INSTRUCTION MANUAL FOR SCREW COMPRESSOR UNIT CONTROLLER MYPRO-CPIV

F1

F2

F3

F4

F5

F6

F7

START ST OP

1 4

2 5 8 .

3 6 9 -

ESC SH IFT

DELETE ALT

MYPRO-CP 7
CLEAR ALARM

TAB

SAVE

ENTER

MYPRO-CPIV (standard version)

Read this manual carefully before you can use and service MYPRO-CPIV safely and properly.

QT108300

Important Notice
This manual has been prepared as a guide to allow you to use the Screw Compressor Unit Controller MYPRO-CPIV properly and safely. Follow all the instructions in this manual. Failure to do so could result in unforeseen accidents. Keep this manual handy for ready and regular reference by all persons working on your MYPRO-CPIV. If the manual is lost or damaged, contact any of the Mayekawa offices or sales/service centers in your area to order a new copy. This manual must remain with the product when you resell it to another user. Mayekawa reserves the right to make changes to the specifications of the product the contents of this manual for improvements without prior notice. If you have any query due to inconsistency between the product and the information in this manual that can result from such changes, please ask questions to any of the Mayekawa offices or sales/service centers in your area. Be sure to start operation, inspection, and servicing of the equipment only after having thoroughly read and understood all the hazard preventive instructions and precautions in this manual. Almost all the past accidents occurred due to failure to follow the basic safety rules. All safety instructions and precautions in this manual are highlighted by appropriate one of the following symbol-letter combinations:

DANGER

Indicates a potentially hazardous situation which, if not avoided, will result in death or serious injury.

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, will or could result in minor or

CAUTION

moderate injury. This also indicates an instruction that should be followed to obtain full performance from the product.

The safety instructions and precautions in this manual are not exhaustive. There may be other safety precautions to be observed that vary from user to user. It is your responsibility to establish a safety management system most appropriate for your particular use of the product. Never disassemble or otherwise interfere with the Screw Compressor Unit Controller MYPRO-CPIV, as it contains many electronic components that can be adversely affected by disassembly or other interference. Mayekawa Mfg. Co., Ltd. assumes no responsibility for any undesirable consequences that would result from disassembly of or interference with the controller. Use this controller solely for control and management of the screw compressor units produced by Mayekawa Mfg. Co., Ltd.

-1-

QT108300

Preface
Thank you for your purchase of Mayekawa Screw Unit Controller MYPRO-CPIV (hereafter called CP4 in this manual). Before installing and putting your CP4 into service, check the following points: a. Is your CP4 exactly of the factory-option variation you specified? CP4 is available from the following 12 factory-option variations: CPIV-110 (standard version): 16 digital inputs/outputs; 16 analog inputs; 2 communication ports CPIV-111: CPIV-110C: CPIV-111C: CPIV-210: CPIV-211: CPIV-210C: CPIV-211C: CPIV-220: CPIV-221: CPIV-220C: CPIV-221C: 16 digital inputs/outputs; 16 analog inputs; 4 analog outputs; 2 communication ports 16 digital inputs/outputs; 16 analog inputs; 2 communication ports; 2 extension communication ports 16 digital inputs/outputs; 16 analog inputs; 4 analog outputs; 2 communication ports; 2 extension communication ports 32 digital inputs/outputs; 16 analog inputs; 2 communication ports 32 digital inputs/outputs; 16 analog inputs; 4 analog outputs; 2 communication ports 32 digital inputs/outputs; 16 analog inputs; 2 communication ports; 2 extension communication ports 32 digital inputs/outputs; 16 analog inputs; 4 analog outputs; 2 communication ports; 2 extension communication ports 32 digital inputs/outputs; 32 analog inputs; 2 communication ports 32 digital inputs/outputs; 32 analog inputs; 4 analog outputs; 2 communication ports 32 digital inputs/outputs; 32 analog inputs; 2 communication ports; 2 extension communication ports 32 digital inputs/outputs; 32 analog inputs; 4 analog outputs; 2 communication ports; 2 extension communication ports b. Are all necessary items supplied? Check the items in the package against the packaging list. The standard version CP4 should be provided with a set of the following items: Control panel enclosure, analog input boards (AI10, AI11); connection cable (1-meter long C1200); digital input/output board (OIA0); connection cable (1-meter long C1300); power cables (1.2-meter long C0312 x 2, 1.2-meter long C0322 x 1); noise filter (rating: 250 VAC, 6 A); instruction manual (one copy of this manual) c. Are the settings in the following windows correct? Be sure to confirm the following settings in the corresponding windows before putting CP4 into service. SETUP menu windows (F6): ADJUSTMENT menu windows (F5): LIMITS menu windows (F3): SETPOINT menu window (F1): Are the settings for the OPTION SETUP items appropriate for the compressor unit under control? (see Chapter 4) Is the scaling setting for each sensor correct? (see Chapter 5) Are the settings for each alarm appropriate? (see Chapter 7) Are the start/stop (CUT IN / CUT OUT) settings appropriate? (see Chapter 6)

Mayekawa Mfg. Co., Ltd.


