Supply and Installation

Substation Automation Systems


PM5-0403-WBX
Metropolitan Electricity Authority

Engineerin g Portable MMI 1

PM5-0403-WBX

Typical System Topology


DCC
BCU-1

Switch

Switch

BCU

Station Computer
CCU#1
2

GPS

MMI
CCU#2
Gateway With Firewall (CGW)

TDS

BCU-2 1 2 Commo n Alarm

Commo n Alarm Commo n Alarm

Transformer 1,2
Switch Switch

AC/DC Board

Line Bay

Switch

Trans. Bay

Switch

BS/BC. Bay
LAN B LAN A

Switch

Line Bay

Switch

Trans. Bay

Switch

Main 21/21N,27/ 59, 79, 50BF

Main 87

115/69kV
50/51, 50/51N, 50BF+BCU

Main 21/21N,27/ 59,79,50BF

Main 87

4
67/67N,27/ 59 50BF+ BCU 50/51, 50/51N, 50BF+BCU 67/67N,27/ 59 50BF+ BCU 50/51, 50/51N, 50BF+BCU

Switch

12/24kV
5 Protection & BCU-C Protection & BCU-F Protection & BCU-I Protection & BCU-F Protection & BCUBS 5

Bus # 1

Switch

12/24kV
Protection & BCU-F Protection & BCU-I Protection & BCU-F Protection & BCU-F Protection & BCU-C
DRN. ENGR.

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 1 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus # 3
A B C D E F

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

SYSTEM TOPOLOGY

Jangwatana (JWT) Terminal station (1)


1
7016G 7026G 7013 7023

PM5-0403-WBX
1

7013G

7023G

50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF+ BCU

7014AG

7012

7014BG 7014A 7014B

7024AG

7022

7024BG 7024A 7024B 7906A1G

7014A

7014B

7024A

7024B

2 Voltage Selection Scheme shall be Implemented by SA Software

Bus A1

7907A

Bus B1 7933A 7933A 7933B 7933B 7933AG 7933B 7943AG 7933A 7943A 7943B 7943B 7943B 7953AG 7943A 7943A 7953A 7953B 7953A 7953B 7603AG 7603A 7603B 7963A 7963B 7963A 7963B 7973A 7973B 7973B 7973B 7983AG 7973A 7973A 7983A 7983B 7983B 7983B 7983A 7983A

7907B 7906B1G

7932

7933BG

7942

7943BG

7952

7953BG

7602

7603BG
50/51,50/51N, 50BF + BCU

7963AG

7962

7963BG

7973AG

7972

7973BG

7982

7983BG

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU 7944 7946G Y 27/59


50/51,50/51N,50BF 27/59/81+ BCU

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU 50/51,50/51N, 50BF+ BCU 87 7974 7976G 7984 7986G

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF+ BCU 7956G 87 Y

3
7934 7936G 7966G

27/59
50/51,50/51N,50BF 27/59/81+ BCU

410 410I

420 420I

C1I

415I 415
50/51,50/51N, 50BF 27/59/81 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414,416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

C1

401I1 C1A C1B

401I2 C2A C2B

402I1

402I2

401
50/51,50/51N, 50BF + BCU

402
50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 2 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Jangwatana (JWT) Terminal station (2)


1
7036G 7046G 7033 7043

PM5-0403-WBX
1

7033G

7043G

50/51,50/51N, 50BF+ BCU


50/51,50/51N, 50BF + BCU

50/51,50/51N, 50BF+ BCU

7034AG

7032

7034BG 7034A 7034B

7044AG

7042

7044BG 7044A 7044B

7034A 7906A2G

7034B

7044A

7044B

2
7907A

Bus A2

Voltage Selection Scheme shall be Implemented by SA Software


7907B 7906B2G 7993A 7993A 7993B 7993B 7993AG 7993B 79103AG 7993A 79103A 79103B 79103B 79103B 79113AG 79103A 79103A 79113A 79113B 79113A 79113B 7703AG 7703A 7703B 79123A 79123B 79123B 79123B 79133AG 79123A 79123A 79133A 79133B 79133B 79133B 79143AG 79133A 79133A 79143A 79143B 79143B 79143B Bus B2 79143A 79143A

7992

7993BG

79102

79103BG

79112

79113BG

7702

7703BG
50/51,50/51N, 50BF + BCU

79123AG

79122

79123BG

79132

79133BG

79142

79143BG

50/51,50/51N, 50BF + BCU

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU 79104 79106G 50/51,50/51N, 50BF+ BCU 79116G 87

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU 79124 79126G 79134

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU 79144

21/21N,50BF 27/59,79 50/51,50/51N, 50BF+ BCU

3
7994 7996G 79136G 79146G

Y 27/59
50/51,50/51N,50BF 27/59/81+ BCU

430 430I

437I

436I 435,433,431,432,434 Same As 437 Feeder


50/51,50/51N, 50BF 27/59/81,79 + BCU

C3I C3
50/51,50/51N, 50BF 27/59/81,79 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

437

436

402I1

402I2 C3A C3B

402
50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 3 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

North Bangkok (NKT) Terminal Station (1)


1

PM5-0403-WBX
1

EGAT

MEA
Line NKT-691 Line NKT-692 Line NKT693 Line SIT-694

6992A

6931A

6993A

Bus A1 6907A

Bus A2

6013 A

2
50/51,50/51N, 50BF+ BCU

6913A

6923A

6933A

6943A

Voltage Selection Scheme shall be Implemented by SA Software

Voltage Selection Scheme shall be Implemented by SA Software

Voltage Selection Scheme shall be Implemented by SA Software

6912A

6922A

6932A

6942A

6914A
21/21N,50BF27/59,79

6924A
21/21N,50BF27/59,79

6934A
21/21N,50BF27/59,79

6944A
21/21N,50BF27/59,79

6916G 6914B

67/67N,50BF,27/59+BCU

6926G 6924B

67/67N,50BF,27/59+BCU

6936G 6934B

50/51,50/51N, 50BF+ BCU

6946G 6944B

67/67N,50BF,27/59+BCU

3
6912B

Voltage Selection Scheme shall be Implemented by SA Software

50/51,50/51N, 50BF+ BCU

6922B

6932B

6942B

6913B

6923B

6933B

6943B

6013 B
50/51,50/51N, 50BF+ BCU

6033B

Bus B1

6907B
50/51,50/51N, 50BF+ BCU

Bus B2

50/51,50/51N, 50BF+ BCU

Power Transformer (TR1) 30/40MVA 69/12-24kV


87 50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 4 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

North Bangkok (NKT) Terminal Station (2)


1

PM5-0403-WBX
MEA EGAT
1

Line NKT-695

Line NKT-696

Line NKT697

Line SIT-698

69102A
50/51,50/51N, 50BF + BCU 87 69103A

69112A

69113A

Bus A2 6023A

EGAT

6907A

2
50/51,50/51N, 50BF+ BCU

6953A

6963A

6973A

6983A

Voltage Selection Scheme shall be Implemented by SA Software

Voltage Selection Scheme shall be Implemented by SA Software

Voltage Selection Scheme shall be Implemented by SA Software

6912A

6962A

6972A

6982A

6954A
21/21N,50BF27/59,79

6964A
21/21N,50BF27/59,79

6974A
21/21N,50BF27/59,79

6984A
21/21N,50BF27/59,79

6956G 6954B

67/67N,50BF,27/59+BCU

6966G 6964B

67/67N,50BF,27/59+BCU

6976G 6974B

50/51,50/51N, 50BF+ BCU

6986G 6984B

67/67N,50BF,27/59+BCU

3
6952B

Voltage Selection Scheme shall be Implemented by SA Software

50/51,50/51N, 50BF+ BCU

6962B

6972B

6982B

6953B

6963B

6973B

6983B

6907B
50/51,50/51N, 50BF+ BCU

Bus B2

6023B
50/51,50/51N, 50BF+ BCU

EGAT

Power Transformer (TR2) 30/40MVA 69/12-24kV

50/51,50/51N, 50BF + BCU

87

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 5 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

North Bangkok (NKT-24kV) Terminal Station (3)


1

PM5-0403-WBX
1

HV Side (69kV)
6993A
87T

HV Side (69kV)
69103A
87T

50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF+ BCU

6992A

69102A

Transformer (TR1)

Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU

Transformer (TR2)

Y 27/59
50/51,50/51N,50BF 27/59/81+ BCU

4
410 410I 420 420I

C1I C1
50/51,50/51N, 50BF,27/59 + BCU

415I 415
50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414, 416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

401I1 C1A C1B

401I2 C2A C2B

401
50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 6 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Sainoi (SIT) Terminal Station (1)


1

PM5-0403-WBX
1

EGAT

MEA
Line SIT-791 Line SIT-792 Local Transformer (TR1) Line SIT-794

Bus A1 7013 A 7907A


7913A 7923A 7933A 7943A

Bus A2

2
50/51,50/51N, 50BF+ BCU

Voltage Selection Scheme shall be Implemented by SA Software

Voltage Selection Scheme shall be Implemented by SA Software

Voltage Selection Scheme shall be Implemented by SA Software

7912A

7922A

7932A

7942A

7914A
21/21N,50BF27/59,79

7924A
21/21N,50BF27/59,79

7934A
87T

7944A
21/21N,50BF27/59,79

7916G 7914B

67/67N,50BF,27/59+BCU

7926G 7924B

67/67N,50BF,27/59+BCU

7936G 7934B

50/51,50/51N, 50BF+ BCU

7946G 7944B

67/67N,50BF,27/59+BCU

3
7912B

Voltage Selection Scheme shall be Implemented by SA Software

50/51,50/51N, 50BF+ BCU

7922B

7932B

7942B

7913B

7923B

7933B

7943B

7013 B
50/51,50/51N, 50BF+ BCU

Bus B1

7907B
50/51,50/51N, 50BF+ BCU

Bus B2

Power Transformer (TR1) 30/40MVA 112/24kV

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 7 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Sainoi (SIT) Terminal Station (2)


1

PM5-0403-WBX
1

Local Transformer (TR2)

Line SIT-796

Bus A1 7907 A

Bus A2

2
50/51,50/51N, 50BF+ BCU

7953A

7963A

Voltage Selection Scheme shall be Implemented by SA Software

7952A

79462A

7954A
87T

7964A
21/21N,50BF27/59,79

7956G 7954B

50/51,50/51N, 50BF+ BCU

7966G 7964B

67/67N,50BF,27/59+BCU

3
7952B

Voltage Selection Scheme shall be Implemented by SA Software

7962B

7953B

7963B

Bus B1

7907B
50/51,50/51N, 50BF+ BCU

Bus B2

Power Transformer (TR2) 30/40MVA 112/24kV

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 8 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Sainoi (SIT-24kV) Terminal Station (3)


