

(N-m)

(N)

RETENIDA

CARGAS VERTICALES

60

Vano Viento

292.02

Longitud de Aplicacin

MOMENTO

MOMENTO

TIRO

W.EQUIPO

W.MACIZO

W.POSTE

TOTAL

RESISTENTE

VOLTEO

REQUIERE HORIZONTAL VERTICAL

CS>=2

(N)

(N)

(N)

(N)

(N-m)

(N-m)

RETENIDA

(m)

(N)

(N-m)

(N-m)

2.00

1817.96

1050.10

5.69

1078.46 2134.25 309.31 9.70

2.85

2.85

2137.09 309.72

9.69

98.10

4270.88

4508.00 8876.98

3994.64

2524.61

NO

4.00

1823.48

1050.10 11.39

1081.73 2143.21 310.61 9.66

5.69

5.69

2148.91 311.44

9.63

98.10

4270.88

4508.00 8876.98

3994.64

2534.63

NO

6.00

1832.20

1050.10 17.08

1086.90 2154.08 312.19 9.61

8.54

8.54

2162.62 313.42

9.57

98.10

4270.88

4508.00 8876.98

3994.64

2546.77

NO

8.00

1843.50

1050.10 22.77

1093.61 2166.48 313.98 9.55

11.39

11.39

2177.86 315.63

9.50

98.10

4270.88

4508.00 8876.98

3994.64

2560.63

NO

10.00

1856.72

1050.10 28.46

1101.45 2180.01 315.94 9.50

14.23

14.23

2194.24 318.01

9.43

98.10

4270.88

4508.00 8876.98

3994.64

2575.76

NO

12.00

1871.18

1050.10 34.16

1110.03 2194.28 318.01 9.43

17.08

17.08

2211.36 320.49

9.36

98.10

4270.88

4508.00 8876.98

3994.64

2591.71

NO

14.00

1886.33

1050.10 39.85

1119.02 2208.96 320.14 9.37

19.93

19.93

2228.89 323.03

9.29

98.10

4270.88

4508.00 8876.98

3994.64

2608.11

NO

16.00

1901.68

1050.10 45.54

1128.12 2223.76 322.28 9.31

22.77

22.77

2246.53 325.58

9.21

98.10

4270.88

4508.00 8876.98

3994.64

2624.65

NO

18.00

1916.89

1050.10 51.24

1137.14 2238.48 324.42 9.25

25.62

25.62

2264.09 328.13

9.14

98.10

4270.88

4508.00 8876.98

3994.64

2641.10

NO

20.00

1931.70

1050.10 56.93

1145.93 2252.96 326.52 9.19

28.46

28.46

2281.42 330.64

9.07

98.10

4270.88

4508.00 8876.98

3994.64

2657.28

NO

22.00

1945.94

1050.10 62.62

1154.38 2267.10 328.56 9.13

31.31

31.31

2298.41 333.10

9.01

98.10

4270.88

4508.00 8876.98

3994.64

2673.09

NO

24.00

1959.48

1050.10 68.32

1162.41 2280.82 330.55 9.08

34.16

34.16

2314.98 335.50

8.94

98.10

4270.88

4508.00 8876.98

3994.64

2688.43

NO

26.00

1972.28

1050.10 74.01

1170.00 2294.11 332.48 9.02

37.00

37.00

2331.11 337.84

8.88

98.10

4270.88

4508.00 8876.98

3994.64

2703.28

NO

28.00

1984.29

1050.10 79.70

1177.13 2306.92 334.34 8.97

39.85

39.85

2346.78 340.11

8.82

98.10

4270.88

4508.00 8876.98

3994.64

2717.60

NO

30.00

1995.53

1050.10 85.39

1183.80 2319.29 336.13 8.93

42.70

42.70

2361.98 342.32

8.76

98.10

4270.88

4508.00 8876.98

3994.64

2731.42

NO

32.00

2006.01

1050.10 91.09

1190.01 2331.20 337.85 8.88

45.54

45.54

2376.74 344.45

8.71

98.10

4270.88

4508.00 8876.98

3994.64

2744.73

NO

34.00

2015.76

1050.10 96.78

1195.80 2342.67 339.52 8.84

48.39

48.39

2391.06 346.53

8.66

98.10

4270.88

4508.00 8876.98

3994.64

2757.56

NO

36.00

2024.82

1050.10 102.47 1201.17 2353.74 341.12 8.79

51.24

51.24

2404.98 348.55

8.61

98.10

4270.88

4508.00 8876.98

3994.64

2769.93

NO

38.00

2033.22

1050.10 108.17 1206.15 2364.42 342.67 8.75

54.08

54.08

2418.50 350.51

8.56

98.10

4270.88

4508.00 8876.98

3994.64

2781.86

NO

40.00

2041.01

1050.10 113.86 1210.78 2374.73 344.16 8.72

56.93

56.93

2431.66 352.41

8.51

98.10

4270.88

4508.00 8876.98

3994.64

2793.39

NO

42.00

2048.22

1050.10 119.55 1215.05 2384.70 345.61 8.68

59.78

59.78

2444.48 354.27

8.47

98.10

4270.88

4508.00 8876.98

3994.64

2804.53

NO

44.00

2054.91

1050.10 125.25 1219.02 2394.36 347.01 8.65

62.62

62.62

2456.98 356.08

8.42

98.10

4270.88

4508.00 8876.98

3994.64

2815.33

NO

46.00

2061.11

1050.10 130.94 1222.70 2403.73 348.37 8.61

65.47

65.47

2469.20 357.86

8.38

98.10

4270.88

4508.00 8876.98

3994.64

2825.80

NO

48.00

2066.86

1050.10 136.63 1226.11 2412.84 349.69 8.58

68.32

68.32

2481.15 359.59

8.34

98.10

4270.88

4508.00 8876.98

3994.64

2835.98

NO

50.00

2072.20

1050.10 142.32 1229.28 2421.70 350.97 8.55

71.16

71.16

2492.86 361.28

8.30

98.10

4270.88

4508.00 8876.98

3994.64

2845.88

NO

(N)

TIRO

(N)

TIRO
CABLE
(N)

C.S>2

Pg. 23

CALCULO MECANICO DE ESTRUCTURAS EN REDES SECUNDARIAS

Especificacin: Armado E - 3
Tipo de Estructura: Fin de Lnea (Vano normal)

CONDUCTOR

Datos de los Conductores:


3x35/25

Seccin:

mm

Datos del Poste:


Longitud del poste

hp

Datos del Macizo


m

Altura

KN

1.96

arista 1

0.50

25

Esfuerzo en la punta
Longitud de empotramiento

Le

0.8

Arista 2

0.50

Altura util del poste

Peso especifico

Kg/m3

2400

Distancia con respecto a la punta

0.2

Peso del Macizo

4859.48

Velocidad del viento:

Km/h

113

Diametro:

mm

20

Presin del viento

Pv

N/m

231.76

Peso Unitario:

Wc

N/m

0.419

Angulo de retenida:

Ar

grad.