-2-

QT108300

Table of Contents
Preface .........................................................................................................................................................................................2 Table of Contents..........................................................................................................................................................................3 Chapter 0 Information on This Manual..........................................................................................................................................6 0.1 0.2 0.3 0.4 0.5 0.6 1.1 1.2 1.3 2.1 2.2 This Manual and Other Related Manuals .......................................................................................................................6 Organization of This Manual...........................................................................................................................................6 Glossary of Special Terms ..............................................................................................................................................7 Units ...............................................................................................................................................................................8 Words Displayed on Screen ...........................................................................................................................................8 Acronyms and Abbreviations ..........................................................................................................................................8 Functions and Features..................................................................................................................................................9 Menu-Window Organization (Menu Tree).......................................................................................................................9 Usable Control Functions Depending on Selected Factory Options.............................................................................11 Front Panel...................................................................................................................................................................13 Parts on CPU Board (REF-CX100-PR01) ....................................................................................................................15 Reset Switch on CPU Board................................................................................................................................17 Replacement of Memory Backup Battery on CPU Board .....................................................................................18 Replacement of EPROM on CPU Board ..............................................................................................................20 Current / Voltage Selection and Terminal Block Connections for Analog Input Boards .........................................22 Input Type Selection for Channels 15 and 16 of Analog Input Boards ..................................................................23

Chapter 1 General Description .....................................................................................................................................................9

Chapter 2 Components and Their Functions ..............................................................................................................................13

2.2.1 2.2.2 2.3 2.4 2.3.1 2.4.1 2.4.2 2.5 2.6 2.7 2.8 2.9 3.1

EPROM Board (REF-CX100-RM01) ............................................................................................................................19 Analog Input Boards (REF-CX100-AI01, REF-CX100-AI11) ........................................................................................21

Optional Analog Output Board (REF-CX100-DA01) .....................................................................................................24 Optional Digital Input/Output Drive Base (DB) Board (REF-CX100-DB01) ..................................................................25 Digital Input/Output Board (REF-MCS200-OIA0, REF-MCS200-OIE0 (Optional)) .......................................................26 Optional Communication Board (REF-CX100-RS01)...................................................................................................27 Optional Analog-to-Digital (AD) Converter Board (REF-CX100-AD01) ........................................................................28 Display Screens ...........................................................................................................................................................29 Acronyms and Abbreviations Used for Indicated Items.........................................................................................29 Main Graphic Screen ............................................................................................................................................32 Main Status Screen...............................................................................................................................................33

Chapter 3 Operation ...................................................................................................................................................................29 3.1.1 3.1.2 3.1.3 3.2 3.3 3.4 3.5 4.1 4.2 4.3 4.4 4.5 4.6 5.1 5.2 5.3 5.4 5.5 5.6

To Make Settings Selection from Options..................................................................................................................39 To Make Setting Entry Using Keys ............................................................................................................................40 Software Resetting Method ..........................................................................................................................................42 Special Booting.............................................................................................................................................................43 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6)) ......................................................................46 Settings in ANALOG INPUT SCALING Window (Option 2 of SETUP Menu (F6)).....................................................48 Settings in OPTION ANALOG INPUT Window (Option 3 of SETUP Menu (F6)).......................................................49 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)) ...............................................................51 Setting in OPTION SETUP 2/2 Window (Option 5 of SETUP Menu (F6)) .................................................................53 Settings in OPTION SELECT Window (Option 6 of SETUP Menu (F6)) ...................................................................55 Settings in SLIDE VALVE SETUP Window (Option 1 of ADJUSTMENT Menu (F5)) ................................................57 Settings in SET TIME Windows (Option 2 of ADJUSTMENT Menu (F5)) .................................................................66 Settings in PASSWORD Window (Option 3 of ADJUSTMENT Menu (F5)) ...............................................................68 Settings in ANALOG INPUT ADJUSTMENT Window (Option 4 of ADJUSTMENT Menu (F5)) ................................69 Settings in ANALOG OUTPUT ADJUSTMENT Window (Option 5 of ADJUSTMENT Menu (F5)) ............................70 Settings in ANALOG OUTPUT ASSIGNMENT Window (Option 6 of ADJUSTMENT Menu (F5)).............................71