1

PM5-0403-WBX
1

HV Side (115kV)
7933A 7953A

HV Side (115kV)

7932A

7952A

2
7934A
87T

2
7954A
87T

7936G 7934B

50/51,50/51N, 50BF+ BCU

7956G 7954B

50/51,50/51N, 50BF+ BCU

7932B

7952B

7933B

7953B

Transformer (TR1)

Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU

Transformer (TR2)

Y 27/59
50/51,50/51N,50BF 27/59/81+ BCU

4
410 410I 420 420I

C1I C1
50/51,50/51N, 50BF,27/59 + BCU

415I 415
50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414, 416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

401I1 C1A C1B

401I2 C2A C2B

401
50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 9 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Bangson (BZ) Substation


1
6016G 6026G 6013 6023

PM5-0403-WBX
1

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

6012
6014B 6014A 6014A

6012

6022
6024B 6014B 6024A 6024A

6022

6024B

6906AG

2 Voltage Selection Scheme shall be Implemented by SA Software


6012 6913A 6913B 6913A 6913B 6923A 6923B 6923A 6923B 6903A 6903B 6933A 6933B 6933A 6933B 6903A 6902 6903B 6022

6906BG

6912
50/51,50/51N, 50BF+ BCU 6914 87 Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU

6922
50/51,50/51N, 50BF+ BCU 6924 87

6902
50/51,50/51N, 50BF + BCU

6932
50/51,50/51N, 50BF+ BCU 6934 87

3
Y

6916G

6926G

Y 27/59

6936G

27/59 50/51,50/51N,50BF 27/59/81+ BCU

50/51,50/51N,50BF 27/59/81+ BCU

410 410I

420 420I

430 430I

C1I

415I 415
50/51,50/51N, 50BF,27/59 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414, 416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

C1

401I1 C1A C1B

401I2 C2A C2B

402I1

401
50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 10 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Chatujak (CTJ) Substation


1
6016G 6026G 6013 6023

PM5-0403-WBX
1
6036G

6033

21/21N,50BF27/59,79

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

6012
6014B 6014A 6014A

6012

6022
6024B 6014B 6024A 6024A

6022

6032
6034B 6024B 6034A 6034A

6032

6034B

6906AG

2 Voltage Selection Scheme shall be Implemented by SA Software

6906BG

6913A

6913B 6913A 6913B

6923A

6923B 6923A 6923B 6903A 6903B

6933A

6933B 6933A 6933B

6943A

6943B 6943A 6943B

6912
50/51,50/51N, 50BF+ BCU 6914 87 Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU

6922
50/51,50/51N, 50BF+ BCU 6924 87

6902
50/51,50/51N, 50BF + BCU

6932
50/51,50/51N, 50BF+ BCU 6934 87 Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU

6942
50/51,50/51N, 50BF+ BCU 6944 87

3
Y

6916G

6926G

Y 27/59

6936G

6946G

27/59 50/51,50/51N,50BF 27/59/81+ BCU

50/51,50/51N,50BF 27/59/81+ BCU

410 410I

420 420I

430 430I

440 440I

BTS.

C1I

415I 415
50/51,50/51N, 50BF,27/59 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414, 416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

437 437
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 435,433,431,432,434 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C3I C3
50/51,50/51N, 50BF,27/59 + BCU

C1

401I1 C1A C1B

401I2 C2A C2B

402I1

402I2 C3A C3B

401
50/51,50/51N, 50BF + BCU

50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 11 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Ghoaklang (GK) Substation


1
6016G 6026G 6013 6023

PM5-0403-WBX
1

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

6012
6014B 6014A 6014A

6012

6022
6024B 6014B 6024A 6024A

6022

6024B

6906AG

2 Voltage Selection Scheme shall be Implemented by SA Software


6012 6913A 6913B 6913A 6913B 6923A 6923B 6923A 6923B 6903A 6903B 6933A 6933B 6933A 6933B 6903A 6902 6903B 6022

6906BG

6912
50/51,50/51N, 50BF+ BCU 6914 87 Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU

6922
50/51,50/51N, 50BF+ BCU 6924 87

6902
50/51,50/51N, 50BF + BCU

6932
50/51,50/51N, 50BF+ BCU 6934 87

3
Y

6916G

6926G

Y 27/59

6936G

27/59 50/51,50/51N,50BF 27/59/81+ BCU

50/51,50/51N,50BF 27/59/81+ BCU

410 410I

420 420I

430 430I

C1I

415I 415
50/51,50/51N, 50BF,27/59 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414, 416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

C1

401I1 C1A C1B

401I2 C2A C2B

402I1

401
50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 12 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Pradipat (PP) Substation


1
6016G 6026G 6013 6023

PM5-0403-WBX
1
6036G

6033

21/21N,50BF27/59,79

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

6012
6014B 6014A 6014A

6012

6022
6024B 6014B 6024A 6024A

6022

6032
6034B 6024B 6034A 6034A

6032

6034B

6906AG

2 Voltage Selection Scheme shall be Implemented by SA Software

6906BG

6913A

6913B 6913A 6913B

6923A

6923B 6923A 6923B 6903A 6903B

6933A

6933B 6933A 6933B

6912
50/51,50/51N, 50BF+ BCU 6914 87 Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU

6922
50/51,50/51N, 50BF+ BCU 6924 87

6902
50/51,50/51N, 50BF + BCU

6932
50/51,50/51N, 50BF+ BCU 6934 87

3
Y

6916G

6926G

Y 27/59

6936G

27/59 50/51,50/51N,50BF 27/59/81+ BCU

50/51,50/51N,50BF 27/59/81+ BCU

410 410I

420 420I

430 430I

C1I

415I 415
50/51,50/51N, 50BF,27/59 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414, 416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

437 437
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 435,433,431,432,434 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C3I C3
50/51,50/51N, 50BF,27/59 + BCU

C1

401I1 C1A C1B

401I2 C2A C2B

402I1

402I2 C3A C3B

401
50/51,50/51N, 50BF + BCU

50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 13 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Minburi (MB) Substation


1
7016G 7026G 7013 7023

PM5-0403-WBX
1

7013G

7023G

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

7014AG

7012

7014BG

6012

7024AG

7022

7024BG

7022

7014A 7906AG

7014B

7014A

7014B

7024A

7024B

7024A

7024B

2 Voltage Selection Scheme shall be Implemented by SA Software


7012 7022

7906BG 7913A 7913B 7923A 7923B 7903A 7903B 7933A 7933B

7913A

7913B 7923AG

7923A

7923B 7903AG

7933A

7933B

7903A 7902

7903B

7913AG

7912

7913BG

7922

7923BG

7902

7903BG
50/51,50/51N, 50BF + BCU

7933AG

7932

7933BG

50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF+ BCU 87 Y 27/59 27/59


50/51,50/51N,50BF 27/59/81+ BCU

50/51,50/51N, 50BF+ BCU

3
7916G Y 7926G 87 Y 27/59
50/51,50/51N,50BF 27/59/81+ BCU

3
7936G 87

50/51,50/51N,50BF 27/59/81+ BCU

410 410I

420 420I

430 430I

C1I

415I 415
50/51,50/51N, 50BF,27/59 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414, 416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

437I 437
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 435,433,431,432,434 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C3I C3
50/51,50/51N, 50BF,27/59 + BCU

C1

401I1 C1A C1B

401I2 C2A C2B

402I1

402I2 C3A C3B

401
50/51,50/51N, 50BF + BCU

402
50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 14 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Makasan (MS) Substation


1
6016G 6026G 6013 6023

PM5-0403-WBX
1
6036G

6013G

6023G

6033G

6033

21/21N,50BF27/59,79

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

6012

6014G

6012

6022

6024G

6022

6032

6034G

6032

6014A 6906AG

6014B

6014A

6014B

6024A

6024B

6024A

6024B

6034A

6034B

6034A

6034B

2 Voltage Selection Scheme shall be Implemented by SA Software

6906BG 6913A 6913B 6923A 6923B 6903A 6903B 6933A 6933B

6913A

6913B

6923A

6923B 6903AG

6933A

6933B

6912

6913G

6922

6923G

6902

6903BG
50/51,50/51N, 50BF + BCU

6932

6933G

50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF+ BCU 87 Y 27/59 27/59


50/51,50/51N,50BF 27/59/81+ BCU

50/51,50/51N, 50BF+ BCU

3
6916G Y 6926G 87 Y 27/59
50/51,50/51N,50BF 27/59/81+ BCU

3
6936G 87

50/51,50/51N,50BF 27/59/81+ BCU

410 410I

420 420I

430 430I

C1I

415I 415
50/51,50/51N, 50BF,27/59 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

418I 413,411,412,414, 416 Same As 415 Feeder 418


50/51,50/51N, 50BF 27/59/81,79 + BCU

427I 427
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 425,423,421,422,424 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

437I 437
50/51,50/51N, 50BF 27/59/81,79 + BCU

426I 435,433,431,432,434 Same As 427 Feeder 426


50/51,50/51N, 50BF 27/59/81,79 + BCU

C3I C3
50/51,50/51N, 50BF,27/59 + BCU

C1

401I1 C1A C1B

401I2 C2A C2B

402I1

402I2 C3A C3B

401
50/51,50/51N, 50BF + BCU

402
50/51,50/51N, 50BF + BCU

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 15 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Sansab (SS) Substation


1
6016G 6026G

PM5-0403-WBX
1

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

6012
6014G 6014

6022
6024G 6024

2
6907
6916G 50/51,50/51N, 50BF+ BCU 6913 6913G 6926G

Voltage Selection Scheme shall be Implemented by SA Software

6933 6933G

6912
50/51,50/51N, 50BF+ BCU

6932
50/51,50/51N, 50BF + BCU

3
87 Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU Y 27/59 50/51,50/51N,50BF 27/59/81+ BCU 87

410 410I

420 420I

430 430I

C1I

417I 417
50/51,50/51N, 50BF,27/59 + BCU 50/51,50/51N, 50BF 27/59/81,79 + BCU

416I 415,413,411,412,414, Same As 415 Feeder 416


50/51,50/51N, 50BF 27/59/81,79 + BCU

425I 425
50/51,50/51N, 50BF 27/59/81,79 + BCU

428I 423,421,422,424,426 Same As 427 Feeder 428


50/51,50/51N, 50BF 27/59/81,79 + BCU

C2I C2
50/51,50/51N, 50BF,27/59 + BCU

435I 435 50/51,50/51N, 50BF,79,81 + BCU 433,431,432,434,436 Same As 437 Feeder

438I 438 50/51,50/51N, 50BF,79,81+ BCU

C3I C3
50/51,50/51N, 50BF,27/59 + BCU

C1

401I1

401I2

402I1

402I2

401
C1A C1B 50/51,50/51N, 50BF + BCU C2A C2B

402
50/51,50/51N, 50BF + BCU C3A C3B

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 16 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