30

Vano Viento

Vv

Vv

Carga de retenida:

Crr

30920

Vano Peso:

Vp

1,1Vv

Diametro en la punta

Do

0.12

Pto. De volteo

0.45

Angulo de Desvio:

Ang.

grad

60

Diametro de empotramiento

Dm

0.24

Peso del Equipo

98.1

Altura de aplicacin de fuerzas:

Ha

7.8

Factor de seguridad

Fs

F.V.

2
N

339.314

Peso del poste

Pp

4508

Carga en la punta

Cr

3000

Puntos de aplicacin de las fuerzas horizontales


en el poste de CAC con respecto al macizo
Fuerzas Horizontales en el Poste
FVP

V(Km/h)
113

MOMENTO EN CONDICIONES NORMALES

TOPOGRAFICO

MOMENTOS EN CONDICIONES DE ROTURA DEL CONDUCTOR

4.596

Variable

7.7

TC

Variable

7.7

MVP

MVC

MTC

MRN

Qn

M.T.

M.f.

M.T.E.

M.R.F.

Qr

(N-m)

(N-m)

(N)

C.S>=2 (N-m)

(N-m)

(N-m)

(N-m)

(N)

CS>=2

RETENIDA

CARGAS VERTICALES

60

Longitud de Aplicacin

FVC

MOMENTOS ACTUANTES

ANGULO

Vano Viento

292.02

MOMENTO

MOMENTO

TIRO

W.EQUIPO

W.MACIZO

W.POSTE

TOTAL

RESISTENTE

VOLTEO

REQUIERE HORIZONTAL VERTICAL

TIRO

TIRO

(N)

(N)

(N)

(N)

(N-m)

(N-m)

RETENIDA

(N)

(N)

(N)

C.S>2

CABLE

(m)

(N)

(N-m)

(N-m)