Chapter 4 Setups (SETUP Menu (F6))......................................................................................................................................46

Chapter 5 Adjustments (ADJUSTMENT Menu (F5)) .................................................................................................................57

-3-

QT108300

5.7 5.8 6.1 6.2 6.3 6.4 6.5 6.6 6.7 7.1

Settings in AUXILIARY INPUT TIMER Window (Option 7 of ADJUSTMENT Menu (F5)) .........................................74 Adjustments in COMMUNICATION SETUP Window (Option 8 of ADJUSTMENT Menu (F5)) .................................75 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1)).......................................................77 Manual Control from D/O TEST OPERATION Window (Option 2 of SETPOINTS Menu (F1))..................................78 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1)) ..................................................................80 Settings in SCHEDULER Window (Option 4 of SETPOINTS Menu (F1)) .................................................................81 Setting in OTHER SETPOINT Window (Option 5 of SETPOINTS Menu (F1))..........................................................84 Settings in AUTO Vi Window (Option 6 of SETPOINTS Menu (F1)) .........................................................................86 Settings in AUTO STAGE Window (Option 7 of SETPOINTS Menu (F1)).................................................................88 Settings in ALARM/FAILURE Windows 1/3 to 3/3 ......................................................................................................95 ALARM/FAILURE 1/3 Window ............................................................................................................................95 ALARM/FAILURE 2/3 Window ............................................................................................................................97 ALARM/FAILURE 3/3 Window ............................................................................................................................98 ALARM/FAILURE & OEM LIMITS 1/2 Window ...................................................................................................99 ALARM/FAILURE & OEM LIMITS 2/2 Window .................................................................................................100

Chapter 6 Control Selections (SETPOINTS Menu (F1)) ...........................................................................................................77

Chapter 7 Alarms (LIMITS Menu (F3)) ......................................................................................................................................95 7.1.1 7.1.2 7.1.3 7.2 7.2.1 7.2.2 7.3 8.1

Settings in OEM LIMITS 1/2 and OEM LIMITS 2/2 Windows (Options 4 and 5 of LIMITS Menu (F3)) ....................99

Settings in RANGE OVER Window (Option 6 of LIMITS Menu (F3)) ......................................................................100 Control of Compressor Unit Operation .......................................................................................................................102 Start/Stop Control in Different Operation Control Modes.....................................................................................102 Compressor Capacity Control Settings in CAPACITY CONTROL Window (Option 1 of CONTROLLER Menu (F2)) ............................................................................................................104 Settings in VFD COMPRESSOR CONTROL window (Option 2 of CONTROLLER Menu (F2)) ......................107 Settings in VFD SETUP Window (SHIFT 3 of CONTROLLER Menu (F2))......................................................108 Settings in CONDENSER CONTROL Window (Option 0 of CONTROLLER Menu (F2)).................................109 System Configuration ......................................................................................................................................... 112 Remote Communication Device and Communication Protocols......................................................................... 112 Connecting Communication Terminating Resistors ............................................................................................ 113 MODBUS Protocol.............................................................................................................................................. 114

Chapter 8 Operation .................................................................................................................................................................102 8.1.1 8.1.2 8.1.3 8.1.4 8.1.5 8.2 8.2.1 8.2.2 8.2.3 8.2.4 9.1 9.2 9.3 9.4 9.5 9.6 9.7 10.1 10.2 10.3 10.4 10.5 10.6 10.7 10.8 10.9

Communications......................................................................................................................................................... 112

