REINFORCED PLASTIC SYSTEMS INC.

Figure P13: Riser Guide

PIPE SUPPORTS

'A'
D ELASTOMERIC CUSHION

1/8" GAP STANDARD D GUIDE ANGLE MAY BE WELDED OR BOLTED

'B' 6" T.O.S. 3 SIDES SECTION D-D PIPE O.D.

Finish: Hot-dipped galvanized*. Service: Two-directional lateral guide for riser piping. Material: Carbon steel**.
P ip e S ize [in ] 2 3 4 6 8 10 12 14 16 18 20 24 A [in ] 1 1 1 /4 1 2 1 /4 1 3 1 /4 1 5 3 /4 1 7 3 /4 2 0 3 /4 2 4 3 /4 27 2 9 1 /2 3 1 1 /2 34 38

Notes: Specify required width at placement of order. See general notes. *Other finishes are available upon request. **Other materials are available upon request. Lateral X is perpendicular to clamp ears Lateral Z is parallel to clamp ears
B [in ] 3 3 3 4 4 6 6 8 8 10 10 12 A llow ab le L o ad s [lb ] L ateral X 100 170 200 400 400 600 1300 1600 1700 2000 2000 2700 L a tera l Z 280 390 500 1000 1200 1600 2400 3200 3300 4000 4000 5500

10 Sep 09 Precision Pipe Supports - P13 Page 34

REINFORCED PLASTIC SYSTEMS INC.

PIPE SUPPORTS

Figure P14: Riser Support

'A'
FRP SHEAR COLLAR MUST BE ORDERED SEPARATELY)

'B' T.O.S.

MAY BE WELDED OR FREE TO MOVE

ELASTOMETRIC CUSHION

PIPE O.D.

Finish: Hot-dipped galvanized*. Service: To carry dead weight of a riser from nearby structure. Material: Carbon steel**.
P ip e S ize [in ] 2 3 4 6 8 10 12 14 16 18 20 24 A [in ] 1 1 1 /4 1 2 1 /4 1 3 1 /4 1 5 3 /4 1 7 3 /4 2 0 3 /4 2 4 3 /4 27 2 9 1 /2 3 1 1 /2 34 38 B

Notes: Specify required width at placement of order. See general notes. *Other finishes are available upon request. **Other materials are available upon request.

A llow ab le L o ad s [lb ] V ertica l 1100 1400 1800 2000 2400 4500 5500 7000 8000 8500 12000 16000

[in ] 3 3 3 4 4 6 6 8 8 10 10 12