2.00

1817.96

1050.10

4.93

12362.13 13417.16 1944.52 1.54

2.47

2.47

13419.63 1944.87 1.54

98.10

4859.48

4508.00 9465.58

4259.51

15345.99

SI

2129.71

3688.76

4259.42

7.26

4.00

1823.48

1050.10

9.87

12399.66 13459.63 1950.67 1.54

4.93

4.93

13464.56 1951.39 1.54

98.10

4859.48

4508.00 9465.58

4259.51

15394.09

SI

2136.45

3700.44

4272.90

7.24

6.00

1832.20

1050.10 14.80 12458.96 13523.86 1959.98 1.53

7.40

7.40

13531.26 1961.05 1.53

98.10

4859.48

4508.00 9465.58

4259.51

15466.82

SI

2146.64

3718.10

4293.29

7.20

8.00

1843.50

1050.10 19.74 12535.80 13605.64 1971.83 1.52

9.87

9.87

13615.51 1973.26 1.52

98.10

4859.48

4508.00 9465.58

4259.51

15559.42

SI

2159.62

3740.58

4319.25

7.16

10.00

1856.72

1050.10 24.67 12625.70 13700.47 1985.57 1.51

12.34

12.34 13712.80 1987.36 1.51

98.10

4859.48

4508.00 9465.58

4259.51

15666.80

SI

2174.68

3766.65

4349.35

7.11

12.00

1871.18

1050.10 29.61 12724.02 13803.73 2000.54 1.50

14.80

14.80 13818.53 2002.69 1.50

98.10

4859.48

4508.00 9465.58

4259.51

15783.73

SI

2191.07

3795.04

4382.14

7.06

14.00

1886.33

1050.10 34.54 12827.04 13911.68 2016.19 1.49

17.27

17.27 13928.96 2018.69 1.49

98.10

4859.48

4508.00 9465.58

4259.51

15905.97

SI

2208.20

3824.72

4416.41

7.00

16.00

1901.68

1050.10 39.48 12931.42 14021.00 2032.03 1.48

19.74

19.74 14040.74 2034.89 1.47

98.10

4859.48

4508.00 9465.58

4259.51

16029.75

SI

2225.56

3854.78

4451.11

6.95

18.00

1916.89

1050.10 44.41 13034.85 14129.36 2047.73 1.47

22.21

22.21 14151.57 2050.95 1.46

98.10

4859.48

4508.00 9465.58

4259.51

16152.46

SI

2242.76

3884.57

4485.51

6.89

20.00

1931.70

1050.10 49.35 13135.56 14235.00 2063.04 1.45

24.67

24.67 14259.68 2066.62 1.45

98.10

4859.48

4508.00 9465.58

4259.51

16272.08

SI

2259.52

3913.61

4519.05

6.84

22.00

1945.94

1050.10 54.28 13232.39 14336.77 2077.79 1.44

27.14

27.14 14363.91 2081.73 1.44

98.10

4859.48

4508.00 9465.58

4259.51

16387.32

SI

2275.68

3941.59

4551.36

6.79

24.00

1959.48

1050.10 59.22 13324.46 14433.78 2091.85 1.43

29.61

29.61 14463.39 2096.14 1.43

98.10

4859.48

4508.00 9465.58

4259.51

16497.17

SI

2291.08

3968.26

4582.15

6.75

26.00

1972.28

1050.10 64.15 13411.50 14525.75 2105.18 1.43

32.08

32.08 14557.83 2109.83 1.42

98.10

4859.48

4508.00 9465.58

4259.51

16601.31

SI

2305.68

3993.55

4611.35

6.71

28.00

1984.29

1050.10 69.09 13493.17 14612.36 2117.73 1.42

34.54

34.54 14646.90 2122.74 1.41

98.10

4859.48

4508.00 9465.58

4259.51

16699.38

SI

2319.42

4017.36

4638.84

6.67

30.00

1995.53

1050.10 74.02 13569.60 14693.72 2129.53 1.41

37.01

37.01 14730.74 2134.89 1.41

98.10

4859.48

4508.00 9465.58

4259.51

16791.52

SI

2332.34

4039.73

4664.67

6.63

32.00

2006.01

1050.10 78.96 13640.87 14769.92 2140.57 1.40

39.48

39.48 14809.40 2146.29 1.40

98.10

4859.48

4508.00 9465.58

4259.51

16877.80

SI

2344.43

4060.68

4688.86

6.59

34.00

2015.76

1050.10 83.89 13707.17 14841.16 2150.89 1.39

41.95

41.95 14883.10 2156.97 1.39

98.10

4859.48

4508.00 9465.58

4259.51

16958.46

SI

2355.74

4080.26

4711.48

6.56

36.00

2024.82

1050.10 88.83 13768.78 14907.70 2160.54 1.39

44.41

44.41 14952.12 2166.97 1.38

98.10

4859.48

4508.00 9465.58

4259.51

17033.81

SI

2366.30

4098.55

4732.60

6.53

38.00

2033.22

1050.10 93.76 13825.90 14969.76 2169.53 1.38

46.88

46.88 15016.64 2176.32 1.38

98.10

4859.48

4508.00 9465.58

4259.51

17104.08

SI

2376.15

4115.62

4752.30

6.51

40.00

2041.01

1050.10 98.70 13878.87 15027.66 2177.92 1.38

49.35

49.35 15077.01 2185.07 1.37

98.10

4859.48

4508.00 9465.58

4259.51

17169.65

SI

2385.34

4131.54

4770.69

6.48

42.00

2048.22

1050.10 103.63 13927.90 15081.63 2185.74 1.37

51.82

51.82 15133.44 2193.25 1.37

98.10

4859.48

4508.00 9465.58

4259.51

17230.76

SI

2393.91

4146.37

4787.82

6.46

44.00

2054.91

1050.10 108.57 13973.39 15132.05 2193.05 1.37

54.28

54.28 15186.34 2200.92 1.36

98.10

4859.48

4508.00 9465.58

4259.51

17287.86

SI

2401.91

4160.24

4803.83

6.44

46.00

2061.11

1050.10 113.50 14015.55 15179.15 2199.88 1.36

56.75

56.75 15235.90 2208.10 1.36

98.10

4859.48

4508.00 9465.58

4259.51

17341.19

SI

2409.39

4173.18

4818.78

6.42

48.00

2066.86

1050.10 118.44 14054.65 15223.18 2206.26 1.36

59.22

59.22 15282.40 2214.84 1.35

98.10

4859.48

4508.00 9465.58

4259.51

17391.05

SI

2416.38

4185.29

4832.76

6.40

50.00

2072.20

1050.10 123.37 14090.96 15264.43 2212.24 1.36

61.69

61.69 15326.12 2221.18 1.35

98.10

4859.48

4508.00 9465.58

4259.51

17437.76

SI

2422.93

4196.63

4845.85

6.38

Pg. 24

CALCULO MECANICO DE ESTRUCTURAS EN REDES SECUNDARIAS

Especificacin: Armado E - 4
Tipo de Estructura: Fin de Lnea (Vano normal)

CONDUCTOR

Datos de los Conductores:


3x35/25

Seccin:

mm

Datos del Poste:


Longitud del poste

hp

25

Esfuerzo en la punta

Datos del Macizo


m

Altura

1.1

KN

1.96

arista 1

0.50

Velocidad del viento:

Km/h

113

Diametro:

mm

20

Longitud de empotramiento

Le

0.8

Arista 2

Presin del viento

Pv

N/m

231.76

Peso Unitario:

Wc

N/m

0.419

Altura util del poste

Peso especifico

Angulo de retenida:

Ar

grad.

30

Vano Viento

Vv

1Vv

Distancia con respecto a la punta

0.2

Carga de retenida:

Crr

30920

Vano Peso:

Vp

1,1Vv

Diametro en la punta

Do

0.12

Angulo de Desvio:

Ang.

grad

Diametro de empotramiento

Dm

0.24

Altura de aplicacin de fuerzas:

Ha

7.8

Factor de seguridad

Fs

F.V.

0.50

Kg/m3

2400

Peso del Macizo

5448.08

Pto. De volteo

0.45

Peso del Equipo

98.1

2
N

339.314

Peso del poste

Pp

4508

Carga en la punta

Cr

3000

Puntos de aplicacin de las fuerzas horizontales


en el poste de CAC con respecto al macizo
Fuerzas Horizontales en el Poste
FVP

V(Km/h)
113

4.696

FVC

Variable

7.8

TC

Variable

7.8

MOMENTOS ACTUANTES

ANGULO
MOMENTO EN CONDICIONES NORMALES

TOPOGRAFICO

MOMENTOS EN CONDICIONES DE ROTURA DEL CONDUCTOR

MVP

MVC

MTC

MRN

Qn

M.T.

M.f.

M.T.E.

M.R.F.

Qr

(N-m)

(N-m)

(N)

C.S>=2 (N-m)

(N-m)

(N-m)

(N-m)

(N)

RETENIDA

CARGAS VERTICALES

60

Vano Viento

292.02

Longitud de Aplicacin

MOMENTO

MOMENTO

TIRO

W.EQUIPO

W.MACIZO

W.POSTE

TOTAL

RESISTENTE

VOLTEO

REQUIERE HORIZONTAL VERTICAL

CS>=2

(N)

(N)

(N)

(N)

(N-m)

(N-m)

RETENIDA

(m)

(N)

(N-m)

(N-m)