Chapter 9 Maintenance (LOGS Menu (F4)) ............................................................................................................................ 116 Display in TRENO LOG Window (Option 1 of LOGS Menu (F4))............................................................................ 116 Display in TREND GRAPH Window (SHIFT 1 of LOGS Menu (F4)) ....................................................................... 117 Settings in GRAPH ASSIGNMENT Window (SHIFT2 of LOGS Menu (F4))............................................................ 118 Displays in ALARM LOG Window (Option 2 of LOGS Menu (F4)) .......................................................................... 119 Display in EVENT LOG Window (Option 3 of LOGS Menu (F4)).............................................................................121 Display in DEVICE COUNTER MONITOR Window (Option 4 of LOGS Menu (F4)) ...............................................122 Resetting Made in DEVICE COUNTER SET Window (Option 5 of LOGS Menu (F4) )...........................................123 Display in SHOW SYSTEM SETUP Window (Option 1 of DIAGNOSTIC Menu (F7)) ..........................................124 Display in SHOW ANALOG INPUT SCALINGT Window (Option 2 of DIAGNOSTIC Menu (F7)).........................124 Display in SHOW OPTION ANALOG INPUT Window (Option 3 of DIAGNOSTIC Menu (F7)).............................125 Display in SHOW DIGITAL I/O STATUS Window (Option 4 of DIAGNOSTIC Menu (F7)) ....................................125 Display in SHOW OPTION SETUP 1/2 Window (Option 5 of DIAGNOSTIC Menu (F7)) .....................................126 Display in SHOW OPTION SETUP 2/2 Window (Option 6 of DIAGNOSTIC Menu (F7)) .....................................126 Display in SHOW PROGRAM VERSION Window (Option 7 of DIAGNOSTIC Menu (F7)) ..................................127 Display in READ REGISTER Window (Option 8 of DIAGNOSTIC Menu (F7)).....................................................127 Display in READ BIT Window (Option 9 of DIAGNOSTIC Menu (F7)) .................................................................128

Chapter 10 Analysis (DIAGNOSTIC Menu (F7)) .....................................................................................................................124

10.10 Display in READ TIMER/COUNTER Window (Option 0 in DIAGNOSTIC Menu (F7)) .............................................128 Chapter 11 Troubleshooting......................................................................................................................................................129 Chapter 12 Specifications .........................................................................................................................................................133 -4-

QT108300

Device List ............................................................................................................................................................................136 List of Replaceable Parts ......................................................................................................................................................242 Software Revision Record 1..................................................................................................................................................243 Software Revision Record 2..................................................................................................................................................244

-5-

QT108300

Chapter 0 Information on This Manual


0.1 This Manual and Other Related Manuals
This manual is one of the four manuals each containing information about MYPRO-CPIV (CP4) as follows: - COMPRESSOR CONTROL PANEL (Model MYPRO-CPIV/E) MANUAL Contains information necessary for the engineering staff in charge of operation, maintenance, and communications of CP4. The information includes description on the CP4s functions and specifications, instructions for wiring/connections, setting and operation, method for troubleshooting, and other data necessary for maintenance service. - MYPRO-CPIV (MYCOM SCREW UNIT CONTROLLER) MANUAL Provides information on transportation, installation, setting up for operation, maintenance, and disposal of the MYCOM Screw Compressor Unit Control Panel Model MYPRO-CPIV/E. - MYPRO-CPIV (MYCOM SCREW UNIT CONTROLLER) START-UP MANUAL Describes the start-up procedures of CP4 in a simplified form, beginning with the initialization. - MYPRO-CPIV (MYCOM SCREW UNIT CONTROLLER) FACTORY MANUAL Contains instructions for the setting to be made on CP4 before shipment from the factory.

0.2 Organization of This Manual


This manual consists of the following three groups of chapters. Chapters 1 to 3 These chapters contain the following introductory information for the use of CP4. Chapter 1 shows the function menus (hereafter simply called menu) and the function windows (hereafter simply called windows) that can be accessed from each menu (menu tree). The functions available as factory options are also shown in this chapter. Chapter 2 contains the following items of information about CP4: the functions and operation of the individual keys on the front panel; description of the CPU board including the operations you need to perform on it; and the optional extension circuit boards. Chapter 3 contains the following items of information: how to make appear a desired display on the front panel screen and read the displayed data; how to make selections or entries to set parameters; and how to perform special booting required when making some settings and initialization/resetting. Chapters 4 to 10 These chapters contain detailed description of individual windows, including the methods of setting for the parameter items in each window, limitations applied to certain settings, and detailed explanation of special function-related items, such as the communication protocol, automatic staging (AUTO STAGE) control, etc. Chapters 11 and 12 Chapter 11 provides troubleshooting information. Chapter 12 contains the specifications and other miscellaneous information including the replacement parts list, software version list, device lists etc.