SINGLE LINE DIAGRAM

Single Busbar Configuration


1

PM5-0403-WBX
1

Voltage Selection Scheme


7016G 7013 7013G 7036G 7033 7033G

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

7012

7032
7034G 7034

7014G 7014

7012 7014

Voltage Selection Scheme shall be Implemented by SA Software

7032 7034

7907 7908

7907

7908

7907 7908

7012X 7012X 7913 7923 7032X 7933

7907
7916G 7913 7913G 50/51,50/51N, 50BF+ BCU 7926G 7923 7923G

7908
7936G 50/51,50/51N, 50BF+ BCU 7933 7933G

7912
7914G

7922
7924G

7932
7934G

50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF + BCU

7012X
7012 7014

7022X
7032 7034

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 17 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Voltage Selection

Single Busbar Configuration 3 Incoming Lines


1

PM5-0403-WBX
1

Voltage Selection Scheme


7016G 7013 7013G 7026G 7023 7023G 7036G 7033 7033G

21/21N,50BF27/59,79

21/21N,50BF27/59,79

21/21N,50BF27/59,79

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

67/67N,50BF,27/59+BCU

7012

7022
7024G 7024

7032
7034G 7034

7014G 7014

7012 7014

Voltage Selection Scheme shall be Implemented by SA Software

7022 7024

7032 7034

7907 7907

7907 7908

7908 7907 7908

7908 7022X 7012X

7022X

7012X 7913

7022X 7923

7032X 7933

7907
7916G 7926G 50/51,50/51N, 50BF+ BCU 7923 7923G

7908
7936G 50/51,50/51N, 50BF+ BCU 7933 7933G

7913 7913G

7912
7914G

7922
7924G

7932
7934G

50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF+ BCU

50/51,50/51N, 50BF + BCU

7012X
7012 7014

7022X
7022 7024

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

7032X
7032 7034

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 18 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Voltage Selection

One and a Half Busbar Configuration


1

PM5-0403-WBX
1

Example Voltage Selection Scheme

BUS A 7013 A

2
50/51,50/51N, 50BF+ BCU

BUS B 7013 B
50/51,50/51N, 50BF+ BCU

7913A A B

7913B

7913A
7912A 7912B

7912A
7914A

&

A
4

C B

7914A

7914B

4
7916AG
67/67N,50BF,27/59+BCU

7912C
7913C 7914C 7916BG
67/67N,50BF,27/59+BCU

7913C 7912C 7914C

&

21/21N,50BF27/59,79 21/21N,50BF27/59,79

7913B 7912B
Line KRT-791A Line KRT-791B

&
-Vdc

B
5

5
+Vdc

7914B
7913A +Vdc 7912A

A
7914A -Vdc

7913C +Vdc

C
7912C 7914C -Vdc

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

7913B

B
7912B 7914A

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 19 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Voltage Selection

6913A, B: Disconnecting Switch 6912A, B : Circuit Breaker 6914A, B: Disconnecting Switch

Example Double Busbar Double Breaker Configuration Voltage Selection Scheme


DC(+)

PM5-0403-WBX

Schematic Diagram

Close Command 6012A

6913AX, BX: DS Auxiliary Contact 6912AX, BX : CB Auxiliary Contact

6912AX

6912BX

Busbar Protn Bus A Close Command 6012B

Bus A

Busbar Protn Bus B

6912BX

6912AX

Bus B 6913A 6913B


6912AX

Logic Diagram
1 &
Close Com. 6012A

XXX

XXX VT Bus A VT Bus B

6912A
4

6912B

6914A

6914B 6916G 6912ABX

S Q
SET RESET
DC(-)

87B B

6912BX

1
6912ABX
High Speed Latching (S-R) Relay

Relay/BCU
6912BX
Close Com. 6012B

R Q
1 &
6912AB

Relay/BCU

Wiring Diagram
DESCRIPTION OF REVISIONS BY DATE

87B A

Outgoing Line #1
A B C

6912AX

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 20 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

VT Transfer Scheme

Double Busbar Single Breaker Configuration Voltage Selection Scheme


1

PM5-0403-WBX
1

6012
2

6022

6032
2

6014A

6014B 6012

6024A 6014A

6024B 6012

6034A 6014A

6034B 6014B 6012


3

6014B 6012

6022 Bus A Bus B


4

6024A

6044B 6022

6012 6013 6022 6023 6032 6033

6022 6032 6012 6032 6012 6022

6913A

6913B

6923A

6923B

6923A

6923B

BCU
6

6903A 6902

6903B

BCU
DESCRIPTION OF

BCU
REVISIONS BY DATE

METROPOLITAN

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 21 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

BCU 6902

POWER SYSTEM MAINTENANCE DEPARTMENT DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

VT Transfer Scheme

Double Busbar Single Breaker Configuration Voltage Selection Scheme(Option)


1

6012

6022

PM5-0403-WBX

6032

6014A Bus A-1


2

6014B

6024A

6024B

6034A

6034B

Bus B-1 Bus A-2 Bus B-2


3

Bus A-3 Bus B-3

6022X

6012 6013 6022 6023 6032 6033

6012 6013 6022 6023 6032 6033

6022 6032 6012 6032 6012 6022 6012 6013 6022 6023 6032 6033
5

6022 6032 6012 6032 6012 6022

6012X
6022 6032 6012 6032 6012 6022 6903A 6902
6012X

6913A

6913B

6903B

6903A 6902

6903B

6012

614A 6014B

BCU
A B

6903A
Transformer #2, #3, Same As Transformer #1

6903B
6022X
6022 6024 6014B DRN. ENGR.

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 22 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

6902

XXXXXXXXXXXXXXXXXXXXXXXX

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

VT Transfer Scheme

Example Voltage Selection Scheme : 2 Incoming Lines


1

PM5-0403-WBX
R Y B N
1

R Y B
X012

Single Busbar (H-Frame) Configuration


X032

&
X014

L1
X034

&
BCU-6032

L2

BCU-6012
2

PT BUS WIRE (Hardwire)

PT BUS WIRE (Hardwire)

GOOSE

X907
BCU-6907

GOOSE

X907

T21

GOOSE

X907
BCU-6907

&

T11

BCU-6907

&

T31

GOOSE

GOOSE GOOSE

X908
BCU-6908

X908
BCU-6907

T22

X908
BCU-6908

GOOSE

GOOSE

GOOSE

X012

T12

X012

T23

X032

T32

&
X014
BCU-6012

&
X014
BCU-6012

&
X034
BCU-6032

X913
5

T13

X913

T24

X933

T33
5

VT Inputs

VT Inputs

VT Inputs

BCU-6912
6

BCU-6922

BCU-6932
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 23 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Voltage Selection

Breaker Failure Protection (50BF)


1

PM5-0403-WBX
1

Cut-Off Sw.

Logic Diagram

I>

&
CB (52a) or I<
3

T1=XX Sec.

Tripping scheme
REVISIONS BY DATE

Protection Trip
4

1 &
For 115/69kV Only

SF6 Low
5

2nd

Stage

T2=0.0 Sec
5

DESCRIPTION

OF

METROPOLITAN

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 24 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

T1 = 0.15 Sec. for 115/69kV T1 = 0.50 Sec. for 12-24kV


A B C D E F

POWER SYSTEM MAINTENANCE DEPARTMENT DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Breaker Failure Protection

Example Breaker Failure Protection Scheme


1

PM5-0403-WBX
1

Double Busbar Single Breaker Configuration


Switch Switch Switch Switch Switch

Transformer Protective Devices eg. Buchholz

X014A

Transformer Protective Devices eg. Buchholz

X024A

Busbar Differential Prot. Zone A

Busbar Differential Protin Zone B

Trans. Bay-X912
2
TX

Switch

Line Bay-X012
&
OpEx 50BF Zone A

Switch

Trans. Bay-X922
TX

Switch

Line Bay-X022
&
OpEx 50BF Zone A

Switch

BC Bay-X902
X903A

Switch

&
OpEx

50BF Zone A

GOOSE
Str

GOOSE GOOSE
RX

1 & &
X014B

TX

GOOSE
Str

GOOSE GOOSE
RX

1 & &
X024B

TX

GOOSE
Str

1 & &
X903B

TX

LN : RBRF

RX 50BF Zone B 50BF Zone AB

LN : RBRF

RX 50BF Zone B 50BF Zone AB

LN : RBRF

50BF Zone B

RX

50BF
SF 6 Low 2nd Stage

GOOSE
50 BF Tripping

50BF
SF 6 Low 2nd Stage

GOOSE
50 BF Tripping

50BF
SF 6 Low 2nd Stage 50BF Zone A 50 BF Tripping

GOOSE

50BF Zone B

X014A X014B

X024A X024B

&

&

&
X903A X903B

&

BI(s)
1 Tripping (87)

BI(s)
1

+VDC
50BF Zone A 50BF Zone B

Tripping (87)

+VDC
50BF Zone A 50BF Zone B

+VDC 3

+VDC 3
Transformer Protective Devices eg. Buchholz
&
X014A X014B

&

50BF Zone AB X024A

&
X024B

&

50BF Zone AB

+VDC

87
Differential relay (87)

Transformer Protective Devices eg. Buchholz

20/21N

87
Differential relay (87)

20/21N

50/51,51/51N,BCU
Tripping CCT#1 Block Close CCT Tripping CCT#2

X913A

X014A

X923A

X024A

&
OpEx Str

50BF Zone A OpEx

&
TX Str

50BF Zone A

&
OpEx

50BF Zone A OpEx

&
TX Str

50BF Zone A

1 & &
X913B

GOOSE

GOOSE 1 & &


X014B

TX

GOOSE
Str

GOOSE 1 & &


X024B

Reset
TX

1 & &
X923B

LN : RBRF

RX 50BF Zone B 50BF Zone AB

LN : RBRF

RX 50BF Zone B 50BF Zone AB

LN : RBRF

RX 50BF Zone B 50BF Zone AB

LN : RBRF

RX 50BF Zone B 50BF Zone AB

S 50BFX R
86 BF (High Speed)

50BF
SF 6 SF 6 Low 2nd Stage

GOOSE
50 BF Tripping SF 6

50BF
SF 6 Low 2nd Stage

GOOSE
50 BF Tripping SF 6

50BF
SF 6 Low 2nd Stage

GOOSE
50 BF Tripping SF 6

50BF
SF 6 Low 2nd Stage

GOOSE
50 BF Tripping

X913A X913B

X014A X014B 50BF 410

X923A X923B

X024A X024B 50BF 420

&

&

&

&

-VDC
Trip TC1 Trip TC2

+VDC
50BF Zone A 50BF Zone B 50BF Zone A 50BF Zone B 50BF Zone A 50BF Zone B 50BF Zone A 50BF Zone B

&
X913A X913B

&

50BF Zone AB X014A

&
X014B

&

50BF Zone AB

+VDC
X923A

&
X923B

&

50BF Zone AB

+VDC
X024A

&
X024B

&

50BF Zone AB

+VDC

50/51/51N,BCU

67/67N,BCU
Block Close CCT Tripping CCT#1 Tripping CCT#2 Reset Block Close CCT

50/51/51N,BCU

67/67N,BCU
Tripping CCT#1 Tripping CCT#2 Reset Block Close CCT

Tripping CCT#1 Tripping CCT#2 Reset

Tripping CCT#1 Tripping CCT#2 Reset

S 50BFX R
86 BF (High Speed)

S 50BFX R
86 BF (High Speed)

S 50BFX R
86 BF (High Speed)

S 50BFX R
86 BF (High Speed) DESCRIPTION OF REVISIONS BY DATE

6 -VDC
Trip TC1 Trip TC2

METROPOLITAN
-VDC
Trip TC1 Trip TC2

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 25 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

-VDC
Trip TC1 Trip TC2

-VDC
Trip TC1 Trip TC2

POWER SYSTEM MAINTENANCE DEPARTMENT DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Breaker Failure Pro.