2.00

1817.96

1050.10

5.69

1078.46 2134.25 309.31 9.70

2.85

2.85

2137.09 309.72

9.69

98.10

5448.08

4508.00 10054.18

4524.38

2614.90

NO

4.00

1823.48

1050.10 11.39

1081.73 2143.21 310.61 9.66

5.69

5.69

2148.91 311.44

9.63

98.10

5448.08

4508.00 10054.18

4524.38

2625.18

NO

6.00

1832.20

1050.10 17.08

1086.90 2154.08 312.19 9.61

8.54

8.54

2162.62 313.42

9.57

98.10

5448.08

4508.00 10054.18

4524.38

2637.65

NO

8.00

1843.50

1050.10 22.77

1093.61 2166.48 313.98 9.55

11.39

11.39

2177.86 315.63

9.50

98.10

5448.08

4508.00 10054.18

4524.38

2651.87

NO

10.00

1856.72

1050.10 28.46

1101.45 2180.01 315.94 9.50

14.23

14.23

2194.24 318.01

9.43

98.10

5448.08

4508.00 10054.18

4524.38

2667.39

NO

12.00

1871.18

1050.10 34.16

1110.03 2194.28 318.01 9.43

17.08

17.08

2211.36 320.49

9.36

98.10

5448.08

4508.00 10054.18

4524.38

2683.76

NO

14.00

1886.33

1050.10 39.85

1119.02 2208.96 320.14 9.37

19.93

19.93

2228.89 323.03

9.29

98.10

5448.08

4508.00 10054.18

4524.38

2700.60

NO

16.00

1901.68

1050.10 45.54

1128.12 2223.76 322.28 9.31

22.77

22.77

2246.53 325.58

9.21

98.10

5448.08

4508.00 10054.18

4524.38

2717.58

NO

18.00

1916.89

1050.10 51.24

1137.14 2238.48 324.42 9.25

25.62

25.62

2264.09 328.13

9.14

98.10

5448.08

4508.00 10054.18

4524.38

2734.46

NO

20.00

1931.70

1050.10 56.93

1145.93 2252.96 326.52 9.19

28.46

28.46

2281.42 330.64

9.07

98.10

5448.08

4508.00 10054.18

4524.38

2751.07

NO

22.00

1945.94

1050.10 62.62

1154.38 2267.10 328.56 9.13

31.31

31.31

2298.41 333.10

9.01

98.10

5448.08

4508.00 10054.18

4524.38

2767.29

NO

24.00

1959.48

1050.10 68.32

1162.41 2280.82 330.55 9.08

34.16

34.16

2314.98 335.50

8.94

98.10

5448.08

4508.00 10054.18

4524.38

2783.03

NO

26.00

1972.28

1050.10 74.01

1170.00 2294.11 332.48 9.02

37.00

37.00

2331.11 337.84

8.88

98.10

5448.08

4508.00 10054.18

4524.38

2798.27

NO

28.00

1984.29

1050.10 79.70

1177.13 2306.92 334.34 8.97

39.85

39.85

2346.78 340.11

8.82

98.10

5448.08

4508.00 10054.18

4524.38

2812.97

NO

30.00

1995.53

1050.10 85.39

1183.80 2319.29 336.13 8.93

42.70

42.70

2361.98 342.32

8.76

98.10

5448.08

4508.00 10054.18

4524.38

2827.15

NO

32.00

2006.01

1050.10 91.09

1190.01 2331.20 337.85 8.88

45.54

45.54

2376.74 344.45

8.71

98.10

5448.08

4508.00 10054.18

4524.38

2840.81

NO

34.00

2015.76

1050.10 96.78

1195.80 2342.67 339.52 8.84

48.39

48.39

2391.06 346.53

8.66

98.10

5448.08

4508.00 10054.18

4524.38

2853.98

NO

36.00

2024.82

1050.10 102.47 1201.17 2353.74 341.12 8.79

51.24

51.24

2404.98 348.55

8.61

98.10

5448.08

4508.00 10054.18

4524.38

2866.67

NO

38.00

2033.22

1050.10 108.17 1206.15 2364.42 342.67 8.75

54.08

54.08

2418.50 350.51

8.56

98.10

5448.08

4508.00 10054.18

4524.38

2878.92

NO

40.00

2041.01

1050.10 113.86 1210.78 2374.73 344.16 8.72

56.93

56.93

2431.66 352.41

8.51

98.10

5448.08

4508.00 10054.18

4524.38

2890.75

NO

42.00

2048.22

1050.10 119.55 1215.05 2384.70 345.61 8.68

59.78

59.78

2444.48 354.27

8.47

98.10

5448.08

4508.00 10054.18

4524.38

2902.19

NO

44.00

2054.91

1050.10 125.25 1219.02 2394.36 347.01 8.65

62.62

62.62

2456.98 356.08

8.42

98.10

5448.08

4508.00 10054.18

4524.38

2913.27

NO

46.00

2061.11

1050.10 130.94 1222.70 2403.73 348.37 8.61

65.47

65.47

2469.20 357.86

8.38

98.10

5448.08

4508.00 10054.18

4524.38

2924.02

NO

48.00

2066.86

1050.10 136.63 1226.11 2412.84 349.69 8.58

68.32

68.32

2481.15 359.59

8.34

98.10

5448.08

4508.00 10054.18

4524.38

2934.46

NO

50.00

2072.20

1050.10 142.32 1229.28 2421.70 350.97 8.55

71.16

71.16

2492.86 361.28

8.30

98.10

5448.08

4508.00 10054.18

4524.38

2944.62

NO

(N)

TIRO

(N)

TIRO
CABLE
(N)

C.S>2

Pg. 25

CALCULO MECANICO DE ESTRUCTURAS EN REDES SECUNDARIAS

Especificacin: Armado E - 5
Tipo de Estructura: Fin de Lnea (Vano normal)

CONDUCTOR

Datos de los Conductores:


3x35/25

Seccin:

mm

Datos del Poste:


Longitud del poste

hp

25

Esfuerzo en la punta

Datos del Macizo


m

Altura

0.9

KN

1.98

arista 1

0.50

Velocidad del viento:

Km/h

Diametro:

mm

20

Longitud de empotramiento

Le

0.8

Arista 2

Presin del viento

Pv

N/m 231.76

Peso Unitario:

Wc

N/m

0.419

Altura util del poste

7.2

Peso especifico

Angulo de retenida:

Ar

grad.

30

Vano Viento

Vv

1Vv

Distancia con respecto a la punta

0.3

Carga de retenida:

Crr

30920

Vano Peso:

Vp

1,1Vv

Diametro en la punta

Do

0.12

Angulo de Desvio:

Ang.

grad

Diametro de empotramiento

Dm

0.24

Altura de aplicacin de fuerzas:

Ha

7.8

Factor de seguridad

Fs

113

F.V.

339.314

Peso del poste

Pp

4508

Carga en la punta

Cr

3000

113

Peso del Macizo

4270.88

Pto. De volteo

0.45

Peso del Equipo

98.1

Puntos de aplicacin de las fuerzas horizontales


en el poste de CAC con respecto al macizo
Fuerzas Horizontales en el Poste
FVP

300.36

MOMENTO EN CONDICIONES NORMALES

TOPOGRAFICO

MOMENTOS EN CONDICIONES DE ROTURA DEL CONDUCTOR

4.496

Variable

7.8

TC

Variable

7.8

MOMENTO
MVP

MVC

MTC

MRN

Qn

M.T.

M.f.

M.T.E.

M.R.F.

Qr

(N-m)

(N-m)

(N)

C.S>=2 (N-m)

(N-m)

(N-m)

(N-m)

(N)

RETENIDA

CARGAS VERTICALES

60
W.EQUIPO

W.MACIZO

CS>=2

(N)

(N)

W.POSTE TOTAL

RESISTENTE

MOMENTO

TIRO

(N-m)

RETENIDA

4508.00 8876.98

3994.64

2594.01

NO

4508.00 8876.98

3994.64

2604.29

NO

4270.88

4508.00 8876.98

3994.64

2616.76

NO

(N)

(N-m)

(N-m)

2.00

1817.96

1080.10

5.78

1094.32 2180.19 307.07 9.77

2.89

2.89

2183.08 307.48 9.76

98.10

4270.88

4.00

1823.48

1080.10 11.55

1097.64 2189.29 308.35 9.73

5.78

5.78

2195.07 309.16 9.70

98.10

4270.88

6.00

1832.20

1080.10 17.33

1102.89 2200.32 309.90 9.68

8.67

8.67

2208.98 311.12 9.64

98.10

(N)

(N)

TIRO

VOLTEO REQUIERE HORIZONTAL VERTICAL

(N-m)

(m)

