41 26
25
24
BUS A BUS B
40-SWG82320 40-SWG82321
24
23
23
250A
250A
250A
22
NO
NO
NC
NO
NO NC
NC
21
21
20
20
NOTE 5 19
NOTE 5 19
SPARE
SPARE
SPARE
SPARE
18
18
41-SWG82320
41-SWG82321
17
NOTE 2
NOTE 2 40-XF82371 6.6kV/420V 1.6MVA ONAN Dyn11 100A 315A 315A 100A 315A 315A
17
FUTURE
16
16
40-EJB82310
NOTE 4 15 NOTE 4 HGCP HV INTERFACE JUNCTION BOX
40-EJB82311
HGCP HV INTERFACE JUNCTION BOX 15
40-BD82271
M
3~
RTD
14
13
13
12
NC
NC
NC
NC 41-XF82310 6.6kV/420V 750kVA ONAN Dyn11 Z=5% 41-XF82311 41-XF82320 41-XF82321 41-XF82322 6.6kV/420V 6.6kV/420V 2MVA ONAN 2MVA ONAN Dyn11 Dyn11 Z=6.25% Z=6.25% 41-XF82323 6.6kV/420V 2MVA ONAN Dyn11 Z=6.25%
12
11
6.6kV/420V 6.6kV/420V 750kVA ONAN 2MVA ONAN Dyn11 Dyn11 Z=5% Z=6.25%
11
NOTE 4
NOTE 4
NOTE 4 41-BD82220
NOTE 4 41-BD82221
NOTE 4 41-BD82222
NOTE 4 41-BD82223 10
NC 40-MCC82272 NO
LV SWITCHROOM 40-LER65710
NOTE 1 ATS NC NC NC NC
NOTE 1 ATS NC 9
NC
41-SWG82210 8
NO
41-SWG82211
41-SWG82220
NO
41-SWG82221
41-SWG82222
NO
41-SWG82223 8
NC 40-MCC82274 NO
NC 40-MCC82275
NON-ESSENTIAL SERVICES
45SWG82360 45SWG82370 7
5 45-XF82320 6.6kV/420V 100kVA ONAN Dyn11 Z=4% 45-XF82330 6.6kV/420V 100kVA ONAN Dyn11 Z=4% 45-XF82340 6.6kV/420V 100kVA ONAN Dyn11 Z=4% 45-XF82350 6.6kV/420V 100kVA ONAN Dyn11 Z=4% 45-XF82360 6.6kV/420V 100kVA ONAN Dyn11 Z=4% 45-XF82370 6.6kV/420V 100kVA ONAN Dyn11 Z=4%
NOTES:
3 1. 2. AUTO TRANSFER SYSTEM SHALL BE INHIBITED UNDER FAULT CONDITIONS. CABLES SHALL BE RUN TO TRANSFORMER LOCATION, COILED, LABELLED AND SECURED FOR FUTURE CONNECTION.
NOTE 4
NOTE 4
NOTE 4
NOTE 4
NOTE 4
NOTE 4 3
c : \ p d f ma k e r \ P DF MAKE R I N\ 5 6 7 7 7 2 6 3 _8 . DW G 2 0 1 1 0 9 1 2 0 3 : 46
3.
SURGE PROTECTION TO BE INSTALLED WHERE REQUIRED FOR LIGHTNING OVERVOLTAGES/SWITCHING TRANSIENTS. 45-DP82820
NC 45-DP82830
NC 45-DP82840
NC 45-DP82850
NC 45-DP82860
NC 45-DP82870
NC
4. 5. 1 6.
LV SYSTEM EARTHED VIA MEN LINKS LOCATED IN LV SWITCHBOARDS. SPARE WELLPAD FEEDER USED DURING BUSBAR MAINTENANCE. IN ESSENTIAL MODE HV FEEDER U/V PROTECTION IS DISABLED & FEEDERS/LOADS ARE RE-ENERGIZED SEQUENTIALLY. 400V, 160A, 3+N+E, 10kA FOR 1 Sec 400V, 160A, 3+N+E, 10kA FOR 1 Sec 400V, 160A, 3+N+E, 10kA FOR 1 Sec 400V, 160A, 3+N+E, 10kA FOR 1 Sec 400V, 160A, 3+N+E, 10kA FOR 1 Sec 400V, 160A, 3+N+E, 10kA FOR 1 Sec 1
SINGLE LINE DIAGRAM HIDES GAS CONDITIONING PLANT Esso Highlands Limited CBI Clough JV
DRAWING NO:
MC
10MAR10
NONE
APPD
PGHU-CV-EDSLD-400002
36 37 38 39 40
0
A1
10
11
12
13
14
15
16
17
18