C CABLE SIZING AND AMPACITY CALCULATION

132/13.8 K.V SUBSTATION #8160

SUPLY
CABLE RUN

Load
(KVA)

S. No.
FROM

TO

No. of
Phase

VOLTAGE

Load
Current (A)

N0 OF
CABLES
/PHASE

CABLE SIZE
SQ.MM

CB Rating

LENGTH
M

(Volts)

500.00

220

1312.16

1C

CABLE
CURRENT
RATING PER
RUN

LAYING
ARRANGEMENT

DERATING FACTOR

GROUP

AMPIENT
TEMP

SOIL
RESISTIVITY

BURRIAL
LEGTH

TOTAL

DERATED
CURRENT A

VOLTAGE
DROP
V/(A*KM)

CALCULATED
CABLE VOLTAGE
DROP

PERCENTAGE
VOLTAGER
REGULATION

10

11

12

13

14

15

16

17

18

19

20

21

630

1600

17

1117

CABLE TRAY

0.87

0.79

0.69

1535.43

0.153

1.71

0.78

AUX TR

ACDB

Power Transformer #1, #2, #3 cooling Fan


(TYPICAL)

4.50

220

11.81

4C

10

32

70

73

CABLE TRAY

0.7

0.79

0.55

40.37

3.35

2.77

1.26

ACDB

ACDB outgoing MCB for power Transformer


OLTC drive motor & OLTC oil filter motor
for G.T1, G.T2 &GT3 typical

2.78

220

7.28

4C

16

70

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

4.22

1.92

ACDB

LAN(PC+ Monitor)

0.60

127

4.72

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.78

0.62

ACDB

router (LAN ) system

0.10

220

0.26

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.04

0.02

ACDB

Control panel heating and lighting (TYPICAL)

1.50

220

3.94

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.65

0.30

ACDB

MW SWGR Panels lighting and haeting


SEC.(A,B,C) (TYPICAL)

5.06

220

13.28

4C

10

32

40

73

CABLE TRAY

0.7

0.79

0.55

40.37

3.35

1.78

0.81

ACDB

Over head traveling Crane Motors

9.70

220

25.46

4C

35

100

50

160

CABLE TRAY

0.7

0.79

0.55

88.48

1.03

1.31

0.60

ACDB

HVAC package unit (1A,1B)

49.20

220

129.20

4C

120

200

50

355

CABLE TRAY

0.7

0.79

0.55

196.32

0.37

2.39

1.09

10

ACDB

HVAC package unit (2A,2B)

86.50

220

227.00

4C

240

300

50

551

CABLE TRAY

0.7

0.79

0.55

304.70

0.231

2.62

1.19

11

ACDB

HVAC package unit (3A,3B)

95.70

220

251.00

4C

240

350

50

551

CABLE TRAY

0.7

0.79

0.55

304.70

0.231

2.90

1.32

12

ACDB

125 VDC Battery charger #1,#2 (TYPICAL)

43.40

220

113.90

4C

120

250

20

355

CABLE TRAY

0.7

0.79

0.55

196.32

0.37

0.84

0.38

13

ACDB

Out door lighting

17.3

220

45.40

4C

35

100

20

160

CABLE TRAY

0.7

0.79

0.55

88.48

1.03

0.94

0.43

14

ACDB

ACDB lighting and heating

2.14

220

5.61

4C

16

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.05

0.02

15

ACDB

RMU E/F relay

0.2

220

0.52

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.09

0.04

16

ACDB

SCADA panels

2.2

220

5.77

4C

16

25

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

1.20

0.54

17

ACDB

Gas handling equibment (TYPICAL)

24

220

63.00

4C

35

63

50

160

CABLE TRAY

0.7

0.79

0.55

88.48

1.03

3.24

1.47

18

ACDB

HVAC control panel

16

220

41.99

4C

35

100

25

160

CABLE TRAY

0.7

0.79

0.55

88.48

1.03

1.08

0.49

19

ACDB

LCC panel heater (TYPICAL)

1.71

220

4.49

4C

16

50

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

1.86

0.84

20

ACDB

M.K heating and lighting for GT (TYPICAL)

2.27

220

5.96

4C

16

70

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

3.45

1.57

21

ACDB

OLTC and oil filteration control for for GT


(typical)

0.4

220

1.05

4C

32

70

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.61

0.28

22

ACDB

FACP-FM200 system 1,2,3,4,5,6,7 & 8

0.40

220

1.05

4C

16

25

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.22

0.10

23

ACDB

Relay Panels lighting and haeting (TYPICAL)