Longitud de Aplicacin

FVC

MOMENTOS ACTUANTES

ANGULO

Vano Viento

0.50
2400

V(Km/h)

m
Kg/m3

8.00

1843.50

1080.10 23.11

1109.69 2212.90 311.68 9.63

11.55

11.55

2224.45 313.30 9.58

98.10

4270.88

4508.00 8876.98

3994.64

2630.98

NO

10.00

1856.72

1080.10 28.88

1117.65 2226.63 313.61 9.57

14.44

14.44

2241.07 315.64 9.50

98.10

4270.88

4508.00 8876.98

3994.64

2646.50

NO

12.00

1871.18

1080.10 34.66

1126.35 2241.11 315.65 9.50

17.33

17.33

2258.44 318.09 9.43

98.10

4270.88

4508.00 8876.98

3994.64

2662.87

NO

14.00

1886.33

1080.10 40.44

1135.47 2256.01 317.75 9.44

20.22

20.22

2276.23 320.60 9.36

98.10

4270.88

4508.00 8876.98

3994.64

2679.71

NO

16.00

1901.68

1080.10 46.21

1144.71 2271.02 319.86 9.38

23.11

23.11

2294.13 323.12 9.28

98.10

4270.88

4508.00 8876.98

3994.64

2696.69

NO

18.00

1916.89

1080.10 51.99

1153.87 2285.96 321.97 9.32

26.00

26.00

2311.95 325.63 9.21

98.10

4270.88

4508.00 8876.98

3994.64

2713.57

NO

20.00

1931.70

1080.10 57.77

1162.78 2300.65 324.03 9.26

28.88

28.88

2329.53 328.10 9.14

98.10

4270.88

4508.00 8876.98

3994.64

2730.17

NO

22.00

1945.94

1080.10 63.54

1171.35 2315.00 326.06 9.20

31.77

31.77

2346.77 330.53 9.08

98.10

4270.88

4508.00 8876.98

3994.64

2746.39

NO

24.00

1959.48

1080.10 69.32

1179.50 2328.92 328.02 9.15

34.66

34.66

2363.58 332.90 9.01

98.10

4270.88

4508.00 8876.98

3994.64

2762.14

NO

26.00

1972.28

1080.10 75.10

1187.21 2342.40 329.92 9.09

37.55

37.55

2379.95 335.20 8.95

98.10

4270.88

4508.00 8876.98

3994.64

2777.38

NO

28.00

1984.29

1080.10 80.87

1194.44 2355.41 331.75 9.04

40.44

40.44

2395.85 337.44 8.89

98.10

4270.88

4508.00 8876.98

3994.64

2792.08

NO

30.00

1995.53

1080.10 86.65

1201.20 2367.95 333.51 9.00

43.33

43.33

2411.28 339.62 8.83

98.10

4270.88

4508.00 8876.98

3994.64

2806.26

NO

32.00

2006.01

1080.10 92.43

1207.51 2380.04 335.22 8.95

46.21

46.21

2426.25 341.73 8.78

98.10

4270.88

4508.00 8876.98

3994.64

2819.92

NO

34.00

2015.76

1080.10 98.20

1213.38 2391.68 336.86 8.91

49.10

49.10

2440.79 343.77 8.73

98.10

4270.88

4508.00 8876.98

3994.64

2833.08

NO

36.00

2024.82

1080.10 103.98 1218.84 2402.91 338.44 8.86

51.99

51.99

2454.90 345.76 8.68

98.10

4270.88

4508.00 8876.98

3994.64

2845.78

NO

38.00

2033.22

1080.10 109.76 1223.89 2413.75 339.96 8.82

54.88

54.88

2468.63 347.69 8.63

98.10

4270.88

4508.00 8876.98

3994.64

2858.03

NO

40.00

2041.01

1080.10 115.53 1228.58 2424.21 341.44 8.79

57.77

57.77

2481.98 349.57 8.58

98.10

4270.88

4508.00 8876.98

3994.64

2869.86

NO

42.00

2048.22

1080.10 121.31 1232.92 2434.33 342.86 8.75

60.66

60.66

2494.98 351.41 8.54

98.10

4270.88

4508.00 8876.98

3994.64

2881.29

NO

44.00

2054.91

1080.10 127.09 1236.95 2444.13 344.24 8.71

63.54

63.54

2507.68 353.19 8.49

98.10

4270.88

4508.00 8876.98

3994.64

2892.38

NO

46.00

2061.11

1080.10 132.86 1240.68 2453.64 345.58 8.68

66.43

66.43

2520.07 354.94 8.45

98.10

4270.88

4508.00 8876.98

3994.64

2903.12

NO

48.00

2066.86

1080.10 138.64 1244.14 2462.88 346.88 8.65

69.32

69.32

2532.20 356.65 8.41

98.10

4270.88

4508.00 8876.98

3994.64

2913.57

NO

50.00

2072.20

1080.10 144.42 1247.36 2471.87 348.15 8.62

72.21

72.21

2544.08 358.32 8.37

98.10

4270.88

4508.00 8876.98

3994.64

2923.73

NO

(N)

(N)

TIRO
CABLE
(N)

C.S>2

Pg. 26

CALCULO MECANICO DE ESTRUCTURAS EN REDES SECUNDARIAS

Especificacin: Armado E - 5
Tipo de Estructura: Fin de Lnea (Vano normal)

CONDUCTOR

Datos de los Conductores:


3x35/25

Seccin:

mm

Datos del Poste:


Longitud del poste

hp

25

Esfuerzo en la punta

Datos del Macizo


m

Altura

0.9

KN

1.96

arista 1

0.50

Velocidad del viento:

Km/h

113

Diametro:

mm

20

Longitud de empotramiento

Le

0.8

Arista 2

Presin del viento

Pv

N/m

231.76

Peso Unitario:

Wc

N/m

0.419

Altura util del poste

Peso especifico

Angulo de retenida:

Ar

grad.

30

Vano Viento

Vv

1Vv

Distancia con respecto a la punta

0.2

Carga de retenida:

Crr

30920

Vano Peso:

Vp

1,1Vv

Diametro en la punta

Do

0.12

Angulo de Desvio:

Ang.

grad

Diametro de empotramiento

Dm

0.24

Altura de aplicacin de fuerzas:

Ha

7.8

Factor de seguridad

Fs

F.V.

0.50

Kg/m3

2400

Peso del Macizo

4270.88

Pto. De volteo

0.45

Peso del Equipo

98.1

2
N

339.314

Peso del poste

Pp

4508

Carga en la punta

Cr

3000

Puntos de aplicacin de las fuerzas horizontales


en el poste de CAC con respecto al macizo
Fuerzas Horizontales en el Poste
FVP

V(Km/h)
113

MOMENTO EN CONDICIONES NORMALES

MOMENTOS EN CONDICIONES DE ROTURA DEL CONDUCTOR

4.496

Variable

7.7

TC

Variable

7.7

MVP

MVC

MTC

MRN

Qn

M.T.

M.f.

M.T.E.

M.R.F.

