DESIGN OF CIRCULAR PURE WATER SUMP

NOTATION USED:
CAPACITY OF TANK =

DIAMETER OF TANK =

DEPTH OF WATER IN TANK =


FREE BOARD WATER IN TANK =
TOTAL DEPTH OF TANK =
WIDTH OF WALK WAY =

h
FB
H
Ww

THICKNESS OF WALK WAY SLAB =

tw

THICKNESS OF VERTICAL WALL @ TOP =

Tw

THICKNESS OF VERTICAL WALL @ BOTTOM =

Bw

WDTH OF WALL FOOTING =

Fw

DEPTH OF WALL FOOTING =

Fd

WATER DEPH =

Hw

THICKNESS OF WALL =
HOOP TENSION IN WALL =
REQUIRED STEEL =
PROVIDED STEEL =
MINIMUM STEEL ON BOTH THE FACE = 0.24%

d
HTw
Ast.req
Ast.prv
Ast.min/b.f

MINIMUM STEEL ON EACH FACE =0.12%

Ast.min/e.f

DIAMETER OF BAR USED =

f.bar

REQUIRED SPACING OF STEEL =


PROVIDED SPACING OF STEEL =
TENSILE STRESS IN CONCRETE =
TENSILE STRESS IN CONCRETE =

Sp.req
Sp.prv

scc.cal
scc.alw

BENDING MOMENT =

DEPTH REQUIRED =

dreq.

Page 1 of 8

TANK DIMENSION:
CAPACITY OF SUMP (Q)

1050000 LITERS
1050 Cum

HEIGHT OF TANK PROPOSED (h)

3.4 Mtrs

FREE BOARD PROPOSED (FB)

0.6 Mtrs

TOTAL DEPTH OF TANK (H)

4 Mtrs

REQUIRED TANK DIAMETER (D)

19.83 Mtrs

PROVIDE DIAMETER OF TANK (D)

20.00 Mtrs

HAUNCH DIMENSION

WIDTH =

0.15 Mtrs

DEPTH =

0.15 Mtrs

NATURAL GROUND LEVEL (NGL)

599.00 Mtrs

STORAGE LEVEL (SL)

598.20 Mtrs

FINISHED BOTTOM FLORR LEVEL (FFL)

594.80 Mtrs

SPHERICAL DOME AT TOP


DOME EIGHT = D/7 TO D/5

2857.143

THEREFORE PROVIDED DOME HEIGHT =


THEREFORE DOME RADIUS = [(D/2)^2+h^2]/(2h)

TO

4000.000

mm

2500.00 mm
21250.00 mm

MATERIALS:
CONCRETE - M20 & STEEL-Fe-415
PERMISSIBLE STRESS IN CONCRETE & STEEL
(REF - IS:3370, (Part-II)-1965, TABLE-1 & 2)
MODULAR RATIO (m)

13.00

Page 2 of 8

a) DESIGN OF TOP DOME

THICKNESS OF TOP DOME

175 mm

LOADS:
SELF WEIGHT OF DOME =

0.4375 t/m^2

LIVE LOAD =

0.15 t/m^2

TOTAL LOAD =

0.588 t/m^2

THEREFORE, SinF =

0.471

THEREFORE, CosF =

0.882

THEREFORE, F =

280

HOOP FORCE =WR[CosF-1/(1+CosF)] =

4.38 t/m

HOOP STRESS =

0.25 N/mm^2

MERIDONIAL FORCE = WR(1-CosF)/(Sin^2(F)) =

6.63 t/m

THERE FORE MERIDONIAL STRESS =

0.38 N/mm^2

THERE PROVIDE MIN. REINFORCEMENT=0.12%

210 mm^2

DIAMETER OF PROVIDED STEEL

< 1.2 N/mm^2 (IS:3370, Part-II)

< 2.8 N/mm^2

8 mm

SPACING REQUIRED (SP.req)

239.39 mm

THEREFORE PROVIDED SPACING (Sp.prv)

200 mm

PROVIDE 8 MM DIA 200 MM C/C IN BOTH MERIDONIALLY & CIRCUMFERENTIALLY


PROVIDED STEEL (Ast,Pro)

