Vous êtes sur la page 1sur 2

Zone Verification

Report Time: 4/30/2013 3:18:45 PM

Zone Verification

Test Time:2013-04-30 15:10:51

Setting
Test mode: Auto
Earth Compensation
Mode: KL , KL: 0.65 , Angle: -5
Close angle: 0
CT Direction : Object
Zone 1:
Test points: 0.95, 1.05, 0.5,
Z Setting(L-L): R=0.065 , X=0.43
Zone 2:
Test points: 0.95, 1.05, 0.9,
Z Setting(L-L): R=0.09 , X=0.53
Zone 3:
Test points: 0.95, 1.05, 0.9,
Z Setting(L-L): R=0.207 , X=1.35
.
Binary input setting:
Bin 1
Trigger Logic : or

Set fixed value: Zone 1(A)=4 , Zone 2(A)=2


Zone 3(A)=2 , Zone 4(A)=2 , Zone 5(A)=2
Prefault: 1 ; Postfault: 0.5
Health voltage after fault: No
.
Select fault: A-B-C,
Z Setting(L-N): R=0.065 , X=0.43
Time Setting(s): 0
Select fault: A-B-C,
Z Setting(L-N): R=0.09 , X=0.53
Time Setting(s): 0.35
Select fault: A-B-C,
Z Setting(L-N): R=0.207 , X=1.35
Time Setting(s): 0.7
.
.
Input name: Trip1

Test results
Trip time(s)

Fault Type

Z Setting(ohm)

Fixed Val

Judge

0.052

A-B-C

Zone 1: 0.435

95

4A

Failure

No Trip

A-B-C

Zone 1: 0.435

105

4A

Passed

0.027

A-B-C

Zone 1: 0.435

50

4A

Passed

0.421

A-B-C

Zone 2: 0.538

95

2A

Passed

No Trip

A-B-C

Zone 2: 0.538

105

2A

Passed

0.3935

A-B-C

Zone 2: 0.538

90

2A

Passed

0.7545

A-B-C

Zone 3: 1.366

95

2A

Passed

No Trip

A-B-C

Zone 3: 1.366

105

2A

Passed

0.7495

A-B-C

Zone 3: 1.366

90

2A

Passed

1 / 1