Qr

(N-m)

(N-m)

(N)

C.S>=2 (N-m)

(N-m)

(N-m)

(N-m)

(N)

RETENIDA

CARGAS VERTICALES

60

Longitud de Aplicacin

FVC

MOMENTOS ACTUANTES

ANGULO
TOPOGRAFICO

Vano Viento

292.02

MOMENTO

MOMENTO

TIRO

W.EQUIPO

W.MACIZO

W.POSTE

TOTAL

RESISTENTE

VOLTEO

REQUIERE HORIZONTAL VERTICAL

CS>=2

(N)

(N)

(N)

(N)

(N-m)

(N-m)

RETENIDA

(m)

(N)

(N-m)

(N-m)

2.00

1817.96

1050.10

5.69

1078.46 2134.25 309.31 9.70

2.85

2.85

2137.09 309.72

9.69

98.10

4270.88

4508.00 8876.98

3994.64

2540.55

NO

4.00

1823.48

1050.10 11.39

1081.73 2143.21 310.61 9.66

5.69

5.69

2148.91 311.44

9.63

98.10

4270.88

4508.00 8876.98

3994.64

2550.71

NO

6.00

1832.20

1050.10 17.08

1086.90 2154.08 312.19 9.61

8.54

8.54

2162.62 313.42

9.57

98.10

4270.88

4508.00 8876.98

3994.64

2563.01

NO

8.00

1843.50

1050.10 22.77

1093.61 2166.48 313.98 9.55

11.39

11.39

2177.86 315.63

9.50

98.10

4270.88

4508.00 8876.98

3994.64

2577.05

NO

10.00

1856.72

1050.10 28.46

1101.45 2180.01 315.94 9.50

14.23

14.23

2194.24 318.01

9.43

98.10

4270.88

4508.00 8876.98

3994.64

2592.37

NO

12.00

1871.18

1050.10 34.16

1110.03 2194.28 318.01 9.43

17.08

17.08

2211.36 320.49

9.36

98.10

4270.88

4508.00 8876.98

3994.64

2608.53

NO

14.00

1886.33

1050.10 39.85

1119.02 2208.96 320.14 9.37

19.93

19.93

2228.89 323.03

9.29

98.10

4270.88

4508.00 8876.98

3994.64

2625.16

NO

16.00

1901.68

1050.10 45.54

1128.12 2223.76 322.28 9.31

22.77

22.77

2246.53 325.58

9.21

98.10

4270.88

4508.00 8876.98

3994.64

2641.91

NO

18.00

1916.89

1050.10 51.24

1137.14 2238.48 324.42 9.25

25.62

25.62

2264.09 328.13

9.14

98.10

4270.88

4508.00 8876.98

3994.64

2658.58

NO

20.00

1931.70

1050.10 56.93

1145.93 2252.96 326.52 9.19

28.46

28.46

2281.42 330.64

9.07

98.10

4270.88

4508.00 8876.98

3994.64

2674.97

NO

22.00

1945.94

1050.10 62.62

1154.38 2267.10 328.56 9.13

31.31

31.31

2298.41 333.10

9.01

98.10

4270.88

4508.00 8876.98

3994.64

2690.99

NO

24.00

1959.48

1050.10 68.32

1162.41 2280.82 330.55 9.08

34.16

34.16

2314.98 335.50

8.94

98.10

4270.88

4508.00 8876.98

3994.64

2706.53

NO

26.00

1972.28

1050.10 74.01

1170.00 2294.11 332.48 9.02

37.00

37.00

2331.11 337.84

8.88

98.10

4270.88

4508.00 8876.98

3994.64

2721.57

NO

28.00

1984.29

1050.10 79.70

1177.13 2306.92 334.34 8.97

39.85

39.85

2346.78 340.11

8.82

98.10

4270.88

4508.00 8876.98

3994.64

2736.09

NO

30.00

1995.53

1050.10 85.39

1183.80 2319.29 336.13 8.93

42.70

42.70

2361.98 342.32

8.76

98.10

4270.88

4508.00 8876.98

3994.64

2750.08

NO

32.00

2006.01

1050.10 91.09

1190.01 2331.20 337.85 8.88

45.54

45.54

2376.74 344.45

8.71

98.10

4270.88

4508.00 8876.98

3994.64

2763.57

NO

34.00

2015.76

1050.10 96.78

1195.80 2342.67 339.52 8.84

48.39

48.39

2391.06 346.53

8.66

98.10

4270.88

4508.00 8876.98

3994.64

2776.56

NO

36.00

2024.82

1050.10 102.47 1201.17 2353.74 341.12 8.79

51.24

51.24

2404.98 348.55

8.61

98.10

4270.88

4508.00 8876.98

3994.64

2789.10

NO

38.00

2033.22

1050.10 108.17 1206.15 2364.42 342.67 8.75

54.08

54.08

2418.50 350.51

8.56

98.10

4270.88

4508.00 8876.98

3994.64

2801.19

NO

40.00

2041.01

1050.10 113.86 1210.78 2374.73 344.16 8.72

56.93

56.93

2431.66 352.41

8.51

98.10

4270.88

4508.00 8876.98

3994.64

2812.87

NO

42.00

2048.22

1050.10 119.55 1215.05 2384.70 345.61 8.68

59.78

59.78

2444.48 354.27

8.47

98.10

4270.88

4508.00 8876.98

3994.64

2824.16

NO

44.00

2054.91

1050.10 125.25 1219.02 2394.36 347.01 8.65

62.62

62.62

2456.98 356.08

8.42

98.10

4270.88

4508.00 8876.98

3994.64

2835.10

NO

46.00

2061.11

1050.10 130.94 1222.70 2403.73 348.37 8.61

65.47

65.47

2469.20 357.86

8.38

98.10

4270.88

4508.00 8876.98

3994.64

2845.71

NO

48.00

2066.86

1050.10 136.63 1226.11 2412.84 349.69 8.58

68.32

68.32

2481.15 359.59

8.34

98.10

4270.88

4508.00 8876.98

3994.64

2856.02

NO

50.00

2072.20

1050.10 142.32 1229.28 2421.70 350.97 8.55

71.16

71.16

2492.86 361.28

8.30

98.10

4270.88

4508.00 8876.98

3994.64

2866.05

NO

(N)

TIRO

(N)

TIRO
CABLE
(N)

C.S>2

5.0 CIMENTACIONES DE POSTES


Las fuerzas que soportar en funcin a la profundidad de enterramiento se incluyen en
los anexos al final del presente captulo. Adems se adjunta en el anexo 5 el mtodo
de Valenci para el clculo de cimentaciones, que es una aproximacin del clculo de
cimentaciones elaborada por Sulzberger.