251.328 mm^2

TENSILE STRESS IN EQUIVALENT AREA =

0.59

N/mm^2

6.63

t/m

< 1.2 N/mm^2 (IS:3370, Part-II)

b) DESIGN RING BEAM


MERIDONIAL FORCE = WR(1-CosF)/(Sin^2(F)) =

THEREFORE HORIZONTAL COMPONENT OF MERIDONIAL THRUST =


HOOP TENSION =
SIZE OF BEAM

58.52

MT

B=

600

mm

D=

600

mm

AREA OF STEEL REQUIRED (Ast.Req.) =


DIAMETER OF PROVIDED STEEL =
NUMBER BAR REQUIRED =
THEREFORE PROVIDED NUMBER

5.852

t/m

3901.37 mm^2
25 mm
7.95
8

SINCE RING BEAM IS SUPPORTED THROUGHT, PROVIDE NOMINAL SHEAR REINFORCEMENT OF 8 MM 2-LEGGED BARS @ 200 MM C/C

c) DESIGN OF VERTICAL WALL

Page 3 of 8

DIAMETER OF TANK (D)

20.00 Mtrs

DEPTH OF WATER (h)

3.4 Mtrs

THICKNESS OF TANK WALL @ TOP (Tw)

200 mm

THICKNESS OF TANK WALL @ BOTTOM (Bw)

350 mm

THICKNESS OF TANK WALL (for calculation)

275 mm

Page 4 of 8

HENCE THE RATIO (H^2/D*T)

2.10

DESIGN FOR HOOP TENSION


(Ref:IS3370, Part-IV,TABLE-12)

HTw

Ast.req

Ast.min/b.f

f.bar

Sp.req

Sp.prv

Ast.prv

scc.cal

scc.alw

mm^2

mm^2

mm

mm

mm

mm^2

N/mm^2

N/mm^2

0.074

2.516

167.73

534.00

10

294.16

180

872.67

0.120

1.20

235.25

0.179

6.086

405.73

564.60

10

278.21

180

872.67

0.275

1.20

1.28

248.00

0.281

9.554

636.93

595.20

10

246.62

180

872.67

0.408

1.20

0.3H

1.62

260.75

0.375

12.75

850.00

625.80

10

184.80

180

872.67

0.516

1.20

0.4H

1.96

273.50

0.449

15.266

1017.73

656.40

10

154.34

125

1256.64

0.576

1.20

0.5H

2.3

286.25

0.506

17.204

1146.93

687.00

10

136.96

125

1256.64

0.620

1.20

0.6H

2.64

299.00

0.519

17.646

1176.40

717.60

10

133.53

125

1256.64

0.608

1.20

0.7H

2.98

311.75

0.479

16.286

1085.73

748.20

10

144.68

125

1256.64

0.537

1.20

0.8H

3.32

324.50

0.375

12.75

850.00

778.80

10

184.80

125

1256.64

0.404

1.20

0.9H

3.66

337.25

0.21

7.14

476.00

809.40

10

194.07

125

1256.64

0.217

1.20

Hw

Hw
Mtrs

mm

0.0H

0.6

222.50

0.1H

0.94

0.2H

COEFF

Page 5 of 8

DESIGN FOR BENDING MOMENT


(Ref:IS3370, Part-IV,TABLE-10)