-6-

QT108300

0.3 Glossary of Special Terms


The special terms used in this manual are defined below. ALARM ALARM is a non-critical alarm that does not involve any compressor unit shutdown. Automatic staging control (AUTO STAGE) The automatic staging control works on multiple compressor units with their CP4s inter-connected through communication ports. Of these CP4s, one is assigned to the master station. The master station issues commands to start or stop the compressor under control of each of the other CP4s (called the slave stations) to properly adjust the number of operating compressors according to the required gas compressing capacity for the refrigerating system. Compressor unit Compressor unit refers to a system consisting of a compressor, condenser, expansion values, chiller, and driving motors. Each compressor unit operates under control of one CP4. FAILURE FAILURE is a critical alarm that involves compressor unit shutdown. Hardware key The hardware key is a special device that is not supplied with the product. It is used for adjustments necessary before shipment of the product from the factory. Main Graphic Screen This screen appears first when CP4 is turned on and shows the compressors status using graphics. Main Status Screen This screen shows the compressors status using alphanumeric characters. This screen appears when the TAB key is pressed on the front panel when the Main Graphic Screen is displayed. Manipulating value The amount of control expressed in a sum of the proportional, integral, and derivative controls (PID control) concerning with the capacity, speed, and other controls. Mask time Mask time refers to the time set by the user during which no determination to or not to issue an alarm takes place. Master station Master station is defined differently according to the control configuration using PC4s. - In the case of the automatic staging control (AUTO STAGE), the master station is the CP4 that gives operational commands to the other CP4s according to information of its own as well as that it receives from the slave CP4s. - In the case of the control using a remote control device such as a computer through communications, the master station refers to the remote control device controlling the CP4s in the network. Menu Each function of CP4 has a menu that provides options to make access to individual windows. Each menu can be selected by pressing one of the function keys on the front panel. OEM limit OEM limit refers to the upper or lower limit of each alarm set value.

-7-

QT108300

Offset If analog input values are too small or too large for processing over the entire range of measurement, a positive or negative offset value is added for proper processing and indication. You can specify offset values as part of settings. Passwords You must enter a password of the specified level before you can make settings in some special windows. Three different levels of password (LEVEL-1, LEVEL-2, and LEVEL-3) must be registered beforehand to be able to access these windows, each requiring a specific level of password for authorization. See Section 5.3 Settings in PASSWORD Window (Option 3 of ADJUSTMENT Menu (F5)) for further details. Scaling Scaling means a setting to specify the range (upper and lower limits) for input values from each sensor. Special booting Special booting is the method for booting CP4 that is required before performing the system setup and initializing individual control settings. Trimming data With CP4, trimming, means output adjustment. The value for the adjustment is written in a non-volatile memory. Window A screen that is accessed from each menu. It is used for making parameter settings and for checking the status of settings or operation of the compressor unit. Some windows include multiple sub-windows.

0.4 Units
Unless otherwise specified, all pressures are indicated in MPa (gauge readings) and temperatures in C.

0.5 Words Displayed on Screen


In this manual, the words displayed on the screen (menus, windows, parameter items, selective options, etc.) are indicated in all capital letters enclosed by single quotation marks like SETUP (although quotation marks are basically omitted in tables).

0.6 Acronyms and Abbreviations


For interpretation of the acronyms and abbreviations used in display, see Section 3.1 Display Screens.

-8-

QT108300

Chapter 1 General Description


1.1 Functions and Features
CP4 is a controller developed for controlling operation of the Mayekawa-produced screw compressor units. The controller has the following standard features: Sequence control and process control inputs/outputs - 16 digital inputs/outputs - 16 analog inputs User-controller interface - Backlit color LCD capable of displaying 80 digits x 30 lines alphanumeric characters - Keypad with numeric keys, function keys, and control keys (33 keys in total) The LCD can collectively display multiple measurements and concurrently display settings and actual measurements. The key groups are arranged efficiently, allowing easy screen switching and change of settings. Communication ports The following communication ports are standard provisions: - One serial communication port with a round connector conforming to special-purpose RS-232C - One half-duplex, 4-wire serial communication port conforming to RS-485 The serial communications function allows remotely monitoring the operating conditions of compressor units, making their start/stop control, and changing various parameter settings. The MODBUS protocol employed is world standard protocol for serial communications in industry and allows for the use of commercially available supervisory control and data acquisition (SCADA) software as well as connection to and communication with PLC MODBUS communications units of various manufacturers. Optional extension boards for additional inputs/outputs channels and communication ports The following optional items are available for expanded connections to CP4. - Extension digital/analog converter (DA) board for additional 4 analog outputs - Extension analog input board for additional 16 analog inputs - Extension digital input/output board for additional 14 digital output channels and 2 digital input channels - Extension communication board for additional 2 communication ports Either of two status windows is selectable: Main Graphic and Main Status. (A function key is used on the menu screen for selecting each window.) No-voltage contact signals or under-voltage solid-state relay (SSR) signals 4 to 20 mA DC inputs, 1 to 5 V DC inputs, or 1-k potentiometer inputs

1.2 Menu-Window Organization (Menu Tree)


The individual function menus are associated with the function keys F1 to F7 (see Section 2.1). Each menu includes the windows to which specific names are given together with Option numbers as shown below. The section number in parentheses after each window menu indicates the section of this manual containing the information on the window.