Pg. 27

CALCULO DE CIMENTACION TIPO I - POSTES DE CONCRETO DE 8 m, 200 kg


La cimentacin ser de concreto ciclopeo y con una profundidad mnima de un dcimo de la altura del poste ms 0.10 m.
Para el anlisis se ha optado por los casos en que el terreno corresponde a un suelo pedregoso con arena, hmedo y con abundante vegetacin.
Para el clculo de las cimentaciones de los postes de concreto se usar el mtodo de Sulzberger:
Dimetro del poste (D)
Longitud del poste (L)
Fuerza horizontal aplicada a 10 cm debajo de la punta (F)
Fuerza horizontal por sismo (0.3g) aplicada a H/2 de la superficie (Fsh)
Fuerza vertical por sismo (0.3g) (Fsv)
Carga de rotura (Cr)
Peso del poste (Wp)
Peso total de conductores (Pc)
Peso extra (Pe)
Longitud de empotramiento (h)
Altura til del poste (H)
Peso vertical total (Wt)
Datos
D= 12

cm

L= 8

F= 2000

Fsh= 1680.1

Fsv= 1900.6

Cr= 5000

Wp= 5346.5

Pc= 989

Pe= 180

N
Resultados
h= 0.9
m
H= 6.8
m
Wt= 6515.5 N
I- Metodologa (no considerando
sismo)

Calculando por el mtodo de Sulzberger el lado de la cimentacin (a) de los postes de concreto:
Datos

1
2

F
h

0
0
0
0
,
5
,
,
5
5

R
R
R
R
/
/ 1
A
A
/
/

1
2
1
2
1
2
2
O

2
2
2
2
2
2
2

t
t
t t
t
t
t

1
1
1
1
0
0
1
0
1
0
1
k
0
k
0
k
k
0
g
k
g
g
g
k
k
/
g
/
/
/
g
cm
g
cm
cm
/
cm
/
cm
/cm
cm
1
2

A
A

0
0
,
,
0
5
5
,5 t
t

Vista en Planta de Cimentacin

Longitud del poste (L)

8 m

Fuerza horizontal aplicada a 10 cm debajo de la punta (F)

2000 N

Fuerza horizontal por sismo (0.4g) aplicada a H/2 de la superficie (Fsh)

1680.1 N

Fuerza vertical por sismo (0.3g) (Fsv)

1900.6 N

Peso del poste (Wp)

5346.5 N

Peso total de conductores (Pc)

989 N

Peso extra (Pe)

180 N

Longitud de empotramiento (h)

0.8 m

Altura til del poste (H)

6.8 m

Peso vertical total (Wt)

6515.5 N

20 kg/cm3

Coeficiente de la comisin suiza, Sulzberger (Ct),


(para terreno rocoso)
Resultados
Momento de vuelco (M)

14667 N-m

Lado de la cimentacin (a )

0.50 m

M F H h
3

Momento de vuelco:

Mct h3 tan_
0,4Pa
/K
36

a su vez se cumple que:


donde:

tan 0,01

14667 N-m

es el mximo giro permisible para llegar a las reacciones estabilizadoras del terreno,

P es igual a Wt + Wc, siendo Wc = peso del bloque de cimentacin


2
luego: P Wt h a g C
donde

tan
y K es una constante que para valores

gC

es la densidad del concreto = 2300 kg/m3

= 0,01 es aproximadamente

1.2 k =

c h tan_
0,4W W a/ K
M t
t
c
36

Resolviendo la ecuacin se obtiene:

Frmula para-1300.09167
Solver (Celda Objetivo)
a = 0.50 m

II- Verificacin por Sismo: Se considerar 0.3(g) fuerza horizontal y 0.3(g) fuerza vertical respecto al peso del poste y conductores. Siguiendo la
misma metodologa se tiene:
Resultados
Momento de vuelco (M)

21275 N-m

Lado de la cimentacin (a )
Momento de vuelco:

0.59 m

2
2

M F H h Fsh. H / 2 h
3
3

21275 N-m

Mct h3 tan_
0,4Pa
/ K
36

a su vez se cumple que:


Resolviendo la ecuacin se obtiene:

-5199.655

#REF!

a = 0.59 m
En este caso obtenemos un ancho de cimentacin un valor de

0.59 m

Para la fuerza vertical se verificara el esfuerzo solicitado como sigue:

A=L2*PI/4 = 2733.98
Wt/A 3=

< 0,25

cm2
dN/cm2

0.24
2

dN/cm

ok

Pg. 28

CALCULO DE CIMENTACION TIPO I - POSTES DE CONCRETO DE 8 m, 300 kg


La cimentacin ser de concreto ciclopeo y con una profundidad mnima de un dcimo de la altura del poste ms 0.10 m.
Para el anlisis se ha optado por los casos en que el terreno corresponde a un suelo pedregoso con arena, hmedo y con abundante vegetacin.
Para el clculo de las cimentaciones de los postes de concreto se usar el mtodo de Sulzberger:
Dimetro del poste (D)
Longitud del poste (L)
Fuerza horizontal aplicada a 10 cm debajo de la punta (F)
Fuerza horizontal por sismo (0.3g) aplicada a H/2 de la superficie (Fsh)
Fuerza vertical por sismo (0.3g) (Fsv)
Carga de rotura (Cr)
Peso del poste (Wp)
Peso total de conductores (Pc)
Peso extra (Pe)
Longitud de empotramiento (h)
Altura til del poste (H)
Peso vertical total (Wt)
Datos
D= 12

cm

L= 8

F= 3000

Fsh= 1680.1

Fsv= 1900.635

Cr= 7500
Wp= 5346.45
Pc= 989

N
N
N

Pe= 180

N
Resultados
h= 0.9
m
H= 6.8
m
Wt= 6515.45
N
I- Metodologa (no considerando
sismo)

Calculando por el mtodo de Sulzberger el lado de la cimentacin (a) de los postes de concreto:
Datos

1
2

F
h

0
0
0
0
,
5
,
,
5
5

R
R
R
R
/
/ 1
A
A
/
/

1
2
1
2
1
2
2
O

2
2
2
2
2
2
2

t
t
t t
t
t
t

1
1
1
1
0
0
1
0
1
0
1
k
0
k
0
k
k
0
g
k
g
g
g
k
k
/
g
/
/
/
g
cm
g
cm
cm
/
cm
/
cm
/cm
cm
1
2

A
A

0
0
,
,
0
5
5
,5 t
t

Vista en Planta de Cimentacin

Longitud del poste (L)

8 m

Fuerza horizontal aplicada a 10 cm debajo de la punta (F)

3000 N

Fuerza horizontal por sismo (0.4g) aplicada a H/2 de la superficie (Fsh)

1680.1 N

Fuerza vertical por sismo (0.3g) (Fsv)

1900.6 N

Peso del poste (Wp)

5346.5 N

Peso total de conductores (Pc)

989 N

Peso extra (Pe)

180 N

Longitud de empotramiento (h)

0.9 m

Altura til del poste (H)