Example Breaker Failure Protection Scheme


1

PM5-0403-WBX
1

Single Busbar (H-Frame) Configuration


Switch Switch Switch Switch

Transf. Bay-X912
Transformer Protective Devices eg. Buchholz

Switch

Line Bay-X012
X014 OpEx

Switch
Transformer Protective Devices eg. Buchholz

Transf. Bay-X922
TX

Switch

Line Bay-X022
X024 OpEx

Switch

& 1 &
TX

&
TX

TX

GOOSE GOOSE
RX

Str

GOOSE GOOSE
RX

GOOSE GOOSE
RX

Str

1 &

GOOSE GOOSE
RX

LN : RBRF

LN : RBRF

50BF
SF 6 Low 2nd Stage 50 BF Tripping 50BF : X912

50BF
SF 6 Low 2nd Stage 50 BF Tripping 50BF : X922

50BF : X022

&

50BF : X922

&

50BF : X012

&

50BF : X912

&

BI

X6907

BI

X907

Tripping (87)

+VDC
1 &
X014

+VDC

Tripping (87)

+VDC
1 &
X924

+VDC 3

3
Transformer Protective Devices eg. Buchholz

87
Differential relay (87)
X913 OpEx Str

20/21N
X014

Transformer Protective Devices eg. Buchholz

87
Differential relay (87)
X923 OpEx Str

20/21N
X024

& 1 &
TX

OpEx

& 1 &
TX

& 1 &
TX

OpEx

& 1 &
TX

GOOSE GOOSE
RX

Str

GOOSE GOOSE
RX

GOOSE GOOSE
RX

Str

GOOSE GOOSE
RX

LN : RBRF

LN : RBRF

LN : RBRF

LN : RBRF

50BF
SF 6 SF 6 Low 2nd Stage 50 BF Tripping 50BF : X012

50BF
SF 6 Low 2nd Stage 50 BF Tripping 50BF : X912

50BF
SF 6 Low 2nd Stage 50 BF Tripping 50BF : X022

50BF
SF 6 Low 2nd Stage 50 BF Tripping 50BF : X922

50BF : X022

&

50BF : X922

&

50BF : X022

&

50BF : X922

&

50BF : X012

&

50BF : X912

&

50BF : X012

&

50BF : X912

&

X6907

X6907

X907

X907

+VDC
1
50BF 410 X913

+VDC
1 &
X014 50BF 420

+VDC
1
X923

+VDC
1 &
X924

&

&

50/51,50/51NBCU
Tripping CCT#1 Tripping CCT#2 Reset Block Close CCT

67/67N+BCU
Tripping CCT#1 Tripping CCT#2 Reset Block Close CCT

50/51,50/51NBCU
Tripping CCT#1 Tripping CCT#2 Reset

67/67N+BCU
Tripping CCT#1 Tripping CCT#2 Reset Block Close CCT

S 50BFX R
86 BF (High Speed)

S 50BFX R
86 BF (High Speed)

S 50BFX R
86 BF (High Speed)

S 50BFX R
86 BF (High Speed) DESCRIPTION OF REVISIONS BY DATE

6 -VDC
Trip TC1 Trip TC2

METROPOLITAN
-VDC
Trip TC1 Trip TC2

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 26 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

-VDC
Trip TC1 Trip TC2

-VDC
Trip TC1 Trip TC2

POWER SYSTEM MAINTENANCE DEPARTMENT DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Breaker Failure Pro.

Example Breaker Failure Protection Scheme


1

PM5-0403-WBX
1

MV Single Busbar Configuration


Switch Switch Switch Switch Switch

Cap/Outgoing Feeders
C1I/417I

Incoming #1
410I OpEx

Cap/Outgoing Feeders
418I OpEx TX

Bus-Section
401I1

Incoming #2
420I1 OpEx

OpEx Str

&
TX

& GOOSE GOOSE


RX

&
TX

&
OpEx

50BF Zone BB1

&
TX

GOOSE GOOSE
RX

Str

Str

GOOSE GOOSE
RX

Str

1 &
401I2

TX

GOOSE
RX

Str

GOOSE GOOSE
RX

LN : RBRF

LN : RBRF

LN : RBRF

LN : RBRF

50BF Zone BB2

LN : RBRF

50BF

50BF
50 BF Tripping 50BF : C1

50BF

50BF
50 BF Tripping 50BF : C1

50BF
GOOSE
50 BF Tripping 50BF : Cap

50BF : 417

+VDC
1

50BF : 417

+VDC
1

50BF : 427

+VDC
1

50BF : 415

50BF : 415 50BF : 426

50BF : 425

Tripping

+VDC

50BF : 418

Tripping
50BF : 401 BB1

+VDC

50BF : C2 50BF : 410 50BF : 420 X401I

50BF : 428

&
X401I

+VDC

&

+VDC

50BF : 401 BB2

&
X014

+VDC

Protection+BCU

Protection+BCU
Trip TC1 Trip TC2

Protection+BCU

Protection+BCU
Trip TC1 Trip TC2

Protection+BCU
Trip TC1 Trip TC2

Tripping Criteria for 12-24kV System


50BF of Capacitor and Outgoing feeders Incoming and Bus Section 50BF of Bus-section 12-24kV Incoming I and II 50BF of 12-24kV Incoming HV. Circuit Breaker (Transformer) and Bus-Section
A B C D E F
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 27 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Breaker Failure Pro.

Automatic Function : Coupler Throwover Scheme


1

PM5-0403-WBX
1

MMI SCADA
Control SW.
21/21N : PTUV
Line 1

Auto-Manual Logic Diagram


1
Caution : 1. CTO shall be implemented on bay level (Bus Coupler BCU). 2. Undervoltage protections shall be located in line protections both Distance(21/21N) and Directional Overcurrent (67/67N)Relay. 3. Switching devices status (e.g. CB,DS, etc) and Undervoltage tripping signal shall be reported by GOOSE via substation LAN. 4. Closing and Tripping command shall be reported by GOOSE via substation LAN. 5. Communication system failure shall not cause of CTO mis-operation and/or malfunction. LAN A Switch Switch LAN B

Ut< 0.2 s Ut< 0.2 s Ut< 0.2 s Ut< 0.2 s

Op

U< (3-) : Str Ut<(3-) : Op


Or Pos Seq. U< PTUV 21/21N

1
Op

GOOSE
2

BCU : PTUV
Line 1

U<(3-) : Str Ut<(3-) : Op


Or Pos Seq. U< 67/67N (BCU) PTUV

Op

GOOSE

21/21N : PTUV
Line 2

1
Op

BCU : PTUV
Line 2 3

Undervoltage Detection for CTO Function

X012 X014A X014B X903A X902 X903B

&

&

S Q

Auto

MMI SCADA

CTO
4

X024A X024B X022 MMI SCADA Control SW. BB. Prot. 50BF X913A X913B X923A X923B X933A X933B MMI

R Q
1

Manual

SCADA LED

86T1

&
5

X012 Local X902 Local

1
86T2

& &
OF

&

X022 Local X903A X903B #1

1
86T2

PT.MCBs L1 PT.MCBs L2
DRN. ENGR.

DESCRIPTION

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 28 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Coupler Throwover

Automatic Function : Coupler Throwover Scheme


S
1

PM5-0403-WBX
1

Function Logic Diagram (Transfer)


21/21N : PTUV
Line 1

CTO Ut< 0.2 s Ut< 0.2 s


Str Str Op

1
Op

BCU : PTUV
Line 1 2

1 & & Trip X012 S Q M-L1 R Q


MMI
Memorized CTO L1 Started
3 2

21/21N : PTUV BCU : PTUV


Line 2

X902 X022 X012


3

&
& 1
21/21N : PTUV

Close X902

Alarm CTO Started

MMI SCADA

Line 2 4

Ut< 0.2 s Ut< 0.2 s


Str Str

Op

1
Op

BCU : PTUV
Line 2

21/21N : PTUV BCU : PTUV


Line 1

&
1

&

Trip X022

&
X902

S R

Q Q

MMI SCADA LED


5

CTO-O/P
Memorized CTO operated

X902
5

X012 X022

&
&

S Q M-L2 R Q
DESCRIPTION

MMI
Memorized CTO L2 Started

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 29 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Coupler Throwover

Automatic Function : Coupler Throwover Scheme


S
1

PM5-0403-WBX
1

Function Logic Diagram (Re-Transfer)


Str

CTO

Q
21/21N : PTUV
Line 1
Str Op
&

1
&

BCU : PTUV
Line 1

Op

T1 60 s

Close X012
Alarm
MMI SCADA

Str

21/21N : PTUV
Line 2

Op

&

&
1

Str

CTO start Re-Transfer

BCU : PTUV
Line 2 3

Op

&

X012 X902 X022

1 &
4
Str

Trip X902 &

Alarm CTO
Re-Transferred

MMI SCADA

21/21N : PTUV
Line 1

Op

&

Str

1
&

X902

BCU : PTUV
Line 1

Op

Str

21/21N : PTUV
Line 2

Op

&

&
1

T2 60 s

Close X022 1

S R

Q Q
5

Str

CTO-O/P

BCU : PTUV
5 Line 2

Op

&

X012 X902 X022

DESCRIPTION

OF

REVISIONS

BY

DATE

&

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 30 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Coupler Throwover

Automatic Function : Coupler Throwover Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Switch to Manual)


S Q

X012
CTO

X902 X022

&
2

X012 X902 X022 X012


3

&

&

Alarm
CTO switch to Manual CB In-corrected Position

MMI

X902 X022

& &
Alarm
CTO switch to Manual CB Failed to Trip

MMI

Trip- X012 X012


4

&

Trip- X022 X022

&

T3 1.0 s

#1

Trip- X902 X092


5

& &
Alarm
CTO switch to Manual CB Failed to Close

MMI

Close- X012 X012

&

Close- X022 X022


6

&

1
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 31 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

Close- X902 X092


A B

&
C D E F

DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

CHK.

