Following flow chart gives the sequences generally

followed in clearing a particular fault in EWSD system.

Fault detection
 
Automatic
Fault analysis measures by
EWSD
Fault signalling System

Alarm confirmation  
manual
measures by
Fault clearance with O&M staff
Diagnosis and removal

Fig 1.0
MML - CMD to read contents of HF.ARCHIVE file.

DISP AENTRY : AFILE= HF.ARCHIVE, AENTRY=…….;

SEL AENTRY : AFILE= HF.ARCHIVE, JN=….. , DATE=…...


TIME=……, MSG=……, ALPRIO=……….,
DIR=…….;

MML - CMD to read contents of AM . ALARM file.

DISP ALARM : [ OBJECT = ] , [ALSTAT = ] , [ALPRIO = ] ;

SRCH ALARM : [ OBJECT = ] , [ALSTAT = ] , [ALPRIO = ] ,


[MSGNO= ] ;
Label on SYPD OBJECT
LINE LOCKOUT LNLCKOUT
LINE/TRUNK GROUPS LTG
SYSTEM PANEL SYP

TRUNK GROUP ALARM TGAL

MAINTEN. ALARM MAL


SERVICE ALARM SAL

EXTERNAL ALARM EALEXCH


EXT. DLU ALARM EALDLU

SWITCHING NETWORK SN
MESSAGE BUFFER MB
CENTRAL UNITS CU

RECOVERY RECOV

SYSTEM OPERATOR SYOP


CLOCK CLOCK
ADMIN. ALARMS ADMINAL
EXTERN. EQUIPM. DLU

SIGNALLING LINK NO. 7 SIGLINK


TIME INSECURE TIMINSEC
COM. CHAN. SIGNALING CCS
SN FAILURE WITH CONFIGURATIONMMN:SN0xx-0000

SGC DEFECT

FAULT  LOCATION:TSG-side-tsgSGC

CONFIGURATION:TSG-side-tsgFROM:   zzz  TO:   UNA

SUPPLEMENTRY  INFORMATION

H’  zzzzzzzz   zzzzzzzz   zzzzzzzz  zzzzzzzz
H’  zzzzzzzz   zzzzzzzz   zzzzzzzz  zzzzzzzz
General Procedure for fault clearance in EWSD
  SYP 100
 
 
 
N
  Alarm END of procedure
 
  Present
  at

Y  N
  Buzzer at SYPD on
 
 
 
 
 

Press accept-key
 
 
  Set up session to exchange
 
  NP means NOT PROCESSED
DISP ALARM: ALSTAT = NP,
  (ALARMS)
OBJECT = xxx
 
  MSGNO is taken from the output of DISP ALARM cmd..
SRCH ALARM : MSGNO = xxx;
 
 
SET ALSTAT : MSGN = xxx, IP means IN PROCESS i.e. ALARM is being processed.
 
ALSTAT = IP
 
  DACT OUTSUP means output suppression on OMT has been
DACT OUTSUP:
  deactivated
LOCDEV =Systemdevice-FUOMT,
 
  Fault clearance Relevant MMN details are taken from
  According to MMN the fault message/printout.
 
SYP101 is a standard procedure for ending the HW fault clearance.
 
  SYP 100
 
 
SRCH ALARM
MSGNO = xxx;