PIPING TECHNICAL QUESTIONNAIRE

OISD 116 & 118

QUESTION - 1

EXAMPLES OF C4 LIGHTER CARBONS

ANSWER

BUTANE, PROPANE,PROPYLE NE

QUESTION
HOW HYDROCARBON LIQUIDS ARE CLASSIFIED

ANSWER
BASED ON FLASH POINT

QUESTION - 2

FLASH POINT FOR GROUP A CLASSIFIED HYDRO CARBONS

ANSWER

BELOW 23 DEG C

QUESTION - 3

FLASH POINT FOR GROUP B CLASSIFIED HYDRO CARBONS

ANSWER

BETWEEN 23-65 DEG C

QUESTION - 4

FLASH POINT FOR GROUP C CLASSIFIED HYDRO CARBONS

ANSWER

BETWEEN 65 - 93 DEG C

QUESTION - 5

FLASH POINT FOR EXCLUDED CLASSIFIED HYDRO CARBONS

ANSWER

ABOVE 93 DEG C

QUESTION - 5

FLASH POINT FOR EXCLUDED CLASSIFIED HYDRO CARBONS

ANSWER

ABOVE 93 DEG C

QUESTION - 5

HOW MANY RAODS NEEDS TO BE PROVIDED TO A PLANT AS PER NORMS AND WHAT ARE THEY FOR?

ANSWER

TWO ROADS, ONE FOR MAN MOVEMENT, EMPLOYEES AND OTHER FOR PRODUCT TRANSPORT

QUESTION - 5

WHERE THE CONTROL ROOMS NEED TO BE LOCATED?

ANSWER
IN THE NON HAZARDOUS AREA, UPWIND OF THE PROCESS UNIT IT SHALL NOT BE LOCATED IN THE LOWER LEVEL THAN SURROUNDING PLNATS AND TANK FARMS

QUESTION - 5

WHERE THE COOLING TOWERS NEED TO BE LOCATED?

ANSWER

SHALL BE LOCATED DOWNWIND OF THE PROCESS EQUIPMENT

QUESTION - 5

WHY IT HAS TO BE LOCATED SO?

ANSWER

BECAUSE OF FOG WHICH CAN CAUSE CORROSION AND OBSTRUCT SHORT CIRCUITING

QUESTION - 5

HOW MUCH DISTANCE IS REQUIRED FOR SULPHUR HANDLING FACILITY AND ANY OTHER PROCESS UNIT

ANSWER

50 M

QUESTION - 5

WHERE ETP OR WTP SHALL BE LOCATED

ANSWER

AT THE EXTREME DOWN DIRECTION AND AT THE LOWER LEVEL

QUESTION - 5

WHAT IS FLARE? AND WHERE IT SHALL BE LOCATED

ANSWER

AT THE EXTREME UPWING DIRECTION AND AREA SHAL BE PAVED WITH 45M RAIDUS

QUESTION - 5

WHERE FIRE STATIONS SHALL BE LOCATED?

ANSWER

UPWIND OF THE PROCESS UNITS AND AWAY FROM THE HAZARDOUS STORAGE AREA

QUESTION - 5

WHAT STANDRADS SHALL BE SEEN WHILE LOCATING OR DESINGING FIRE WATER AREA

ANSWER

OISD 116, 117 & 144

QUESTION - 5

CAN WE LOCATE PUMPS UNDER THE AIR COOLERS? IF IT IS YES/NO

ANSWER

C4 AND LIGHTER HYDROCARBON HANDLING PUMPS SHALL NOT BE LOCATED BELOW THE AIR COOLERS

QUESTION - 5

WHY

ANSWER

IT WILL CATCH FIRE BECAUSE??

QUESTION - 5

WHAT IS THE MAXIMUM CONTAINMENT OF A HYDROCARBON FACILITY IN FIXED ROOF TANKS

ANSWER

60000M3

QUESTION - 5

WHAT IS THE MAXIMUM CONTAINMENT OF A HYDROCARBON FACILITY IN FLOATING ROOF TANKS

ANSWER

120000M3

QUESTION - 5

WHAT IS THE MAXIMUM HEIGHT OF A DYKE WALL

ANSWER

2M AND NOT LESS THAN 1M

QUESTION - 5

WHAT IS THE HEIGHT OF THE CURB WALL

ANSWER

600MM

QUESTION - 5

TWO PROCESS UNITS SHALL BE SEPARATED BY ??

ANSWER

A ROAD OF 6M IN THE CENTER AND A DISTANCE OF 30M

QUESTION - 5

WHER THE BLOW DOWN DRUMS ARE LOCATED?

ANSWER

A ROAD OF 6M IN THE CENTER AND A DISTANCE OF 30M

QUESTION - 5

WHER THE DELUGE VAVLES ARE LOCATED?

ANSWER

ARE LOCATED AT A DISTANCE OF 15 M AWAY FROM THE HYDRO CARBON EQUIPMENT