SUPPLIER TITLE

XXXXXXXXXXXXXXXXXXXXXXXX

Coupler Throwover

Automatic Function : Bus Throwover Scheme


1

PM5-0403-WBX
1

Auto-Manual Logic Diagram


LAN

MMI
BI

Switch U< L1-L2(L3) Str GOOSE


2

SCADA
2

BI

U< L1-L2(L3) Op BCU (Incoming Feeders) Hardwire Interface

Control SW.

U< L1-L2(L3) Str

B0

U<L1-L2(L3) Op

B0 Ut< Op (5 Sec) 1- Undervoltage Relay, 27/59

410
3

410I
BCU(I1)

&
401 I1 401 401 I2

S Q

Auto

MMI SCADA

&

BTO
4

420I 420
U<L1-L2(L3) Op
BCU(I2)

MMI SCADA Control SW. BB. Prot. 50BF 50/51,50/51N L1 MMI

R Q

Manual

SCADA LED

50/51,50/51N L2
Caution : 1. BTO shall be implemented on bay level (Bus Section BCU). 2. Undervoltage Relays shall be located at the both incoming lines and send the tripping signal to the incoming BCU via hardwire interface. 3. Switching devices status (e.g. CB,DS, etc) and Undervoltage tripping signal shall be reported by GOOSE via substation LAN. 4. Closing and Tripping command shall be reported by GOOSE via substation LAN. 5. Communication system failure shall not cause of BTO mis-operation and/or malfunction.

401 I1 401 I2 410 Local 401 Local 420 Local #1 PT.MCB L1 PT.MCB L2

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 32 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Bus Throwover Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Transfer)


S Q U< L1-L2(L3) U< Str:BCU(I2) R Q
Ut< 5.0 s

Op
BCU(I1)

BTO
2

1 & & Trip 410 S Q M-I1 R Q


MMI
Memorized BTO I1 Started
3 2

410 401 420

&

& 1
Op

Close 401

Alarm BTO Started

MMI SCADA

U<L1-L2(L3) U< Str : BCU(I1)

Ut< 5.0 s

4 BCU(I2)

& & Trip 420


401

&

S R

Q Q

MMI SCADA LED


5

420 401 410


5

BTO-O/P
Memorized BTO operated

&

&

S Q M-I2 R Q
DESCRIPTION

MMI
Memorized BTO I2 Started

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 33 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Bus Throwover Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Re-Transfer)


S Q
Str

BTO

U< : BCU(I1) U< : BCU(I2)

Op Str

&

Op

&

&

T1 60 s

Close 410
Alarm
MMI SCADA

410 401 420

BTO start Re-Transfer

& 1 Trip 401 &


Alarm BTO
Re-Transferred MMI SCADA

Str

401
&

U< : BCU(I1) U< : BCU(I2)

Op Str Op

&

&

T2 60 s

Close 420 S 1 R Q Q
5

410 401 420


5

BTO-O/P
Memorized BTO operated

&

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 34 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Bus Throwover Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Switch to Manual)


S Q 410 BTO 401 420

&

#1

Q 410 401 420

1 &

T3 6.0 s

Alarm
BTO switch to Manual CB In-corrected Position

MMI

&
410
3

401 420

&

Trip- 410 410

& 1

&

Alarm
BTO switch to Manual CB Failed to Trip

MMI

Trip- 420 420

&

T4 1.0 s

Trip- 401 401


5

& &
Alarm
BTO switch to Manual CB Failed to Close

MMI

Close- 410 410

&

Close- 420 420


6

&

1
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN Close- 401 401


A B C D E F

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 35 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

&

DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

CHK.

SUPPLIER TITLE

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Load Shedding Scheme


1

PM5-0403-WBX
1

Ut< (U<=80%, t=60ms)Op CB status Closed

Function Logic Diagram


F< (Step 1 : 49.0Hz)) T1 0.15 s

UF Step 1
ON (MMI) ON(SCADA) OFF(MMI) OFF(SCADA)
2

TO MMI TO SCADA

S 1 R

Q Q

&
Set (MMI) Set (SCADA) Reset (MMI)

UF Step 1 T/R
S R Q 11 Q

TO (MMI) TO(SCADA) #T1 #R1


2

UF Step 2
ON (MMI) ON(SCADA) OFF(MMI) OFF(SCADA)

TO MMI TO SCADA F< (Step 2 : 49.8Hz)) T2 0.15 s

Reset (SCADA)

S 2 R

Q Q

&
Set (MMI) Set (SCADA) Reset (MMI)

UF Step 2 T/R
S R Q 12 Q

TO (MMI) TO(SCADA) #T2 #R2

UF Step 3
3

TO MMI TO SCADA F< (Step 3 : 48.6Hz)) T3 0.15 s

Reset (SCADA)
3

ON (MMI) ON(SCADA) OFF(MMI) OFF(SCADA)

S 3 R

Q Q

&
Set (MMI) Set (SCADA) Reset (MMI)

UF Step 3 T/R
S R Q 13 Q

TO (MMI) TO(SCADA) #T3 #R3

UF Step 4
ON (MMI) ON(SCADA)
4

TO MMI TO SCADA F< (Step 4 : 48.3Hz)) T4 0.15 s

Reset (SCADA)

S 4 R

Q Q

OFF(MMI) OFF(SCADA)

&
Set (MMI) Set (SCADA) Reset (MMI)

UF Step 4 T/R
S R Q 14 Q

TO (MMI) TO(SCADA) #T4 #R4

UF Step 5
ON (MMI) ON(SCADA) OFF(MMI) OFF(SCADA)
5

TO MMI TO SCADA F< (Step 5 : 47.9Hz)) T5 0.15 s

Reset (SCADA)

S 5 R

Q Q

&
Set (MMI) Set (SCADA) Reset (MMI) Reset (SCADA)

UF Step 5 T/R
S R Q 15 Q

TO (MMI) TO(SCADA) #T5 #R5


5

Command ON-OFF from LN : IHMI (Station Level : Multicast)

ON OFF Group
LAN Switch

Caution : 1. Load Shedding Scheme shall be implemented on bay level (all outgoing feeder BCUs). 2. Underfrequency and Undervoltage protections shall be located in all outgoing feeder BCUs. 3. Switching devices status (CB,DS, etc) shall be connected to the BCU binary inputs via copper wire. 4. ON-OFF Group, Set, Reset command shall be controlled by HMI
A B C

U< Op
PTUV

Command SET-RESET from LN : IHMI (Station Level : Multicast)

UF Trip and Restore


DESCRIPTION OF REVISIONS BY DATE

F1< Op F2< Op F5< Op


BCU (Feeder) PTUF

GOOSE
DRN.

METROPOLITAN
CHK. SUPPLIER TITLE ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 36 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

Underfrequency Protection for ALS Function


E F

XXXXXXXXXXXXXXXXXXXXXXXX

Load Shedding

Automatic Function : Load Shedding Scheme


1

PM5-0403-WBX
1

OFF (MMI)

Tripping Logic Diagram


UF Step 1 ON Auto-Reclose Scheme
TO MMI #T1 Restoration (Reset) UF-T-M Q

&

T8=0.5 s pulse

ON (MMI)

S-R 22 Q S-R 23 Q
2

Q 21 R Q

&
Tripping #1 Restoration #1

Control SW. ON (MMI), SCADA CB Status-Closed OFF (MMI), SCADA

1
UF Step 2 ON

1 & 1
S Q A/R R Q S Q A/R-M R Q
2

S-R 24 Q S-R 25 Q

TO MMI #T2

ON (MMI)

Q
Tripping #2

Control SW.

S-R 21 Q S-R 23 Q S-R 24 Q


3

22 R Q

&
Restoration #2 CB-Status Closed
3

1
UF Step 3 ON
I>,I>>,Ie>,Ie>> (start) #T3 79In-progress/Lockout

S-R 25 Q TO MMI

ON (MMI)

S R

Q 23 Q
Tripping #3

&

Trip Feeder CB

S-R 21 Q S-R 22 Q S-R 24 Q


4

&
Restoration #3

1
T6=1Sec

1
UF Step 4 ON

Pulse

CB-Status Open

&

S-R 25 Q TO MMI #T4

S Q UF-T-M R Q

ON (MMI)

S-R 21 Q S-R 22 Q S-R 23 Q S-R 25 Q


5

Q 24 R Q

&
Tripping #4 Restoration #4

1
UF Step 5 ON
TO MMI #T5
5

ON (MMI)

S-R 21 Q S-R 22 Q S-R 23 Q S-R 24 Q


6

Q 25 R Q

&
Tripping #5 Restoration #5

1
DESCRIPTION OF REVISIONS BY DATE

Command ON-OFF from LN : IHMI (Station & Local Level : Unicast)


A

UF Step Selection (Individual Feeder)


B C D E F

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 37 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Load Shedding

Automatic Function : Load Shedding Scheme


1

PM5-0403-WBX
1

OFF (MMI)

Restoration Logic Diagram


UF Step 1 ON
ON (MMI) TO MMI #R1 Restoration #1 Restoration (Reset) UF-T-M Q

Auto-Reclose Scheme

&

T8=1.0 s pulse

S-R 22 Q S-R 23 Q
2

Q 21 R Q

&

Control SW. ON (MMI), SCADA

1
Tripping #1

1 & 1
S Q A/R R Q S Q A/R-M R Q
2

S-R 24 Q S-R 25 Q

CB Status-Closed OFF (MMI), SCADA #R2


Control SW.(OFF A/R)

UF Step 2 ON
ON (MMI)

TO MMI

Q
Restoration #2

S-R 21 Q S-R 23 Q S-R 24 Q


3

22 R Q

&
UF-T-M Q
3

1
Tripping #2 CB-Status Open

S-R 25 Q

UF Step 3 ON
ON (MMI)

TO MMI #R3 Restoration #3

& & 1

&
T9=3.0 Sec

Close Feeder CB

S R

Q 23 Q

S-R 21 Q S-R 22 Q S-R 24 Q


4

Restoration In-Progress To MMI

1
Tripping #3
T7=1Sec

S-R 25 Q

Pulse

S Q UF-T-M R Q

UF Step 4 ON
ON (MMI)

TO MMI #R4 Restoration #4

CB-Status Close

& 1

S-R 21 Q S-R 22 Q S-R 23 Q S-R 25 Q


5

Q 24 R Q

&
CB-Status Open

&

T10=1 Sec

1
Tripping #4

Restoration Failure To MMI

UF Step 5 ON
ON (MMI)

TO MMI #R5

S-R 21 Q S-R 22 Q S-R 23 Q S-R 24 Q


6

Q 25 R Q

&
Restoration #5 Tripping #5

1
DESCRIPTION OF REVISIONS BY DATE

UF Step Selection (Individual Feeder)


A B C D E F

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 38 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Load Shedding

X012
1

Automatic Function : Line Throwover Scheme


& &

PM5-0403-WBX
1

X022 Line Prefer Selection


MMI SCADA Control SW.

