TOPICS About Enercon Engineering System Configurations Grid Connection Switchgear New Multi-Function Generator Set Controllers
UTILITY CB
FEEDER CBs
GEN CB
GEN
GEN
GEN
BUILDING LOADS
GEN.
GEN.
GEN.
UTILITY CB
GEN
GEN
GEN
BUILDING LOADS
GEN.
GEN.
GEN.
UTILITY #1 CB TIE CB
UTILITY #2 CB
FEEDER CBs
GEN CB
GEN
BUILDING LOADS
BUILDING LOADS
GEN.
UTILITY #1 CB TIE CB
UTILITY #2 CB
FEEDER CBs
GEN CB
GEN
GEN
GEN.
BUILDING LOADS
BUILDING LOADS
GEN.
UTILITY CB
FEEDER CBs
GEN CB
GEN
GEN
GEN
BUILDING LOADS
GEN.
GEN.
GEN.
UTILITY CB
GEN
GEN
GEN
BUILDING LOADS
GEN.
GEN.
GEN.
UTILITY #1 CB TIE CB
UTILITY #2 CB
FEEDER CBs
GEN CB
GEN
BUILDING LOADS
BUILDING LOADS
GEN.
UTILITY #1 CB TIE CB
UTILITY #2 CB
FEEDER CBs
GEN CB
GEN
GEN
GEN.
BUILDING LOADS
BUILDING LOADS
GEN.
UTILITY CB
TIE CB
UTILITY CB
FEEDER CBs
GEN CB
GEN
GEN
BUILDING LOADS
BUILDING LOADS
GEN.
GEN.
TIE CB
TIE CB
TIE CB
FEEDER CBs
FEEDER CBs
BUILDING LOADS
BUILDING LOADS
GEN
GEN
GRID CONNECTION OPERATING MODES Base load Import control Export control Zero power transfer
BASE LOAD
900 800 700 600 500 400 300 200 100 0 -100 TIME LOAD UTILITY CONTRIBUTION GENERATOR CONTRIBUTION UTILITY LOAD GENERATOR BASE LOAD CONTROLS A FIXED GENERATOR kW.. OUTPUT LEVEL. IF THE LOAD IS GREATER THAN THE GENERATOR OUTPUT, POWER IS IMPORTED FROM THE UTILITY. IF THE LOAD IS LESS THAN THE GENERATOR OUTPUT, POWER IS EXPORTED TO THE UTILITY.
K I L O W A T T S
IMPORT CONTROL
900 800 IMPORT MODE CONTROLS A FIXED IMPORTED kW.. LEVEL FROM THE INCOMING UTILITY. AS THE LOAD VARIES, THE GENERATOR kW.. OUTPUT VARIES AND IS EQUAL TO THE LOAD MINUS THE IMPORTED kW..
K I L O W A T T S
LOAD
LOAD
500 400
300 200 100
GENERATOR
UTILITY
UTILITY
GENERATOR
B TIME UTILITY
GENERATION WITHOUT PROPER PF CONTROLLER ADJUSTMENT Kw LOAD CONSUMTION: UTILITY CONTRIBUTION: GEN. CONTRIBUTION: 1000 500 500 kVARS 750 525 225 kVA 1250 725 548 pF. 0.8 0.69 0.91 -- PF. SET
GENERATION WITH PROPER PF CONTROLLER ADJUSTMENT Kw LOAD CONSUMTION: UTILITY CONTRIBUTION: GEN. CONTRIBUTION: 1000 500 500 kVARS 750 375 375 kVA 1250 625 625 pF. 0.8 0.8 0.8 -- PF. SET
RISERS
MAIN BUS
RISERS
BUS BRACING
BUS RISERS
4000 AMP. MAIN BUS 2000 AMP. RISERS 2000 AMP. BREAKER 2000 AMP. BREAKER 2000 AMP. FEEDER BREAKER
2000 AMP. MAIN BUS 2000 AMP. RISERS 2000 AMP. FEEDER BREAKER 2000 AMP. BREAKER 2000 AMP. BREAKER
INCOMING UTILITY
52U
52F1
52F2
52ET
SITE LOAD
52 DESIGNATIONS ET - EMERGENCY TIE F - FEEDER G - GENERATOR U - UTILITY 52G3 52G1, 52G2, AND 52G3 ARE FIXED MOUNTED TYPE FIXED BREAKER SYMBOL
52G1
52G2
G1
G2
G3
INTEGRATED CONTROLLER FUNCTIONS Engine Start/Stop, Protection, Metering, & Control Generator Protection, Metering, & Control Multi-set Communications Utility and Tie Controller Modules Some Include Programmable Logic Functions (PLC)
ENGINE CONTROL Starter output contact Fuel solenoid contact Magnetic Pickup input (RPM) Cycle crank, overcrank timers Cooldown timer Warm-up timer Many other user settable timers Engine Auto/Manual switch Governor biasing for kW load sharing / kW load control
PT and CT connections (some accept 600v direct, no PTs) RTD Analog Modules for Bearing and Winding Temperature (not all) Protective Functions
Reverse Power Reverse VARS (Loss of Excitation) (not all) Over/Under Voltage Over/Under Frequency Negative Phase Sequence Overcurrent, IEC IMDT Curves (not all) Ground Fault (not all)
GENERATOR METERING
Amperage, each phase Voltage, each phase to phase Frequency Power Factor kW, kVAR kWH, kVARH Synchroscope w/ bus voltage and frequency display
GENERATOR CONTROL
Circuit breaker trip and close output contact Voltage Regulator Biasing (voltage setting)
Automatic Synchronizing w/ Voltage Matching PF Control When Paralleled to Utility kVAR Sharing when Island operation used
MULTISET CONTROL
First Up Sensing, Dead Bus Closing Import and Zero Power Transfer Control Loss of Utility Voltage Sensing Tie Breaker Control (not all) Starting on Load Demand (most require equal rated gensets)
MULTISET COMMUNICATIONS
INCOMING UTILITY #1 INCOMING UTILITY #2
Each Breaker: PTs, 2 sources CTs Close signal Trip signal Aux. contacts
LS4
LS4
LS4
GEN
BUILDING LOADS
BUILDING LOADS
GEN
GCP
CANBus Communications
GCP
CONTROLLER COMMUNIATIONS
MULTI-FUNCTION CONTROLLER
MULTI-FUNCTION CONTROLLER
MULTI-FUNCTION CONTROLLER
MULTI-FUNCTION CONTROLLER
MULTI-FUNCTION CONTROLLER
Deep Sea Electronics 5510 Genset Controller Deep Sea Electronics 5560 Mains Controller