Académique Documents
Professionnel Documents
Culture Documents
Subject :
<CONTENTS>
Job No. SC2252 Job Name OPaL DFCU & AU Project Client OPaL No. SC2252-WI-008 14,Jul,09 Rev. NO. 0 Issue Date PIPING ARRANGEMENTS FOR FLOWMETER INSTALLATIONS
1. PIPING ARRANGEMENTS FOR ORIFICE PLATES INSTALLATIONS 2. PIPING ARRANGEMENTS FOR VENTURI INSTALLATIONS
Made Date
2009-07-14
Sign
Name
Check Date
Sign
Name
C.S.Park
Approval Date
Sign
Name
C.S.Park B.R.Kim S.C.Pee S.Yoo B.Heo Rohit
Remark
DATE
DESCRIPTION
BY
CHK
APP
Page 1 of 3
SC2252-WI-008
REV.0
Work Instruction
Subject :
Job No. SC2252 Job Name OPaL DFCU & AU Project Client OPaL No. SC2252-WI-008 14,Jul,09 Rev. NO. 0 Issue Date PIPING ARRANGEMENTS FOR FLOWMETER INSTALLATIONS
ORIFICE/PIPEDIA. (d/D)RATIO
LENGTHOFSTRAIGHTRUN A F
12D
G
18D
UPSTREAM H K
18D 22D
M
35D
R
44D
DOWNSTREAM Z
5D
0.75
NOTES:
8D
1. TABULATED DIMENSIONS ARE GENERALLY BASED ON INFORMATION IN THE ISO 5167-2 AND ALSO ASME FLUID METERS - 6th EDITION AT A MAXIMUM ORIFICE DIAMETER RATIO (d/D) OF 0.75. 2. THE DIMENSIONS SHOWN ARE TO THE UPSTREAM FACE OF THE ORIFICE PLATE AND THE MINIMUM REQUIRED, WHEN POSSIBLE DIMENSIONS SHOULD BE INCREASED. 3. WHEN SEVERAL FITTINGS (OTHER THAN 90 BENDS) ARE UPSTREAM OF THE ORIFICE PLATE, THE FIRST FITTING CLOSEST TO THE ORIFICE PLATE SHALL BE PER THE TABLE. THE MINIMUM STRAIGHT LENGTH FROM THE SECOND FITTING (TO THE FIRST FITTING) SHALL BE 1/2 OF THE DIMENSION LISTED IN THE TABLE FOR THE SECOND FITTING. 4. WHEN BENDS ARE USED INSTEAD OF FITTINGS TO CHANGE DIRECTION, DIMENSION LINES SHALL BE TO TANGENT LINE OF BEND.
* THIS INSTRUCTION SHALL BE USED FOR ROUTING STUDY ONLY. * THE INSTRUCTION INCLUDING THE DETAILED DATA IS TO BE ISSUED AFTER RECEIVING INTRUMENTATION DATA.
DATE
DESCRIPTION
BY
CHK
APP
Page 2 of 3
SC2252-WI-008
REV.0
H G F A Z
VALVE
CONCENTRIC REDUCER
CONCENTRIC EXPANDER
TEE,CROSS,OR LATERAL
LENGTHOFSTRAIGHTRUN
VENTURI/PIPEDIA. (d/D)RATIO
UPSTREAM A F
3.5D
DOWNSTREAM G H
8D
Z
4d
0.75
8D
4.5D
NOTES:
1. TABULATED DIMENSIONS ARE BASED ON INFORMATION IN THE ISO 5167-4 AND ALSO ASME FLUID METERS - 6th EDITION, AT A MAXIMUM THROAT DIAMETER RATIO (d/D) OF 0.75. 2. DIMENSIONS SHOWN ARE MINIMUM REQUIRED. WHEN POSSIBLE THEY SHOULD BE INCREASED. 3. WHEN BENDS ARE USED INSTEAD OF FITTINGS TO CHANGE DIRECTION, DIMENSION LINES SHALL BE TO TANGENT LINE OF BEND. 4. D: INNER DIAMETER OF PIPE / d : THROAT DIAMETER OF VENTURI
DATE
DESCRIPTION
BY
CHK
APP
Page 3 of 3
SC2252-WI-008
REV.0