Auto-Manual Logic Diagram


LAN A Switch Switch

S Q L-P-1 R Q Line X022-Prefer

Line X012-Prefer

MMI SCADA

MMI SCADA Control SW.

LAN B

1
21/21N

U< (3-) : Str Ut<(3-) : Op


Or Pos Seq. U< PTUV

GOOSE
2

MMI SCADA Control SW.

MMI

SCADA

U<(3-) : Str
Or Pos Seq. U< 67/67N (BCU) PTUV

Ut<(3-) : Op

GOOSE

21/21N : PTUV
Line 1 3

Ut< 0.2 s Ut< 0.2 s Ut< 0.2 s Ut< 0.2 s

Op

Undervoltage Detection for LTO Function

1
Op

BCU : PTUV
Line 1

&
Op

S Q

Auto

MMI SCADA

21/21N : PTUV
Line 2

1
Op

& 1 & &


MMI
MMI SCADA Control SW. BB. Prot. 50BF X012 Local X022 Local X014

BCU : PTUV
Line 2 4

LTO
4

X012 X014 X907 X908 X024 X022

R Q

Manual
X913 86T1 X923 86T2 X933 86T2
DESCRIPTION

SCADA LED

&
5

& &
OF

&
6

X024 #1 PT.MCBs L1 PT.MCBs L2


DRN. ENGR.

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 39 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Line Throwover

Automatic Function : Line Throwover Scheme


1

PM5-0403-WBX
1

S Q LTO R Q S Q L-P-S R Q

Function Logic Diagram (Transfer)


X012

1
21/21N : PTUV
Line 1

Ut< 0.2 s Ut< 0.2 s


Str Str

Op

1
Op

S Q M-L1 R Q

MMI
Memorized LTO L1 Started

&

Trip X012 Close X012


2

BCU : PTUV
Line 1

& 1
Alarm LTO Started
MMI SCADA

&

21/21N : PTUV BCU : PTUV


Line 2

X022 X012
3

Alarm LTO Operated

MMI SCADA

&

X012

& 1 S R Q Q
Memorized LTO operated

&
X022

LTO-O/P

&

X022
21/21N : PTUV
Line 2

Ut< 0.2 s Ut< 0.2 s


Str Str

Op

1
Op

1 & 1 S Q M-L2 R Q &


MMI
Memorized LTO L2 Started
DESCRIPTION OF

&

Trip X022 Close X022

BCU : PTUV
Line 2

21/21N : PTUV
5

BCU : PTUV
Line 1

&

X012 X022

REVISIONS

BY

DATE

&
A B C D E F

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 40 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Line Throwover

Automatic Function : Line Throwover Scheme


1

PM5-0403-WBX
1

S Q LTO R Q S Q L-P-S R Q
21/21N : PTUV
Line 1
Str

Function Logic Diagram (Re-Transfer)


X012
Str Op
&

1
1
&

&

Trip X012 Close X012


2

BCU : PTUV
Line 1

Op

T1 60 s

Str

&
&

&

21/21N : PTUV
Line 2

Op

Str

1
&

BCU : PTUV
Line 2

Op

Alarm

MMI SCADA

X012 X022 X012

&

LTO Re-Transferred

1 &
X022

S & 1 R

Q Q
LTO Operated
4

LTO-O/P

4
Str

21/21N : PTUV
Line 1

Op

&

X022
1

Str

BCU : PTUV
Line 1

Op

&

1 &
T2 60 s

&

Trip X022 Close X022

Str

21/21N : PTUV
5 Line 2

Op

&

Str

1
&

1
Alarm
LTO Start Re-Transfer MMI SCADA
DESCRIPTION OF

&

BCU : PTUV

Op

X012 X022

REVISIONS

BY

DATE

&

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 41 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Line Throwover

Automatic Function : Line Throwover Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Switch to Manual )


S Q LTO R Q

X012 X022 X012 X022

& 1 & &


Alarm
LTO switch to Manual CB In-corrected Position
2

MMI

Trip X012 X012

& & 1 & 1 & & 1


T3 1.0 s

Alarm
LTO switch to Manual CB Failed to Trip

MMI

Trip X022 X012


S Q L-P-S R Q

#1

Line X022-Prefer X012

Alarm

MMI
4

X022 Line X012-Prefer X012 X022

LTO switch to Manual Line Prefer In-corrected Position

& &
Alarm
LTO switch to Manual CB Failed to Close

MMI
5

Close X012 X012

& 1

Close X022 X012

&
DRN. ENGR.

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 42 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Line Throwover

Automatic Function : Bus Throwover 3 Incoming Lines Scheme


1

PM5-0403-WBX
1

Line # 1

Line # 2

Line # 3

Y
2
27/59 50/51,50/51N,50BF 27/59/81+ BCU

Y
2
27/59 50/51,50/51N,50BF 27/59/81+ BCU 27/59 50/51,50/51N,50BF 27/59/81+ BCU

410

420

430

410I

420I

430I

BTO-401
3

BTO-402

401I1

401I2

402I1

402I2

401
50/51,50/51N, 50BF + BCU

402
50/51,50/51N, 50BF + BCU

BTO 401
5

Line # 1 U<
Trip Close

Line # 2 U<
Trip Close

Line # 3 U<
Trip Close

Remark

410 -

401 -

420 420

401 402

430 430

402 402
BTO-401: Auto BTO-401: Man
5

402

21/21N : 27/59 : 50BF : 50/51 : 50/51N : 67/67N : 79 : 81 : 87 : BCU :

Distance Protection( Phase and Ground Fault Protection) Under/Over Voltage Protection Breaker Failure Protection Overcurrent Protection Earth Fault Protection Directional Overcurrent/Earth Fault Protection Automatic Re-closing Function Under/Over Frequency Protection Transformer Differential Protection Bay Controller

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 43 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Bus Throwover 3 Incoming Lines Scheme


1

PM5-0403-WBX
1

BTO-401 Auto-Manual Logic Diagram


LAN

MMI
BI

Switch U< L1-L2(L3) Str GOOSE


2

SCADA
2

BI

U< L1-L2(L3) Op BCU (Incoming Feeders) Hardwire Interface

Control SW.

U<L1-L2(L3) Op

U< L1-L2(L3) Str

B0

410 410I
BCU(I1) 3

B0 Ut< Op (5 Sec) 1- Undervoltage Relay, 27/59

401 I1 401 401 I2


U<L1-L2(L3) Op

& &
MMI SCADA

S Q

Auto

MMI SCADA

420 420I
BCU(I2) 4

BTO 401
MMI

BI (BCU) by pass sw. 402

&
Manual

Control SW. BB. Prot.

1 &

50BF 50/51,50/51N L1 50/51,50/51N L2 401 I1 401 I2 410Local 401 Local 420 Local #1 PT.MCB L1

R Q

Manual

SCADA LED

BTO 402
BTO 402 Manual 5

Difference Voltage Level Shutdown Transformer#3 Maintenance Busbar#3

To Start Sequence # BTO 401-A Caution : 1. BTO shall be implemented on bay level (Bus Section BCU). 2. Undervoltage protection shall be located at both incoming lines and issue the tripping signal to incoming BCU. 3. Switching devices status (CB,DS, etc) and Undervoltage tripping signal shall be reported by GOOSE via substation LAN. 4. Closing and Tripping command shall be reported by GOOSE via substation LAN. 5. Communication system failure shall not cause of BTO mis-operation and/or malfunction.
A B C

DESCRIPTION

OF

REVISIONS

BY

DATE

PT.MCB L2 BTO-401 O/P : Q BTO-402 O/P : Q


BCU 402 DRN. ENGR.

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 44 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Bus Throwover

Automatic Function : Bus Throwover (BTO-401) Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Transfer)


S R Q Q
BTO-401

U< L1-L2(L3)
U< Str:BCU(I2)

Ut< 5.0 s

Op
BCU(I1)

& &

1 Trip 410 S Q M-I1 R Q


MMI
Memorized BTO I1 Started
3 2

401 420
BTO 401-A

410

&

&
1
Ut< 5.0 s
Op

Close 401

Alarm BTO 401 Started

MMI SCADA

U< L1-L2(L3)
U< Str:BCU(I1)

4 BCU(I2)

& &

401 420
BTO 401-A

Trip 420

&
401

S R

Q Q

BTO-O/P
Memorized BTO operated

MMI SCADA LED


BTO-401 sw.to Man BTO-402 sw.to Man

420

&

&
6

S Q M-I2 R Q
DESCRIPTION

MMI
Memorized BTO I2 Started

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 45 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Bus Throwover (BTO-401) Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Switch to Manual )


S R Q Q
BTO-401

410 401 420

&

#1

410 401 420

1 &

T1 6.0 s

Alarm

MMI

BTO 401 switch to Manual CB-In-corrected Position

&
410
3

401 420

&

Trip- 410 410

& 1

&

Alarm

MMI

BTO 401 switch to Manual CB Failed to Trip


4

Trip- 420 420

&

T2 1.0 s

Close- 401 401

&

&

Alarm
BTO switch to Manual CB Failed to Close

MMI

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 46 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Bus Throwover 3 Incomings Lines Scheme


1

PM5-0403-WBX
1

BTO-402 Auto-Manual Logic Diagram


LAN

MMI
BI

Switch U< L1-L2(L3) Str GOOSE


2

SCADA
2

BI

U< L1-L2(L3) Op BCU (Incoming Feeders) Hardwire Interface

Control SW.

U<L1-L2(L3) Op

U< L1-L2(L3) Str

B0

420 420I
BCU(I2) 3

B0 Ut< Op (5 Sec) 1- Undervoltage Relay, 27/59

402 I1 402 402 I2


U<L1-L2(L3) Op

& &
MMI SCADA

S Q

Auto

MMI SCADA

430 430I
BCU(I3) 4

BTO 402
MMI

BI (BCU) by pass sw. 401

&
Manual

Control SW. BB. Prot. 50BF 50/51,50/51N L2 50/51,50/51N L3 402 I1 402 I2 420Local 402 Local 430 Local #1 PT.MCB L2
DESCRIPTION OF

1 &

R Q

Manual

SCADA LED

BTO 401
BTO 401 Manual 5

Difference Voltage Level Shutdown Transformer#1 Maintenance Busbar#1

To Start Sequence # BTO 402-A Caution : 1. BTO shall be implemented on bay level (Bus Section BCU). 2. Undervoltage protection shall be located at both incoming lines and issue the tripping signal to incoming BCU. 3. Switching devices status (CB,DS, etc) and Undervoltage tripping signal shall be reported by GOOSE via substation LAN. 4. Closing and Tripping command shall be reported by GOOSE via substation LAN. 5. Communication system failure shall not cause of BTO mis-operation and/or malfunction.
A B C

REVISIONS

BY

DATE

PT.MCB L3 BTO-401 O/P : Q BTO-402 O/P : Q


BCU 402 DRN. ENGR.