0.10

220

0.26

4C

16

30

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.07

0.03

24

ACDB

PABX charger

1.20

220

3.15

4C

16

25

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.65

0.30

25

ACDB

Fiber Obtic panel

0.44

220

1.15

4C

16

25

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.24

0.11

26

ACDB

FR & B.B panels heating and lighting

0.81

220

2.13

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.35

0.16

27

ACDB

FACP control & detection system

0.70

220

1.84

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.30

0.14

28

ACDB

48V battery charger fiber obtic panel

48.00

220

125.00

4C

120

160

20

355

CABLE TRAY

0.7

0.79

0.55

196.32

0.37

0.93

0.42

\\vboxsrv\conversion_tmp\scratch_2\157798255.xls.ms_office

Incomer #1 ( TYPICAL)

Page 1 of 2

SUPLY
CABLE RUN

Load
(KVA)

S. No.
FROM

TO

No. of
Phase

VOLTAGE

Load
Current (A)

N0 OF
CABLES
/PHASE

CABLE SIZE
SQ.MM

CB Rating

LENGTH
M

(Volts)
3

CABLE
CURRENT
RATING PER
RUN

LAYING
ARRANGEMENT

DERATING FACTOR

GROUP

AMPIENT
TEMP

SOIL
RESISTIVITY

BURRIAL
LEGTH

TOTAL

DERATED
CURRENT A

VOLTAGE
DROP
V/(A*KM)

CALCULATED
CABLE VOLTAGE
DROP

PERCENTAGE
VOLTAGER
REGULATION

10

11

12

13

14

15

16

17

18

19

20

21

29

ACDB

welding receptacles on roof

30.40

220

80.00

4C

35

160

70

160

CABLE TRAY

0.7

0.79

0.55

88.48

1.03

5.77

2.62

30

ACDB

Indoor lighting panel+power sockets

62.75

220

164.68

4C

120

250

20

355

CABLE TRAY

0.7

0.79

0.55

196.32

0.37

1.22

0.55

31

ACDB

DCDB lighting and heating

1.22

220

3.21

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.53

0.24

32

ACDB

Door shutter

1.491

220

3.91

4C

10

32

60

73

CABLE TRAY

0.7

0.79

0.55

40.37

3.35

0.79

0.36

33

ACDB

DCDB E/F relay (typical)

0.1

127

0.79

4C

16

10

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.07

0.05

34

ACDB

DSM panels heating & lightind

0.5

220

1.31

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.22

0.10

35

ACDB

SEP+ASCE+LS, panels lighting & lighting

0.1

220

0.26

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.04

0.02

36

ACDB

SMK & FMK panels

2.2

220

5.77

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.96

0.43

37

ACDB

AVC panels lighting & heating

0.1

220

0.26

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.04

0.02

38

ACDB

Aux supply AVC relay (typical)

0.1

127

0.79

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.13

0.10

39

ACDB

MDF panel heating & lighting

0.1

220

0.26

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.04

0.02

40

ACDB

PSE panel heating &lighting

0.1

220

0.26

4C

16

20

42

CABLE TRAY

0.7

0.79

0.55

23.23

8.28

0.04

0.02

41

ACDB

portable battery chargers (typical)

43.40

220

113.90

4C

120

250

20

355

CABLE TRAY

0.7

0.79

0.55

196.32

0.37

0.84

0.38

42

ACDB

OIL filtering machine

96.00

220

251.93

4C

240

500

70

551

PVC DUCT

0.79

0.79

435.29

0.231

4.07

1.85

FORMULAE USED: (Numbers in paranthesis refer to column numbers indicated in the table)
LOAD KVA

(3)

VOLTAGE AT SOURCE, V

(5)

Voltage at previous destination

LOAD CURRENT, A

(6)

Load kVA / {Voltage at source x Sqrt of No. Of Phases}

TOTAL DERATING FACTOR

(17)

Grouping Factor(14) x Temperature Correction factor(15) x Soil thermal resistivity factor(16) x Laying Depth Factor (17)

DERATED CURRENT, A

(18)

current rated per run(11)No.of Cables per phase(7) x Total Derating Factor(17)

CALCULATED VOLTAGE DROP, V

(20)

(Load Current x Length x Cable voltage drop in volt per amp per kilometer / 1000) + Voltage Drop from Aux. T/F to ACDB

PERECENTAGE VOLTAGE REGULATION , %

(21)

Calculated voltage drop x 100 / Voltage at Source

NOTES:
1

Ambient temerature for Air is taken as 50 deg. C for outdoor & 40 deg C for indoor as per TES-P-119.29 , page#10.

Ambient temerature for Ground is taken as 40 deg. C as per TES-P-119.29 , page#10.

Soil Thermal Resistivity is taken as 2.5 C M/W as per TES-P-119.29 , page#10.