6.8 m

Peso vertical total (Wt)

6515.5 N

20 kg/cm3

Coeficiente de la comisin suiza, Sulzberger (Ct),


(para terreno rocoso)
Resultados
Momento de vuelco (M)

22200 N-m

Lado de la cimentacin (a )

0.50 m

M F H h
3

Momento de vuelco:
a su vez se cumple que:
donde:

tan 0,01

22200 N-m

Mct h3 tan_
0,4Pa
/K
36

es el mximo giro permisible para llegar a las reacciones estabilizadoras del terreno,

P es igual a Wt + Wc, siendo Wc = peso del bloque de cimentacin


2
luego: P Wt h a g C
donde

tan
y K es una constante que para valores

gC

= 0,01 es aproximadamente

es la densidad del concreto = 2300 kg/m3


k =

1.2

c h tan_
0,4W W a/ K
M t
t
c
36

Resolviendo la ecuacin se obtiene:

Frmula para-3823.96667
Solver (Celda Objetivo)
a = 0.50 m

II- Verificacin por Sismo: Se considerar 0.3(g) fuerza horizontal y 0.3(g) fuerza vertical respecto al peso del poste y conductores. Siguiendo la misma
metodologa se tiene:
Resultados
Momento de vuelco (M)

28920 N-m

Lado de la cimentacin (a )
Momento de vuelco:

0.60 m

2
2

M F H h Fsh. H / 2 h
3
3

28920 N-m

Mct h3 tan_
0,4Pa
/ K
36

a su vez se cumple que:


Resolviendo la ecuacin se obtiene:

-6480.66

#REF!

a = 0.60 m
En este caso obtenemos un ancho de cimentacin un valor de

0.60 m

Para la fuerza vertical se verificara el esfuerzo solicitado como sigue:

A=L2*PI/4 = 2827.44
Wt/A 3=
0.23

< 0,25

dN/cm

cm2
dN/cm2

ok

Pg. 29

6.0 CLCULO DE RETENIDAS


6.1 Criterios de Diseo de Retenidas
Los criterios de diseo adoptados son los que se indican a continuacin:
-

6.2

Las retenidas sern empleadas para compensar aquellas fuerzas que el poste
no puede soportar por s mismo.
Las fuerzas a compensar sern las ejercidas por el tiro de los conductores, as
como la fuerza del viento sobre el poste y sobre los conductores, multiplicadas
por los factores de sobrecarga correspondientes, definidos en los criterios de
diseo
La retenida estar fijada a la estructura en un punto que resulte lo ms
cercano posible al centro de carga del tiro de los conductores que va ha
soportar.
La carga permitida ser la carga de rotura del alambre de la retenida
multiplicada por un factor de resistencia de 0,9 indicada en los criterios de
diseo.
Clculo de Retenidas

De acuerdo con el diagrama las fuerzas de trabajo de la retenida se calculan con las
frmulas:
TH = TR[max] x sen f.s
Ttot = (TH x hv ) / h
Donde:
TH
hV
Ttot
h
TR[max]
sen
f.s
Adicionalmente se
valor:

: Fuerza horizontal en la retenida en Newton


: Altura del punto de aplicacin de la retenida en metros
: Fuerza horizontal que compensa la retenida en Newton
: Altura del punto de aplicacin de Ftot en metros
: Fuerza mxima en la retenida en Newton
: Seno del ngulo que forma la retenida con la vertical
: Factor de sobrecarga 1,33 segn CNE Tabla 253-1
tiene que la fuerza en la retenida no debe superar el siguiente
TR (MAX) = (Trot * f.r.)

Pg. 30

Dnde:
Trot
f.r.

:
:

Tiro de rotura del cable en N.


Factor de resistencia para el alambre de la retenida, igual a 0,9
segn el CNE.

Para el caso de ms de una retenida, se aplicar las mismas ecuaciones; pero en


cada caso se tomar en cuenta la altura a la que la retenida se une al poste, el
ngulo que forma con la vertical y, si es que fuera necesario, el ngulo horizontal que
forma la retenida con la fuerza resultante que debe equilibrar. A partir de estos datos
se calcular el momento equivalente que resulte del trabajo combinado de estas
retenidas.
La varilla de anclaje deber ser similarmente resistente al cable de retenida.
Clculo de Bloque de las Retenidas

6.3

El bloque de anclaje de las retenidas ser dimensionado considerando las siguientes


relaciones:
a.

Dimensiones del bloque de anclaje


d

R
1.5L

Dnde:
R :
D :
L :
b.

Tiro de la retenida
Ancho del bloque de la retenida
Longitud del bloque de la retenida
Volumen de la cimentacin de la retenida
1
V h ( S1 S 2 S1 S 2 )
3

S1 (L 2htan ) 2
S 2 L2

c.

Peso del volumen de tierra y coeficiente de seguridad


PV t x V
C.S

PV
R

Dnde:
t :

Densidad del terreno

Pg. 31

ILUMINACION CC CAM LAS BAMBAS


CALCULO DE CIMENTACIN DE RETENIDAS

CARGA DE ROTURA DE RETENIDA SIMPLE: Fo 30 920 N


ITEM
1.00

MAGNITUD
VALOR
UNIDAD
DATOS DE LA EXCAVACIN DE LA RETENIDA:

37.00

Fuerza de Trabajo de retenida

2.00

Datos Geomtricos de Excavacion :


S
0.80
D
0.70
H
2.00
f
0.70

m
m
m
m

Fo a vencer

DATOS DEL BLOQUE DE CONCRETO

rea seccin lateral:

rea (a restar)

rea neta
Volumen total de relleno

0.40
0.40
0.15
1.82

m
m
m
m2

0.06
0.04
0.10
0.01
0.20
1.62
1.14

m2
m2
m2
m2
m2
m3

DATOS DEL RELLENO


Peso especfico del terreno
ngulo de Friccin
m
Ka
Masa del relleno
Peso del relleno Wt
Peso bloque de concreto Wc

4.00

sex

15,460.00

L
B
h

3.00

OBSERVACION

1,500.00
23.00
0.50
0.44
1,702.72
16,703.67
565.06

Kg/m3
sex
adim
adim
Kg
N
N

CLCULO DE FUERZAS RESISTENTES


Pw = W Cos
W Sen
Pb Sen
Fuerza de rozamiento frontal
Fuerza de rozamiento lateral
(caras derecha e izquierda)
Fuerza de rozamiento posterior

S FUERZAS RESISTENTES

5.00
FINALMENTE DEBE CUMPLIR:
TIRO DE TRABAJO DE LA RETENIDA
15460 N

13,340.13
10,052.54
451.27
5,026.27

N
N
N
N

7,207.79

7,207.79

40,441.05

<
<

S FUERZAS RESISTENTES
40441.05 N

CORRECTO !

Pg. 32