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 47 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Bus Throwover

Automatic Function : Bus Throwover (BTO-402) Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Transfer)


S R Q Q
BTO-402

U< L1-L2(L3)
U< Str:BCU(I2)

Ut< 5.0 s

Op
BCU(I2)

1 & & Trip 420 S Q M-I2 R Q &


MMI
Memorized BTO I2 Started
3 2

402 430
BCU(I1)

BTO 402-A
Manual

BTO 401 : Q

420

&
1
Ut< 5.0 s
Op

Close 402

Alarm BTO 402 Started

MMI SCADA

U< L1-L2(L3)
U< Str:BCU(I2)

4 BCU(I3)

& &

402 420
BTO 402-A

Trip 430

&
401

S R

Q Q

BTO-O/P
Memorized BTO operated

MMI SCADA LED


BTO-401 sw.to Man BTO-402 sw.to Man

430

&

&
6

S Q M-I2 R Q
DESCRIPTION

MMI
Memorized BTO I3 Started

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 48 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Bus Throwover (BTO-402) Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (Switch to Manual)


S R Q Q
BTO-402

420 402 430

&

#1

420 402 430

1 &

T5 6s

Alarm

MMI

BTO 402 switch to Manual CB In-corrected Position

&
420
3

402 430

&

Trip- 420 420

& 1

&

Alarm

MMI

BTO 402 switch to Manual CB Failed to Trip


4

Trip- 430 430

&

T6 1.0 s

Close- 402 402

&

&

Alarm
BTO switch to Manual CB Failed to Close

MMI

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 49 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Bus Throwover

Automatic Function : Automatic Transformer Restoration Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (CK S/S: Tripping Logic)


M X013 M X033

X034

&
X012 X032

Trip X032

MMI

X014 M 6907 M 6908 M X923

X034

X933

X913

X933

&
86 87T

Trip 430

MMI

X913

&
X012

Open X913

MMI

50/51,50/51N

50/51,50/51N

50/51,50/51N

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

86

87T

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

86

87T

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

410

420

430

410 420
3

X923

&

Trip 420

MMI X908

&

Transformer # 1
X014

&

T1 1.0 s

&
5

Trip X012

420
MMI

X032
X908

&

&
5

X913

&

X907

& &

430 6907

87 T1
6

50/51,50/51N T1

Trip 410

DESCRIPTION

OF

REVISIONS

BY

DATE

MMI

X012

410

X907

420

X908

T1
X032 430 X908

METROPOLITAN
DRN. CHK. SUPPLIER TITLE ENGR.

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 50 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

86 T1
Initial condition to open X913
A B C D E F

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Tripping Contact

Automatic Function : Automatic Transformer Restoration Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (CK S/S : Restoration Logic)


Close Command Close : SA Close : Local Close Command Close : SA

1 1
S

X6032

AR Close
LTO : Close
2

&
Q M-L3 R Q

Close X032

MMI

Close : Local

1 1
S

430

BTO : Close
ATR : Close

&
Q M-430

Close 430

MMI

ATR : Close BB. Protn. 50BF 21/21N 67/67N Open : SA

&

BB. Protn. 50BF 50/51,51/51N

&

1
Open : SA Open : Local

1
3

Open : Local LTO : Open

X032
Close Command

BTO : Open

430

Close : SA Close : Local

1 1
S

X6012

AR Close
LTO : Close
4

&
Q M-L1 R Q

Close X012

MMI
Close : SA Close : Local

Close Command

1 1
S

420

ATR : Close BB. Protn. 50BF 21/21N 67/67N Open : SA


5

&

BTO : Close
ATR : Close

&
Q M-420

Close 420

MMI

BB. Protn. 50BF

&

50/51,51/51N

1
5

Open : Local LTO : Open

X012
X908

Open : SA Open : Local

Transformer # 1
X913
6

BTO : Open

420

&
X907

&
50BF

&
DRN. ENGR.

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 51 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

86 T1
A B C D E F

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Tripping Contact

Automatic Function : Automatic Transformer Restoration Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (CK S/S : Tripping Logic)


M X013 M X033

X034

&
X012 X032

Trip X032

MMI

X014 M 6907 M 6908 M X923

X034

X933

X913

X933

&
86 87T

Trip 430

MMI

X923

&

Open X923

MMI

50/51,50/51N

50/51,50/51N

50/51,50/51N

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

86

87T

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

86

87T

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

410

420

430

420 410
3

X923

&

Trip 410

MMI

X012 6907 X908

&

430
4

Transformer # 2
X014

X032 6907

&

&

Trip X012

&

MMI

T1 1.0 s

X908

410 X908 X923 X012

&

X907

& &

430 6032 X907 X908

&

87 T2
6

50/51,50/51N T2

Trip 420

DESCRIPTION

OF

REVISIONS

BY

DATE

MMI

420

6907

6012

410

X908

T1
6907 6032 430 X908

METROPOLITAN
DRN. CHK. SUPPLIER TITLE ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 52 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT


430 X908

RELAY SYSTEM AND TELE-METER DIV.

86 T2
A B C D

6907

6012

410

X032

XXXXXXXXXXXXXXXXXXXXXXXX

Initial condition to open X923


E F

Tripping Contact

Automatic Function : Automatic Transformer Restoration Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (CK S/S : Restoration Logic)


Close Command Close : SA Close : Local Close Command Close : SA

1 1
S

X6032

AR Close
LTO : Close
2

&
Q M-L3 R Q

Close X032

MMI

Close : Local

1 1
S

430

BTO : Close
ATR : Close

&
Q M-430

Close 430

MMI

ATR : Close BB. Protn. 50BF 21/21N 67/67N Open : SA

&

BB. Protn. 50BF 50/51,51/51N

&

1
Open : SA Open : Local

1
3

Open : Local LTO : Open

X032
Close Command

BTO : Open

430

Close : SA Close : Local

1 1
S

X6012

AR Close
LTO : Close
4

&
Q M-L1 R Q

Close X012

MMI
Close : SA Close : Local

Close Command

1 1
S

410

ATR : Close BB. Protn. 50BF 21/21N 67/67N Open : SA


5

&

BTO : Close
ATR : Close

&
Q M-410

Close 410

MMI

BB. Protn. 50BF

&

50/51,51/51N

1
5

Open : Local LTO : Open

X012
X908

Open : SA Open : Local

Transformer # 2
X923
6

BTO : Open

410

&
X907

&
50BF

&
DRN. ENGR.

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 53 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

86 T2
A B C D E F

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Tripping Contact

Automatic Function : Automatic Transformer Restoration Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (CK S/S : Tripping Logic)


M X013 M X033

X014

&
X012 X032

Trip X012

MMI

X014 M 6907 M 6908 M X923

X034

X913

X913

X933

&
86 87T

Trip 410

MMI

X933

&
X032 430 420

Open X933

MMI

50/51,50/51N

50/51,50/51N

50/51,50/51N

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

86

87T

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

86

87T

Buchholz Pressure Relief Transformer Protective Device Winding Temp.

410

420

430

X923

&

Trip 420

MMI
X907

&

Transformer # 3
X034

&

T1 1.0 s

&
5

Trip X032

420

MMI
X012 X907

&

&
5

X933

&

X908

& &

410 6908

87 T3
6

50/51,50/51N T3

Trip 430

DESCRIPTION

OF

REVISIONS

BY

DATE

MMI

X032

430

X908

420

X907

T1
X012 410 X907

METROPOLITAN
DRN. CHK. SUPPLIER TITLE ENGR.

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 54 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

86 T3 Initial condition to open X933


A B C D E F

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Tripping Contact

Automatic Function : Automatic Transformer Restoration Scheme


1

PM5-0403-WBX
1

Function Logic Diagram (CK S/S : Restoration Logic)


Close Command Close : SA Close : Local Close Command Close : SA

1 1
S

X012

AR Close
LTO : Close
2

&
Q M-L1 R Q

Close X012

MMI

Close : Local

1 1
S

410

BTO : Close
ATR : Close

&
Q M-410

Close 410

MMI

ATR : Close BB. Protn. 50BF 21/21N 67/67N Open : SA

&

BB. Protn. 50BF 50/51,51/51N

&

1
Open : SA Open : Local

1
3

Open : Local LTO : Open

X012
Close Command

BTO : Open

410

Close : SA Close : Local

1 1
S

X032

AR Close
LTO : Close
4

&
Q M-L3 R Q

Close X032

MMI
Close : SA Close : Local

Close Command

1 1
S

420

ATR : Close BB. Protn. 50BF 21/21N 67/67N Open : SA


5

&

BTO : Close
ATR : Close

&
Q M-420

Close 420

MMI

BB. Protn. 50BF

&

50/51,51/51N

1
5

Open : Local LTO : Open

X032
X907

Open : SA Open : Local

Transformer # 3
X933
6

BTO : Open

420

&
X908

&
50BF

&
DRN. ENGR.