-9-

QT108300

Menu Tree

Main Graphic and Main Status windows F1 SETPOINTS 1. OPERATION MODE (Section 6.1) 2. D/O TEST OPERATION (Section 6.2) 3. SET POINTS (Section 6.3) 4. SCHEDULER (Section 6.4) 5. OTHER SET POINTS (Section 6.5) 6. AUTO Vi (Section 6.6) 7. AUTO STAGE (Section 6.7) 1. CAPACITY CONTROL (Section 8.1.2) 2. VFD COMPRESSOR CONTROL (Section 8.1.3) 3 .HIGH STAGE CONTROL 4. EXPANSION VALVE (SH) CONTROL (4.LIQUID SUPPLY CONTROL) 5. EXPANSION VALVE (SP) CONTROL 6. EXPANSION VALVE (LB) CONTROL 7. ECONOMIZER/INTER COOLER EXPANSION VALVE CONTROL (7.ECONOMIZER/INTERCOOLER SV) 8. LIQUID INJECTION OIL COOLING (8.LIQUID INJECTION SV) 9. CHILLER LB TEMPERATURE CONTROL 0. CONDENSER CONTROL (Section 8.1.5) SHIFT1. LEVEL CONTROL SHIFT3. VFD SETUP (Section 8.1.4) 1. ALARM/FAILURE 1/3 (Section 7.1) 2. ALARM/FAILURE 2/3 (Section 7.1) 3. ALARM/FAILURE 3/3 (Section 7.1) 4. OEM LIMITS 1/2 (Section 7.2) 5. OEM LIMITS 2/2 (Section 7.2) 6. RANGE OVER (Section 7.3) 1. TREND LOG (Section 9.1) 2. ALARM LOG (Section 9.4) 3. EVENT LOG (Section 9.5) 4. DEVICE COUNTER MONITOR (Section 9.6) 5. DEVICE COUNTER SET (Section 9.7) SHIFT1. TREND GRAPH SHIFT2. GRAPH ASSIGNMENT 1. SLIDE VALVE SETUP (Section 5.1) 2. SET TIME (Section 5.2) 3. PASSWORD (Section 5.3) 4. ANALOG INPUT ADJUSTMENT (Section 5.4) 5. ANALOG OUTPUT ADJUSTMENT (Section 5.5) 6. ANALOG OUTPUT ASSINGMENT (Section 5.6) 7. AUXILIARY INPUT TIMER (Section 5.7) 8. COMMUNICATION SETUP (Section 5.8) 1. SYSTEM SETUP (Section 4.1) 2. ANALOG INPUT SCALING (Section 4.2) 3. OPTION ANALOG INPUT (Section 4.3) 4. OPTION SETUP 1/2 (Section 4.4) 5. OPTION SETUP 2/2 (Section 4.5) 6. OPTION SELECT (Section 4.6) 1. SHOW SYSTEM SETUP (Section 10.1) 2. SHOW ANALOG INPUT SCALING (Section 10.2) 3. SHOW OPTION ANALOG INPUT (Section 10.3) 4. SHOW DIGITAL I/O STATUS (Section 10.4) 5. SHOW OPTION SETUP 1/2 (Section 10.5) 6. SHOW OPTION SETUP 2/2 (Section 10.6) 7. SHOW PROGRAM VERSION (Section 10.7) 8. READ REGISTER (Section 10.8) 9. READ BIT (Section 10.9) 0. READ TIMER/COUNTER (Section 10.10)

F2

CONTROLLER

F3

LIMITS

F4

LOGS

F5

ADJUSTMENT

F6

SETUP

F7

DIAGNOSTIC

- 10 -

QT108300

1.3 Usable Control Functions Depending on Selected Factory Options


You can use any control functions listed in the OPTION SETUP column in the table below according to your selection in the Item column if the corresponding functions in the OPTION SELECT column have been enabled for your specific CP4 before its shipment from the factory (factory option). Any setups you make is invalid if they are for those OPTION SETUP items that correspond to the disabled OPTION SELECT functions. You cannot enable any disabled OPTION SELECT functions yourself. (see Chapter 4 for details of the OPTION SELECT and OPTION SETUP windows) NOTE: In the table below, marked * in the Item column are the default selections.

