Standards and Guides for Transformer Maintenance and Diagnostics

Matz Ohlen, Megger Sweden

Testing and Standards


CIGRE
CIGRE Brochure 342 (SFRA-FRAX) CIGRE Brochure 414 (DFR-IDAX) CIGRE Brochure 445 (Guide for Transformer Maintenance)

IEC, TC 14
IEC 60076-1, Power Transformers IEC 60076-2, Temperature rise IEC 60076-3, Insulation levels, dielectric tests and external clearances in air IEC 60076-18, Measurement of frequency response (SFRA)

ANSI, IEEE Transformer Committee


IEEE C57.152 IEEE C57.12.00-2006 IEEE C57.12.90-2006 IEEE PC57.149 (former IEEE 62-1995) (under revision) (under revision) (SFRA)

Guides and standards for transformer testing (1)

Most standards (IEC and ANSI/IEEE) are focusing on new transformers and factory testing Workgroups in e.g. Cigr have over the years produced a lot of Technical Brochures (TB) e.g. on sweep frequency response measurements (TB342), partial discharge (TB366), dielectric response measurements (TB414) etc IEEE 62-1995 Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors is probably the most well-known guide for diagnostic field testing of oil filled power transformers. The guide today belong to the IEEE C57-series and last published revision is C57.152-2013

Cigr Technical Brochure 445, 2011 Guide for Transformer Maintenance

CIGRE TB 445
Cigr TB 445, Guide for Transformer Maintenance, was published 2011 TB 445 is a comprehensive combination of education handbook, transformer encyclopedia and a guide for transformer maintenance including guidelines for how to perform measurements in the field

TB 445 - Content

IEEE C57.152-2013 Guide for Diagnostic Field Testing of FluidFilled Power Transformers, Regulators, and Reactors

IEEE C57-152
IEEE C57.152 Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors, is a revision of IEEE 62-1995 and was published 2013 IEEE C57.152 is a guide that describes diagnostic field tests and measurements that are performed on fluid-filled power transformers and regulators and does NOT contain general information on transformer components and transformer maintenance

IEEE C57-152 - Content

Diagnostic and Maintenance test charts IEEE C57.152

10

Diagnostic matrix CIGRE TB445

11

Differences GIGRE - IEEE

CIGRE test categories by methods


o Basic Electrical o Advanced Electrical o Dissolved Gas Analysis (DGA)

IEEE test categories


o By component o Event based

12

Diagnostic Technique (CIGRE)

Basic Electrical Advanced Electrical Dissolved Gas Analysis (DGA)

13

Basic Electrical
Winding Ratio Winding Resistance Magnetization (excitation) current Capacitance and DF/PF Insulation Resistance Core Ground Test

14

Winding Ratio

15

Winding Resistance

16

Magnetization (excitation) current

17

Capacitance and DF/PF

18

Capacitance and DF/PF - Bushings

19

Leakage Reactance

20

Insulation Resistance

21

Core Grounding

22

Advanced Electrical
Frequency Response of Stray Losses (FRSL) Frequency Response Analysis Polarization/Depolarization Frequency Domain Spectroscopy Recovery Voltage Method Electrical Detection of PD Acoustical Detection of PD UHF Detection of PD

23

Frequency Response Analysis

24

Frequency Domain Spectroscopy (FDS/DFR)

25

Bushing measurements

26

Summary CIGRE TB 445


TB 445 is a combination of a transformer handbook, transformer encyclopedia and application guide for transformer maintenance including guidelines for transformer field testing Lots of very good information. Details and guidelines can and will be discussed e.g. assessment data and advantages/disadvantages with different measurement methods (e.g. combined PDC-FDS combination versus true AC DFR/FDS measurements)

27

28