Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

1 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Electrical Transient Analyzer Program Load Flow Analysis


Loading Category (1): Generation Category (1): Load Diversity Factor: Design Design None

Swing Number of Buses: 1

V-Control 0

Load 2

Total 3

XFMR2 Number of Branches: 1

XFMR3 0

Reactor 0

Line/Cable 1

Impedance 0

Tie PD 0

Total 2

Method of Solution: Maximum No. of Iteration: Precision of Solution:

Newton-Raphson Method 99 0.000100

System Frequency: Unit System: Project Filename: Output Filename:

50 Hz English UNIT2 C:\ETAP 503\UNIT2\project.lfr

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

2 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Adjustments
Apply Adjustments
Yes Yes No No No

Tolerance Transformer Impedance: Reactor Impedance: Overload Heater Resistance: Transmission Line Length: Cable Length:

Individual /Global
Individual Individual

Percent

Temperature Correction Transmission Line Resistance: Cable Resistance:

Apply Adjustments
Yes Yes

Individual /Global
Individual Individual

Degree C

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

3 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Bus Input Data


Load Bus
ID Bus1 Bus2 Bus5 Total Number of Buses: 3 kV 20.000 0.380 0.380 Sub-sys 1 1 1

Initial Voltage
% Mag. 100.0 100.0 100.0 Ang. 0.0 0.0 0.0

Constant kVA MW Mvar

Constant Z MW Mvar

Constant I MW Mvar MW

Generic Mvar

0.028 0.028

0.014 0.014

0.000 0.000

-0.010 -0.010 0.000 0.000 0.000 0.000

Generation Bus
ID Bus1 kV 20.000 Swing Type Sub-sys 1

Voltage
% Mag. 100.0 Angle 0.0 0.000 MW

Generation
Mvar % PF

Mvar Limits
Max Min

0.000

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

4 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Line/Cable Input Data


Ohms or Siemens/1000 ft per Conductor (Cable) or per Phase (Line) Line/Cable
ID Cable1 Library 0.6NCUN3 Size 8 Length Adj. (ft) 100.0 % Tol. 0.0 #/Phase 1 T (C) 75 R 0.811000 X 0.057700 Y

Line / Cable resistances are listed at the specified temperatures.

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

5 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

2-Winding Transformer Input Data

Transformer
ID T1 MVA 0.050 Prim. kV 20.000

Rating
Sec. kV 0.380 %Z 6.75 X/R 5.79 + 5% 0

Z Variation
- 5% 0 % Tol. 0

% Tap Setting
Prim. 0 Sec. 0

Adjusted
%Z 6.7500

Phase Shift
Type Std Pos. Seq. Angle 0.0

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

6 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Branch Connections
CKT/Branch
ID T1 Cable1 Type 2W XFMR Cable Bus1 Bus2 From Bus Bus2 Bus5

Connected Bus ID
To Bus

% Impedance, Pos. Seq., 100 MVA Base


R 2297.59 5616.34 X 13303.05 399.58 Z 13500.00 5630.54 Y

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

7 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

LOAD FLOW REPORT

Bus
ID * Bus1 Bus2 kV 20.000 0.380

Voltage
% Mag. 100.000 98.570 Ang. 0.0 -2.2

Generation
MW 0.029 0 Mvar 0.006 0 MW

Load
Mvar 0 0 0 0 Bus2 Bus5 Bus1 ID

Load Flow
MW 0.029 0.029 -0.029 -0.028 Mvar 0.006 0.005 -0.005 -0.005 Amp 0.9 45.2 45.2 45.2 % PF 97.8 98.5 98.5 98.5

XFMR
% Tap

Bus5

0.380

96.903

-2.1

0.028

0.005

Bus2

* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it) # Indicates a bus with a load mismatch of more than 0.1 MVA

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

8 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Bus Loading Summary Report

Directly Connected Load Bus


ID Bus1 Bus2 Bus5 kV 20.000 0.380 0.380 Rated Amp Constant kVA MW 0 0 0.028 Mvar 0 0 0.014 0 Constant Z MW 0 0 Mvar 0 0 -0.009 Constant I MW 0 0 0 Mvar 0 0 0 MW 0 0 0 Generic Mvar 0 0 0 MVA 0.030 0.029 0.032

Total Bus Load


Percent Loading 0.9 45.2 50.0

% PF 97.8 98.5 89.2

Amp

* Indicates operating load of a bus exceeds the bus critical limit ( 100.0 % of the Continuous Ampere rating). # Indicates operating load of a bus exceeds the bus marginal limit ( 95.0 % of the Continuous Ampere rating).

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

9 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Branch Loading Summary Report

CKT / Branch
ID T1 Type Transformer

Cable & Reactor


Ampacity (Amp) Loading Amp % Capability (MVA) 0.050 MVA 0.030

Transformer
Loading (input) % 59.6 Loading (output) MVA 0.029 % 58.7

* Indicates a branch with operating load exceeding the branch capability.

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

10 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Branch Losses Summary Report


Vd % Drop in Vmag 1.43 1.67

CKT / Branch
ID T1 Cable1

From-To Bus Flow


MW 0.029 0.029 Mvar 0.006 0.005

To-From Bus Flow


MW -0.029 -0.028 Mvar -0.005 -0.005 kW

Losses
kvar 1.2 0.0 1.2

% Bus Voltage
From 100.0 98.6 To 98.6 96.9

0.2 0.5 0.7

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

11 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

Alert Summary Report % Alert Settings Critical Loading


Bus Cable Reactor Line Transformer Panel Protective Device Generator 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 95.0 95.0 95.0 95.0 95.0 95.0 95.0 95.0

Marginal

Bus Voltage
OverVoltage UnderVoltage 105.0 95.0 102.0 98.0

Generator Excitation
OverExcited (Q Max.) UnderExcited (Q Min.) 100.0 100.0 95.0

Marginal Report
ID Bus5 Device Type Bus Rating 0.380 Unit kV Calculated 0.368 %Mag. 96.9 Condition UnderVoltage

Project: Location: Contract: Engineer: Filename: UNIT2

ETAP
5.0.3Z

Page: Date: SN:

12 01-01-2002 85OTI30125 Base Normal

Study Case: LF

Revision: Config.:

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW Source (Swing Buses): Source (Non-Swing Buses): Total Demand: Total Motor Load: Total Static Load: Apparent Losses: System Mismatch: 0.029 0.000 0.029 0.028 0.000 0.001 0.000

Mvar 0.006 0.000 0.006 0.014 -0.009 0.001 0.000

MVA 0.030 0.000 0.030 0.032

% PF 97.77 Lagging 100.00 Lagging 97.77 Lagging 89.17 Lagging

Number of Iterations: 2