Enter DC Voltage Inverter of UPS Efficiency

UPS Capacity in VA

UPS Load Backup In Power Factor Hour

Enter De rating Factor of Batteries

6000

0.8

384

0.9

0.65

Backup Time <0.5 Hour 1 Hour 2 Hours 3 Hours >4 Hours DC voltage Accenta 1KVA Accenta 2KVA Accenta 3KVA Accenta 6KVA Accenta 10KVA Renata I 5 KVA Renata I 10 KVA Renata I 15 KVA Renata I 20 KVA Proacta 10 KVA Proacta 15 KVA Proacta 20 KVA Proacta 20 KVA Renata-300- 3Phase ( 10 KVA -300 KVA Renata-Cyclone- 3Phase ( 10 KVA -200 KVA Renata-Cyclone T- 3Phase ( 10 KVA -200 KVA

De rating factor of Batteries 0.45 0.55 0.65 0.75 0.85 AH=

UPS CAPACITY IN VA X LO DC VOLTGE of UPS X INVE

AH Availabl 36 96 96 240 240 192 384 384 384 384 384 384 384 360 720 Exide/Amaraon/GY Exide Exide Amaraon/GY Exide/Amaraon/GY Exide/Amaraon/GY Exide/Amaraon/GY Exide/Amaraon/GY Amaraon Exide/Amaraon/GY Exide Exide/Amaraon Exide/GY Amaraon Exide/GY

624

LOAD power Factor Accenta Renata i/Proacta Renata 300 / Cyclone

0.7 0.8 0.8

AH Required

No of 12V Batteries Required

85

32

UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR DC VOLTGE of UPS X INVERTOR EFFICIENCY X BATTERY DERATING FACOR

AH Available SMF TUBULAR 7 40 Exide /southern /GY 15 50 Exide 17 60 Exide /southern /GY 18 66 Exide 26 75 Exide /southern /GY 42 80 Southern 65 100 Exide /southern /GY 75 120 Southern /GY 84 130 Exide /southern /GY 100 150 Exide /southern /GY 120 200 Exide /southern /GY 130 150 160 200

BATTERY AH CALCULATION

Derating Backup factor of Time Batteries AH= <0.5 Hour 0.45 1 Hour 0.55 2 Hours 0.65 3 Hours 0.75 >4 Hours 0.85

UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR DC VOLTGE of UPS X INVERTOR EFFICIENCY X BATTERY DERATING FACOR DC VOLTTAGE INVERTOR EFFICIENCY LOAD POWER FACTOR = NO OF BATTERIES X 12 V = 95% = 0.7 Required AH Nearest AH Available We Offer 12 V/26 AH- 3 No's

for 750VA 60 Minits backup

750 X 0.7 x 1 36 x 0.95 x 0.55 1000 X 0.7 x 1 36 x 0.95 x 0.55 10000 X 0.7 x 1 240 x 0.95 x 0.55 20000 X 0.7 x 1 240 x 0.95 x 0.55

Required - 28 AH - 3 No's

for 1KVA 60 Minits backup

Required - 37 AH- 3 No's

We Offer 12V/42AH - 3No's

for 10 KVA 30 Minits backup

Required - 56 AH / 20 No's

We Offer 12V/65AH - 20 No's

for 20 KVA 30 Minits backup

Required - 112 AH / 20 No's

We Offer 12V/65AH/ 2 x 20 No's

BATTERY AH CALCULATION

Derating Backup factor of Time Batteries AH= <0.5 Hour 0.45 1 Hour 0.55 2 Hours 0.65 3 Hours 0.75 >4 Hours 0.85

UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR DC Voltage X INVERTOR EFFICIENCY X BATTERY DERATING FACOR Load Power factor of E&C Accenta UPS = 0.7 DC Voltage :- 96 VDC ( No of Batteries x 12V ) BacK up Required :- 2 Hours Invertor Efficiency : 93% Required AH 48 AH Nearest AH Available 2 x 26 AH ( 52 AH )

for 2 KVA -2 hours backup

2000X 0.7 x 2 96 x x 0.93 x 0.65

We are offering 12V/ 26 AH - 2 x 8 No's SMF Batteries

Annamalai K.S Electronics & Controls Power Systems Pvt Ltd, 29-A,2nd Phase,Industrial Area, Peenya, Bangalore-560058. Ph -080-; 3242 9511 ;2837 9401; Fax -2839 1587 Mobile 093412 63968

BATTERY AH CHART
DESCRIPTION PARAMETER UNIT BACK-UP HR REQUIRED AH

UPS CAPACITY POWER FACTOR INV EFFICIENCY

200 VA 0.8 PF 90 %

Enter the UPS capacity Required Change the pf Required Change the Efficiency

10 minuts 15 minuts 30 minuts

2 AH 3 AH 5 AH

NO OF BATTERY BATTERY END VOLTAGE BATTERY LOW CUTT-OFF DISCHARGE POWER DISCHARGE CURRENT

3 Nos 10.5 VDC 31.5 VDC 178 VA 6 A

Enter the No-of Battery You offered 60 minuts 90 mints 2 Hour 3 Hour 4 Hour 5 Hour 6 Hour 8 Hour 10 Hour

9 AH 13 AH 16 AH 21 AH 27 AH 33 AH 39 AH 51 AH 63 AH

AH=

UPS CAPACITY IN VA X LOAD POWER FACTOR X BACKUP IN HOUR DC VOLTGE of UPS X INVERTOR EFFICIENCY X BATTERY DERATING FACOR

Backup Time <0.5 Hour 1 Hour 2 Hours 3 Hours >4 Hours

De rating factor of Batteries 0.45 0.55 0.65 0.75 0.85

Required Total VAH

88 VAH 113 VAH 185 VAH

317 VAH 484 VAH 564 VAH 752 VAH 967 VAH 1195 VAH 1401 VAH 1847 VAH 2257 VAH

960

106

Vous aimerez peut-être aussi