IL
VL IL P RL
= = = =
Line to line voltage Line current Total power Load resistance Power factor
VL RL
P= IL=
VL x IL x cos
cos =
VP IL
VP
cos =
VL
IL
VL =VP
IL =IP
Quick Formula
For a balanced delta connected load only: IL = 3 x IP P = 3 x VL x IL x cos P = 3 x VL x IP x cos For resistive loads, cos = 1.0 For a balanced wye connected load only: VL = 3 x VP P = 3 x VL x IL x cos P = 3 x VP x IL x cos For resistive loads, cos = 1.0 To determine the line current (in Amps) for balanced 3- resistive loads (wye- or delta connected) where P = total 3- power in kW: for VL =480V for VL =240V for VL =208V IL = 1.2 x P (in kW) IL = 2.4 x P (in kW) IL = 2.8 x P (in kW)
Copyright Eurotherm Controls Inc 2000 All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Controls Inc. Every effort has been taken to ensure the accuracy of this specification. However, in order to maintain our technological lead we are continuously improving our products which could, without notice, result in amendments or omissions to this specification. We cannot accept responsibility for damage, injury, loss or expenses resulting therefrom.