IEEE Std C57.12.

01-2005 IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers, Including Those with Solid-Cast and/or Resin Encapsulated Windings

Table 3 Preferred continuous power ratings


Single-phase transformers (kVA) 1.0 3.0 5.0 7.5 10.0 15.0 25.0 37.5 50.0 75.0 100.0 167.0 250.0 333.0 500.0 833.0 1 250.0 1 667.0 2 500.0 3 333.0 5 000.0 6 667.0 8 333.0 10 000.0 Three-phase transformers (kVA) 15.0 30.0 45.0 75.0 112.5 150.0 225.0 300.0 500.0 750.0 1 000.0 1 500.0 2 000.0 2 500.0 3 750.0 5 000.0 7 500.0 10 000.0 12 000.0 15 000.0 20 000.0 25 000.0 30 000.0

5.5 Voltage rating and taps


5.5.1 General Standard nominal system voltages are listed in ANSI C84.1. Voltages available on standard transformers are included in the product standards for particular types of transformers. 5.5.2 Voltage rating The voltage rating at no load shall be based on the turn ratio. The ratio of voltage is subject to the effect of regulation at various loads and power factors. 5.5.3 Rating of transformer taps Whenever a transformer is provided with taps from a winding, the taps shall be full-capacity taps. When specified, taps other than full-capacity taps may be provided, and this shall be stated on the nameplate.

5.6 Connections
Standard connection arrangements are described in the product standards for particular types of transformers.