Usable Control Functions


OPTION SELECT REMOTE CAPACITY CONTROL OPTION SETUP REMOTE CAPACITY CONTROL * NONE DIGITAL ANALOG CONDENSER CONTROL CONDENSER VFD CONTROL CONDENSER CONTROL TARGET CONDENSER 3STEPS CONTROL or CONDENSER 6STEPS CONTROL CONDENSER CONTROL METHOD CHILLER CONTROL CONDENSER CONTROL CONDENSER CONTROL TARGET * NOT USE USE * LOCAL DISCHARGE PRESSURE SYSTEM DISCHARGE PRESSURE * NOT USE USE * LOCAL DISCHARGE PRESSURE SYSTEM DISCHARGE PRESSURE * ON/OFF SIGNAL SET ON/OFF MULTI SET * NOT USE USE * 1 LIQUID SUPPLY SV 2 3 NONE/THERMAL EXPANSION YOSAKU 1-VALVE EXPANSION VALVES YOSAKU 2-VALVES YOSAKU 3-VALVES * 1-MOTORIZED CONTROL VALVE CHILLER CONTROL CHILLER GAS TEMP. SENSOR CHILLER ENTERING TEMP. SENSOR CHILLER LEAVING TEMP. SENSOR CHILLER LEAVING TEMP. CONTROL CHILLER PUMP MODE AUTO STAGING (Control of the number of operating compressors) VFD COMPRESSOR (Inverter control) AUTO STAGER VFD COMPRESSOR VFD COMPRESSOR OUTPUT LIMIT 2-MOTORIZED CONTROL VALVES * NO YES * NO YES * NO YES * NOT USE USE CONTINUOUS * AUTO START/STOP * NOT USE 2 UNITS - 8 UNITS * NOT USE USE * NOT USE USE Item

- 11 -

QT108300

Usable Control Functions (continued)


OPTION SELECT HIGH STAGE CAPACITY CONTROL (Control of the high stage capacity of compound type two stage compressors) OPTION SETUP * HIGH STAGE CAPACITY CONTROL * AUTO Vi CONTROL AUTO Vi CONTROL NOT USE USE NOT USE USE Y10,11,12,16,17(UD-V) USE Y19,1A,1B,1C,1D(UD-V) USE J SERIES LIQUID INJECTION OIL COOLING CONTROL * NOT USE USE NONE/THERMAL EXPANSION LIQUID INJECTION CONTROL (Oil cooling control) INJECTION VALVES * YOSAKU 1-VALVE YOSAKU 2-VALVES MOTORIZED CONTROL VALVE CONTROL TARGET HOT GAS BYPASS CONTROL STARTING BYPASS CONTROL HOT GAS BYPASS CONTROL STARTING BYPASS CONTROL ECONOMIZER/INTERCOOLER LIQUID SUPPLY CONTROL ECONOMIZER/INTERCOOLER EXPANSION VALVE CONTROL ECONOMIZER/INTERCOOLER EXPANSION VALVE CONTROL EXPANSION VALVES LEVEL CONTROL (Liquid level control) COMPRESSOR OIL SEAL CONTROL 400 SERIES COMPRESSOR CONTROL * DISCHARGE TEMPERATURE DISCHARGE SUPERHEAT * NOT USE USE * NOT USE USE * LSV & SP HSV & IP * NOT USE USE NONE * YOSAKU MOTORIZED CONTROL VALVE LEVEL CONTROL COMPRESSOR OIL SEAL CONTROL --* NOT USE USE * NOT USE USE --* LOCAL SUCTION PRESSURE --CONTROL TARGET (CUT IN/OUT) (Target of start/stop control) SYSTEM SUCTION PRESSURE CHILLER ENTERING TEMPERATURE CHILLER LEAVING TEMPERATURE * LOCAL SUCTION PRESSURE SYSTEM SUCTION PRESSURE CHILLER LEAVING TEMPERATURE COMBINED LOCAL SP/LB COMBINED SYSTEM SP/LB LOCAL DISCHARGE PRESSURE SYSTEM DISCHARGE PRESSURE Item

---

CONTROL TARGET (CAPACITY CONTROL) (Target of capacity control)

- 12 -

QT108300

Chapter 2 Components and Their Functions


2.1 Front Panel

11 12

F1

F2

F3

F4

F5

F6

F7

START

1 4

2 5 8 .

