Vous êtes sur la page 1sur 10

SIMATIC

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>

12/19/2012 09:52:54 AM

FB976 - <offline>
Material discharge Family: EAF_EKT Version: 0.1 Block version: 2 10/25/2012 10:19:29 AM Time stamp Code: 07/27/2011 08:13:58 AM Interface: Lengths (block/logic/data): 00910 00602 00030 "MatDisch" Name: Author: ALS

Object properties: S7_language


Name IN Sys_Auto Sys_Start Dir_EAF Dir_SPB Sx_RunsEAF Sx_RunsSPB CVx2x_Runs WF1_Runs WF2_Runs WF3_Runs CV1x_Runs LS_CV23_EAF LS_CV23_PARK LS_CV23_TILT WF11_Runs OUT QDischEafAtv QDischSPBAtv QCVx23_ToEAF QCVx23_ToPARK QCVx2x_Start QSx_ToEAF QSx_ToSPB QWF1_Start Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool

9(1) Englisch (USA)


Data Type Address 0.0 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 1.0 1.1 1.2 1.3 1.4 1.5 1.6 0.0 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE

03/11/2005 11:34:06 AM
Comment

Initial Value

System in auto mode System start Direction to EAF selected Direction to SPB selected Conveyor running feedback Conveyor running feedback Vibro motors running feedback Wire feeder 1 running feedback Wire feeder 2 running feedback Wire feeder 3 running feedback Vibro bunker running feedback

Wire feeder 1.1 running feedback

Discharging to EAF active Discharging to SPB active Start Vibro car to EAF Start Vibro car to PARKING Start vibro motors Start conveyor to EAF Start conveyor to SPB Start wire feeder 1

Page 1 of 10

SIMATIC
Name QWF2_Start QWF3_Start QCV1x_Start QWF11_Start IN_OUT STAT DischEafStart DischSPBStart CVx23_ToEAF CVx23_ToPARK CVx2x_Start Sx_ToEAF Sx_ToSPB WF1_Start WF2_Start WF3_Start CV1x_Start Vibro_TOF Conv_TOF Conv_TON Vibro_TON WF11_Start spare_1 spare_2 spare_3 spare_4 spare_5 spare_6 spare_7 TEMP dummy_bool dummy_Int dummy_Real Bool Int Real Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool Bool TOF TOF TON TON Bool Bool Bool Bool Bool Bool Bool Bool Data Type Bool Bool Bool Bool Address 3.0 3.1 3.2 3.3 0.0 0.0 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5.0 5.1 5.2 6.0 28.0 50.0 72.0 94.0 94.1 94.2 94.3 94.4 94.5 94.6 94.7 0.0 0.0 2.0 4.0 FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>


Initial Value FALSE FALSE FALSE FALSE Comment Start wire feeder 2 Start wire feeder 3 Start vibro feeder Start wire feeder 1.1

12/19/2012 09:52:54 AM

Page 2 of 10

SIMATIC
Name dummy_DInt tmp_zero tmp_one tmp_real tmp_int tmp_bool tmp_word Data Type DInt Bool Bool Real Bool Bool Word Address 8.0 12.0 12.1 14.0 18.0 18.1 20.0

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>


Initial Value Comment

12/19/2012 09:52:54 AM

Block: FB976

Furnace mode

Network: 1

Set temporary signals >=1

#tmp_one #tmp_one

#tmp_one #

#tmp_zero =

Network: 2

Start Discharging to EAF &

#Sys_Auto #Dir_EAF #Sys_Start "HMI_ 0921". C14_ QuickStop #DischEafS tart =

Page 3 of 10

SIMATIC

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>

12/19/2012 09:52:54 AM

Network: 3

Start Discharging to SPB &

#Sys_Auto #Dir_SPB #Sys_Start #DischSPBS tart =

Network: 4

Start Vibro car to EAF #spare_1 P

#DischEafS tart #LS_CV23_ EAF

#spare_2 SR S & R Q #LS_CV23_ EAF #CVx23_ ToEAF =

Network: 5

TON delay for vibro car moving to park position

Check also Vibro_TON in chart !!! #Vibro_ TON EN Q #CVx2x_ Runs T#50S IN PT ET ENO

Page 4 of 10

SIMATIC

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>

12/19/2012 09:52:55 AM

Network: 6

Start Vibro car to PARKING #spare_3 N

#DischEafS tart #LS_CV23_ PARK >=1 #Vibro_ TON.Q "HMI_ 0921". C14_ QuickStop

#spare_4 SR S & R Q #LS_CV23_ PARK

#CVx23_ ToPARK =

Page 5 of 10

SIMATIC

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>

12/19/2012 09:52:55 AM

Network: 7

Start vibro motors (vibro car) & &

#tmp_one >=1 #DischEafS tart #Sx_ToEAF #LS_CV23_ EAF #LS_CV23_ TILT EN #LS_CV23_ PARK T#20S & #Vibro_ TOF.Q "HMI_ 0921". C14_ QuickStop #LS_CV23_ EAF #LS_CV23_ TILT #LS_CV23_ PARK #CVx2x_ Start = IN PT #Vibro_ TOF Q ET ENO

Page 6 of 10

SIMATIC

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>

12/19/2012 09:52:55 AM

Network: 8

Start conveyor to EAF &

#DischEafS tart #LS_CV23_ EAF #LS_CV23_ TILT #LS_CV23_ PARK #CVx2x_ Runs #Sx_ToEAF =

Network: 9

Start conveyor to SPB & #Sx_ToSPB =

#DischSPBS tart

Page 7 of 10

SIMATIC

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>

12/19/2012 09:52:55 AM

Network: 10

Start Wire feeders >=1

#DischEafS tart #DischSPBS tart >=1 #Sx_ RunsEAF #Sx_ RunsSPB & #WF1_Start = &

>=1 #Sx_ RunsEAF #Sx_ RunsSPB & #WF2_Start =

>=1 #Sx_ RunsEAF #Sx_ RunsSPB & #WF3_Start =

>=1 #Sx_ RunsEAF #Sx_ RunsSPB #WF11_ Start =

Page 8 of 10

SIMATIC

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>

12/19/2012 09:52:55 AM

Network: 11

Start Vibro feeder &

#DischEafS tart #Sx_ RunsEAF & #DischSPBS tart #Sx_ RunsSPB #CV1x_ Start = >=1

Network: 12 A = A = A = A = A = A = A = A = A = A = A =

Outputs #DischEafStart #QDischEafAtv #DischSPBStart #QDischSPBAtv #CVx23_ToEAF #QCVx23_ToEAF #CVx23_ToPARK #QCVx23_ToPARK #CVx2x_Start #QCVx2x_Start #Sx_ToEAF #QSx_ToEAF #Sx_ToSPB #QSx_ToSPB #WF1_Start #QWF1_Start #WF2_Start #QWF2_Start #WF2_Start #QWF3_Start #WF11_Start #QWF11_Start

Page 9 of 10

SIMATIC
A = Network: 13 SET SAVE #CV1x_Start #QCV1x_Start Save Eno

EAF6\PLC_EAF6\CPU 416-3 PN/DP\...\FB976 - <offline>

12/19/2012 09:52:55 AM

Page 10 of 10

Vous aimerez peut-être aussi