CSV : DRIVE CONTROL & SIGNALLING


PRINT

SUMMARY
1 REPRESENTATION 2 FUNCTION 3 ARGUMENTS 4 PROCESSING 4.1 Closing order 4.2 Blocking order 4.3 Opening order 4.4 Alarm & Signalling 4.5 cMsig processing (VRE for Centralog display) 4.5.1 Validity bit : SIG_V 4.5.2 Closed position (cMSig = 1) 4.5.3 Open position (cMSig = 2) 4.5.4 In progress position (cMSig = 3) 4.5.5 Alarm open position (cMSig = 4) 4.5.6 Alarm closed status (cMSig = 5) 4.5.7 Double indication (cMSig = 6) 4.5.8 Middle indication (cMSig = 7) 5 MVM ASSOCIATION

1 REPRESENTATION

Output elaboration OP_ORD OP_DS BL_ORD BL_DS CL_ORD CL_DS REM_ATH ALARM OP_TLTE CL_TLTE SIG SIG_V

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 2 of 11

NOTA concerning the output SIG (multiple state variables for HMI): -In the CONTRECAD 3.2.x version, SIG is a single output. It is a booleans table (length 8). -In the CONTRECAD 3.3.x version, there are 2 outputs in this purpose, one is a word (SIG) and the other is a boolean validator (SIG_V).

2 FUNCTION
This Function Block provides standard logic for the control and signalling of motorized valve driven by motors supplied via contactors from low voltage or medium voltage switchboards.

3 ARGUMENTS
Name Description Type Neg Range Mand. Connection Def. Value Mand. Data Advised First parameters scan value value

Inputs

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 3 of 11

OP_A OP_M OP_A_ATH OP_M_ATH OP_PS OP_PS_V BL_A BL_M BL_A_ATH BL_M_ATH CL_A CL_M CL_A_ATH CL_M_ATH CL_PS CL_PS_V FLT_IN AV MANU TLTE_OP TLTE_CL OP_PL BL_PL CL_PL F_TP Outputs OP_ORD OP_DS BL_ORD BL_DS CL_ORD CL_DS REM_ATH ALARM OP_TLTE CL_TLTE SIG SIG_V

Automatic opening Manual opening Automatic opening authorization Manual opening authorization Open position Open position validant Automatic blocking Manual blocking Automatic blocking authorization Manual blocking authorization Automatic closing Manual closing Automatic closing authorization Manual closing authorization Close position Close position validant Fault input Availability Manual mode selected Opening TLTE value Closing TLTE value Opening pulse duration Blocking pulse duration Closing pulse duration Fault temporization

B B B B B B B B B B B B B B B B B B B D D D D D D

N N N N Y Y N N N N N N N N Y Y N N Y -

N N N N Y N N N N N N N N N Y N Y Y N N N N N N N

0 0 1 1 1 0 0 1 1 0 0 1 1 1 1 50 50 10 10 10 10

Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y

Opening order Opening order disabled Blocking order Blocking order disabled Closing order Closing order disabled Remote control authorized Alarm (filtered input "FLT_IN" Opening TLTE Closing TLTE Multiple state variable for HMI Multiple state validator

B B B B B B B B B B W B

N N N N N N N N N N N N

Y N Y N Y N N N N N N N

Y Y Y Y Y Y Y Y Y Y Y Y

4 PROCESSING 4.1 Closing order

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 4 of 11

4.2 Blocking order

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 5 of 11

4.3 Opening order

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 6 of 11

4.4 Alarm & signalling

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 7 of 11

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 8 of 11

4.5 cMsig processing (VRE for Centralog display) 4.5.1 Validity bit : SIG_V

4.5.2 Closed position (cMSig = 1)

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 9 of 11

4.5.3 Open position (cMSig = 2)

4.5.4 In progress position (cMSig = 3)

4.5.5 Alarm open position (cMSig = 4)

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 10 of 11

4.5.6 Alarm closed status (cMSig = 5)

4.5.7 Double indication (cMSig = 6)

4.5.8 Middle indication (cMSig = 7)

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSV.html

9/24/2007

Page 11 of 11

5 MVM ASSOCIATION