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 55 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

86 T3
A B C D E F

CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

Tripping Contact

Automatic Function : Capacitor Control Scheme


1

PM5-0403-WBX
1

MMI SCADA
Control SW.
2

Auto-Manual Logic Diagram


1

S Q

Auto

MMI SCADA

Cap Control Relay Step 1

Busbar VT Lost (Cap UV) Capacitor Feeder CB Close

&

Close Cap DS-1

CAP
MMI SCADA
Control SW.
Cap Control Relay Step 2

R Q

Manual

MMI SCADA
MMI Control Step 1 ON Busbar VT Lost (Cap UV) Capacitor Feeder CB Close

Open Cap DS-1


3

&

Cap Control Relay Step 2


MMI Control Step 1 OFF
4

& 1
Busbar VT Lost (Cap UV)

1
Capacitor Feeder CB Open

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 56 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Coupler Throwover

Automatic Function : Capacitor Control Scheme


1

PM5-0403-WBX
1

MMI SCADA
Control SW.
2

Auto-Manual Logic Diagram


1

S Q

Auto

MMI SCADA

Cap Control Relay Step 2

Busbar VT Lost (Cap UV) Capacitor Feeder CB Close

&

Close Cap DS-2

CAP
MMI SCADA
Control SW.
Cap Control Relay Step 1

R Q

Manual

MMI SCADA
MMI Control Step 2 ON Busbar VT Lost (Cap UV) Capacitor Feeder CB Close

Open Cap DS-2


3

&

Cap Control Relay Step 1


MMI Control Step 2 OFF
4

& 1
Busbar VT Lost (Cap UV)

1
Capacitor Feeder CB Open

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 57 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Coupler Throwover

24kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 58 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

24kV 24 kV Interlocking Logic

24kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 59 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

24kV 24 kV Interlocking Logic

24kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 60 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

24kV 24 kV Interlocking Logic

24kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 61 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

24kV 24 kV Interlocking Logic

24kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 62 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

24kV 24 kV Interlocking Logic

24kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 63 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

24kV 24 kV Interlocking Logic

69/115kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 64 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

69kV 69 kV Interlocking Logic

69/115kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 65 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

69kV 69 kV Interlocking Logic

69/115kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 66 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

69kV 69 kV Interlocking Logic

69/115kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 67 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

69kV 69 kV Interlocking Logic

69/115kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 68 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

69kV 69 kV Interlocking Logic

69/115kV Interlocking Logic (Typical Existing)


1

PM5-0403-WBX
1

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 69 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

69kV 69 kV Interlocking Logic

Closing Tripping Diagram (Line)


1

PM5-0403-WBX
1

67/67N & BCU


Close (SA) Open (SA) Trip (Protn.2) 50BF Reset Trip (Protn.1) 50BF Trip

21/21N
Trip (Protn.2) Close (A/R) Trip (Protn.1) 50BF Trip

50BF Reset +VDC-Backup Protection


Interlocking

Reset

S 50BFX R

Block Close HV CB

-VDC-Backup Ptn.

+VDC1 +VDC2
Local Control Local Control

115/69kV Switchgear Circuit Breaker


4
Local/Remote Sw. Local/Remote Sw.

CC

TC1

TC2

-VDC1 -VDC2
6

All Disconnecting Switches shall be also controlled by SA via BCU Output Contacts
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 70 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Output Contact

Closing Tripping Diagram (Transformer)


1

PM5-0403-WBX
1

50/51,50/51N & BCU


50,50/51N Open (SA) Trip (Protn.2) 50BF Reset (Trip) Close (SA) Trip (Protn.1) 50BF Trip Int. 50BF
BI

87
Trip Trip (Protn.2) Trip (Protn.1)

Transf. Protective Devises WT. OLTC. Prot. Buchholz Pres. V.


BI BI BI BI

50BF Reset
To 86 (Lock out)

Reset

+VDC-BCU +VDC-Backup Protection


Interlocking
S 50BFX R

Block Close HV CB

-VDC-Backup Ptn.

+VDC1 +VDC2
Local Control Local Control

115/69kV Switchgear Circuit Breaker


4
Local/Remote Sw. Local/Remote Sw.

CC

TC1

TC2

-VDC1 -VDC2
6

All Disconnecting Switches shall be also controlled by SA via BCU Output Contacts
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 71 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Output Contact

Closing Tripping Diagram (Bus Coupler)


1

PM5-0403-WBX
Bus A
1

50/51,50/51N & BCU


Close (SA) Open (SA) Trip (Protn.2) 50BF Reset Trip (Protn.1) 50BF Trip
Bus B

Reset

+VDC-Backup
Interlocking

S 50BFX R

BO : Control & Protection BCU BI :Alarm & Status

Block Close HV CB

-VDC-Backup

+VDC1 +VDC2
Local Control Local Control

115/69kV Switchgear Circuit Breaker


4
Local/Remote Sw. Local/Remote Sw.

CC

TC1

TC2

-VDC1 -VDC2
6

All Disconnecting Switches shall be also controlled by SA via BCU Output Contacts
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 72 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Output Contact

Closing Tripping Diagram (12-24kV Incoming)


1

PM5-0403-WBX
1

50/51,50/51N,50BF,27/59 & BCU


ON OFF Close (SA) Trip (Protn.1)) Open (SA) Trip (Protn.2)

50/51,50/51N+BCU Trip (Protn.2) Trip (Protn.2) Trip (Protn.1) 86 Reset Trip (Protn.1) Any Trip

87
WT. OLTC. Prot. Buchholz Pres. V.
BI BI BI BI

+VDC-Main

50/51N (Trip)

Reset

Interlocking

Capacitor Control Auto/Manual Existing CCT +VDC1 +VDC2


Local Control

S 86 R

115/69kV Relay Board

Block Close HV,MV CB

-VDC-Main

12-24kV Switchgear Circuit Breaker


Local Control

4
Local/Remote Sw. Local/Remote Sw.

CC

TC1

TC2

-VDC1 -VDC2
6

All Disconnecting Switches shall be also controlled by SA via BCU Output Contacts
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 73 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Output Contact

Closing Tripping Diagram (12-24kV Outgoing Feeder)


1

PM5-0403-WBX
1

50/51,50/51N,50BF,79,27/59/81 & BCU


Trip (Protn.1)) Close (AR) Close (SA) Open (SA) Trip (Protn.2)

Interlocking

+VDC1 +VDC2
Local Control Local Control

12-24kV Switchgear Circuit Breaker


4
Local/Remote Sw. Local/Remote Sw.

CC

TC1

TC2

-VDC1 -VDC2
6

All Disconnecting Switches shall be also controlled by SA via BCU Output Contacts
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 74 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Output Contact

Closing Tripping Diagram (12-24kV Bus Section)


1

PM5-0403-WBX
1

50/51,50/51N & BCU


Close (SA) Open (SA) Trip (Protn.2) Trip (Protn.1)

Interlocking

+VDC1 +VDC2
Local Control Local Control

12-24kV Switchgear Circuit Breaker


4
Local/Remote Sw. Local/Remote Sw.

CC

TC1

TC2

-VDC1 -VDC2
6

All Disconnecting Switches shall be also controlled by SA via BCU Output Conracts
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 75 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Output Contact

Closing Tripping Diagram (12-24kV Capacitor)


1

PM5-0403-WBX
1

50/51,50/51N,50BF,27/59 & BCU


Close (SA) Trip (Protn.1)) Open (SA) Trip (Protn.2) Close Open Close Open

Interlocking

C1A

C1B
3

Existing Capacitor Bank


+VDC1 +VDC2
Local Control Local Control

12-24kV Switchgear Circuit Breaker


4
Local/Remote Sw. Local/Remote Sw.

CC

TC1

TC2

-VDC1 -VDC2
6

All Disconnecting Switches shall be also controlled by SA via BCU Output Contacts
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 76 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Output Contact

Auxiliary DC Power Supply (Example)


1

PM5-0403-WBX
1

VDC-BCU BCU Binary Input

VDC-Backup Protection

VDC-Main Protection 21/21N Binary Input

Switching devices, Control Sw. etc

Switching devices, Control Sw. etc

21/21N Binary Input

BCU Binary Input

BCU Binary Input

27

27

27

21/21N Binary Input

BCU Binary Input

BCU Binary Input

+ +
4

+ -

Close (SA)

67/67N & BCU


Open (SA) Trip (Protn.2) 50BF Reset Trip (Protn.1) 50BF Trip

21/21N
4

Trip (Protn.2) Close (A/R) Trip (Protn.1) 50BF Trip


BI BI BI BI

Reset

S 50BFX R

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 77 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Auxiliary DC PS

Auxiliary DC Power Supply (Example)


1

PM5-0403-WBX
1

VDC-BCU BCU Binary Input

VDC-Backup Protection

VDC-Main Protection 87 Binary Input

Switching devices, Control Sw. etc

Switching devices, Control Sw. etc

87 or Nearby BCU Binary Input

BCU Binary Input

BCU Binary Input

27

27

27

87or Nearby BCU Binary Input

BCU Binary Input

BCU Binary Input

+ +
4

+ -

Close (SA)

50/51,50/51N & BCU


Open (SA) Trip (Protn.2) 50BF Reset Trip (Protn.1) 50BF Trip

87
4

Trip (Protn.2) Trip Any Trip (start 50BF) Trip (Protn.1)


BI BI BI BI

Reset

+VDC-Main Protection

Reset
S 50BFX R S 86 R

-VDC-Main Protection
6
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 78 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Auxiliary DC PS

Auxiliary DC Power Supply (Example)


1

PM5-0403-WBX
1

VDC-BCU BCU Binary Input

VDC-Backup Protection

Switching devices, Control Sw., etc

Near by BCU Binary Input

BCU Binary Input

27

27

Near by BCU BinaryInput

BCU Binary Input

+ 50/51,50/51N & BCU BC or BS 50/51N Open (SA) Trip (Protn.2) 50BF Reset (Trip) Close (SA) Trip (Protn.1) 50BF Trip

Reset

S 50BFX R

DESCRIPTION

OF

REVISIONS

BY

DATE

METROPOLITAN
DRN. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 79 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT.

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Protection and related functions only


A B C D E F

Auxiliary DC PS

Example Trip Circuit Supervision (Line Protection)


+VDC1 Close (SA) Open (SA)
1

Distance

Dir. Overcurrent

PM5-0403-WBA
1

Close (AR)

+VDC2
TB-21

Distance

Dir. Overcurrent

TB-67

TB-21

TB-67

67
2

21

67

21

21

67

67

21

21

67

67
2

TB-21

TB-67

TB-21

TB-67

21

67

21

67

Option Interlocking

Option

+VDC1 +VDC2
Local Control Local Control

Local/Remote Sw.

Local/Remote Sw.

CC
6

TC1

115-69kV Switchgear Circuit Breaker

TC2

21 : Distance Relay 67 : Directional Overcurrent Relay + BCU TB-XX : Test Block SA : Substation Automation Systems AR : Auto Reclosing Relay CC : Closing Coil TC1, TC2 : Tripping Coil
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. CHK. SUPPLIER TITLE

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 80 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

-VDC1 -VDC2
A B C D E F

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

Output Contact

PM5-0403-WBX
1

C
Existing Protection Cubicle

SA Cubicle
BCU or Relay
2 2

BCU or Relay

Provided by Contractor

+
4

+ + + +
5

Provided by Contractor

+
DESCRIPTION OF REVISIONS BY DATE

METROPOLITAN
DRN. ENGR. CHF. OF SECT. DIR. OF DIV. DIR. OF DEPT. TITLE CHK. SUPPLIER

ELECTRICITY

AUTHORITY
TELE-METER-1 SECTION NONE 13/01/2012 81 OF 81 RL-MEA-003 SCALE DATE SH.NO. DWG. NO.

POWER SYSTEM MAINTENANCE DEPARTMENT

RELAY SYSTEM AND TELE-METER DIV.

XXXXXXXXXXXXXXXXXXXXXXXX

External Connection