d.req

Ast.req

Ast.min/e.f

f.bar

Sp.req

Sp.prv

t-m

mm

mm^2

mm^2

mm

mm

mm

mm^2

0.001

0.039

35.868

14.32

282.30

10

278.21

180

436.33

248.00

0.0035

0.138

67.104

47.27

297.60

10

263.91

180

436.33

260.75

0.0068

0.267

93.534

86.87

312.90

10

251.01

180

436.33

1.96

273.50

0.0099

0.389

112.857

119.99

328.20

10

567.73

180

436.33

0.5H

2.3

286.25

0.012

0.472

124.252

138.34

343.50

10

228.65

180

436.33

0.6H

2.64

299.00

0.0115

0.452

121.636

126.41

358.80

10

218.90

180

436.33

0.7H

2.98

311.75

0.0075

0.295

98.230

78.77

374.10

10

209.94

180

436.33

0.8H

3.32

324.50

-0.0021

-0.083

51.978

-21.12

389.40

10

201.69

180

436.33

0.9H

3.66

337.25

-0.0185

-0.727

154.276

-178.44

404.70

10

194.07

180

436.33

1.0H

350.00

-0.0436

-1.714

236.841

-404.04

420.00

10

187.00

180

436.33

Hw

Hw
Mtrs

mm

0.1H

0.94

235.25

0.2H

1.28

0.3H

1.62

0.4H

COEFF

DESIGN FOR SHEAR FORCE


(Ref:IS3370, Part-IV,TABLE-11)
SHEAR COEFFICIENT =

0.299

SHEAR FORCE AT BASE =

3.46

MT

SHEAR STRESS =

0.122

N/mm^2

PERMISSIBLE SHEAR STRESS =

1.700

N/mm^2

Page 6 of 8

Ast.prv

d) DESIGN OF FLOOR
SLAB IS RESTING ON CONTINUOUS GROUND HENCE PROVIDE 150 MM THICK SLAB
MINIMUM AREA OF STEEL REQUIRED = 0.12% ON EACH FACE =

180.00

mm^2

PROVIDE 8 mm DIA & 250 mm C/C ON BOTH THE FACES & BOTH THE WAYS

e) DESIGN OF WALL FOOTING


WIDTH OF FOOTING BEYOND FACE OF WALL =

450

mm

WIDTH OF FOOTING INSIDE THE TANK BEYOND FACE =

600

mm

TOTAL WIDTH OF FOOTING (Fw)

1400

mm

DEPTH OF FOOTING (Fd)

300

mm

SURFACE AREA OF DOME =

333.84

Sq.M

THEREFORE TOTAL LOAD FROM DOME =

196.13

MT

LOAD PER METER ON WALL FROM DOME =

3.09

t/m

SELF WEIGHT OF RING BEAM =

0.6

t/m

RECTANGLE PORTION =

2.00

MT

TRIANGULAR PORTION =

0.75

MT

SELF WEIGHT OF FOOTING =

1.05

MT

WEGHT OF WATER =

2.04

MT

TOTAL VERTICAL LOAD PER M =

9.53

MT

FROM DOME LOAD =

2.163

t-m

FROM RING BEAM =

0.300

t-m

FROM VERTICAL WALL-REC. PORTION =

1.400

t-m

FROM VERTICAL WALL-TRIA. PORTION =

0.413

t-m

FROM SELF WEIGHT. FOOTING =

0.74

t-m

FROM WEIGHT WATER =

2.24

t-m

MOMENT @ BASE OF WALL =

-1.71

t-m

5.541

t-m

SELF WEIGHT OF VERTICAL WALL =

MOMENT @ END OF FOOTING

TOTAL MOMENT =

Page 7 of 8

DISTANCE OF THE RESULTANT FROM END = X =

0.581

ECCENTRICITY =(B/2-X) =

0.119

SBC OF SOIL =

m
m

15

t/m^2

MAXIMUM SOIL PRESSURE =

10.267

t/m^2

MINIMUM SOIL PRESSURE =

3.348

t/m^2

PRESSURE ON SOIL = P/A+or-M/Z

SOIL PRESSURE LESS THEN SBC HENCE OK


MAXIMUM BENDING MOMENT @ FACE OF WALL =

1.040

t-m

DEPTH REQUIRED =

184.464

mm

PROVIDED DEPTH = D-60 =

240.00

mm

AREA OF STEEL REQUIRED =

331.91

mm^2

MIN. ASTEEL REQUIRED ON ECH FACE =

360

mm^2

DIAMETER OF MAIN BARS USED =

10

mm

218.17

mm

200

mm

mm

SPACING REQUIRED FOR MAIN BARS =


PROVIDED SPACING OF MAIN BARS =
DIAMETER OF DISTRIBUTION BARS USED =
SPACING REQUIRED FOR DISTRIBUTION BARS =
PROVIDED SPACING OF DISTRIBUTION BARS =

139.626667 mm
125

mm

CHECK FOR ONE WAY SHEAR:


TOTAL SHEAR FORCE =

4.620

SHEAR STRESS =

0.221

< 1.7 N/mm^2

(REF:IS3370-Part-II, TABLE-2)

HENCE O.K

CHECK FOR TWO WAY SHEAR:


PUNCHING LOAD =
RESISTING AREA FOR PUNCHING =
PUNCHING STRESS =
PERMISSIBLE PUNC. STRESS =0.16*SQRT(Fck) =

9.53
480000

T
mm^2

0.199

N/mm^2

0.716

mm^2

(REF:IS456-2000, Clause-31.6.3)

Page 8 of 8