3 6

ESC SH IFT

DELETE ALT

1 2 3 5 4 6

13

ST OP

MYPRO-CP 7
CLEAR ALAR M

TAB

9 SAVE ENTER

10

7 8 9

Keys on Front Panel


No. 1 Key Function keys Function Press one of the F1 to F7 keys to display the corresponding menu. If you press the same function key while the menu is displayed, the menu will close (see Section 1.1 for the key-to-menu correspondence). Press this key to close a menu or window. Press this key in combination with an arrow key to make an up-down or right-left shift between items in the same window. (This key has no effect when pressed independently.) Press this key in combination with the TAB key to make a shift between items across different windows/windows or with the SHIFT key to make a shift between items within the same window/window (it has no effect when pressed independently). Use this key when correcting entries. Use these keys to move the cursor (in reverse video) from one item to another within a menu or window. Use this key to move the cursor (in reverse video) from an item in a window/sub-window to an item in another window/sub-window. Used to confirm a selection or entry. When confirmed by pressing this key, the selected option or entry turns red. Even when confirmed, the selection or entry is not saved in memory. Pressing this key saves selections or entries in memory. Stored in memory are the new/altered selections or entries that have been confirmed by pressing the ENTER key. The characters that have turned red by the confirmation now turn white. Use these keys to select a window in each menu or make entries in each window.

2 3 4

ESC key SHIFT key ALT key

5 6 7 8

DELETE key Arrow keys TAB key ENTER key

SAVE key

10

Numeric keys

- 13 -

QT108300

Keys on Front Panel (continued)


No. 11 Key START key Function Used to start the compressor only when the LOCAL mode (operation control mode) is selected. This key does not work in the REMOTE, COMM, or AUTO STAGE mode (see Section 6.1). This key can be used to stop the compressor regardless of the operation mode selected (see CAUTION below). Use this key to clear an alarm if the compressor has stopped by issuance of an alarm (FAILURE).

12 13

STOP key CLEAR ALARM key

According to the selection for the OPERATION item in the OPERATION MODE window, the following conditions automatically take place when the STOP key is pressed on the front panel of PC4. When the LOCAL, REMOTE, or COMM mode (not the AUTO STAGE mode) has been selected, pressing the STOP key causes no change to the operation control mode in the case of the LOCAL mode, but the mode automatically changes to LOCAL in the case of the REMOTE and COMM modes. The compressor, if operating, will then stop after the liquid recovering sequence. (It remains stopped thereafter.) To restart the compressor, simply press the START key if you need not change the mode from LOCAL to another, or turn ON the relevant operation control command after changing the mode from LOCAL to the desired mode. When the AUTO STAGE mode has been selected, pressing the STOP key does not cause any change to the setting for the OPERATION item in the OPERATION MODE window, but the selection of ENABLE you made for the CONTROL item in the AUTO STAGE window automatically changes to DISABLE. In this case, if the compressor under control is running when the STOP key is pressed, the compressor will then stop after completing the liquid recovering sequence. Even the STOP key is pressed on the master station and its CONTROL item setting in the AUTO STAGE window is consequently changed to DISABLE, the automatic staging control continues to work on all the other stations (slave stations). To recover the AUTO STAGE mode control after pressing the STOP key, it is necessary (for the case of the master station and the case of a slave station) to perform the steps below. (Simply pressing the START key on the station does not recover the automatic staging control.) 1. From the SETPOINTS menu (F1), open the AUTO STAGE window. 2. Select ENABLE for the CONTROL item in the window.

- 14 -

QT108300

2.2 Parts on CPU Board (REF-CX100-PR01)


17 16 4 1 18 19 20 15 14 21 11 6 12 22 25 8 24 26 10 9 23 13 5 7 3 2

The above figure shows the CPU board used in CP4 and the locations of the circuit boards, switches, connectors, and other parts on it. These parts are explained in the following table.

Parts on CPU Boards


No. 1 2 3 4 5 6 Parts Analog input board connector LCD board connector ROM board connector DC (5V) board connector Extension communication board connector Digital input/output drive connector Function Used to connect the two different analog input boards to the CPU board. (Use cable REF-CX100-C1201-U for connection.) Used to connect the LCD interface board to the CPU board. (Use cable REF-CX100-C0901-U for connection.) Used to connect the ROM board to the CPU board. Used to supply 5 V DC from the CPU circuit power supply to the CPU board. (Use cable REF-CX100-C0312-U for connection.) Used to connect an extension communication board (option) to the CPU board. Used to connect digital input/output drive boards. The connectors are provided on the CPU board and can accommodate a maximum of four digital input/output drive boards (16 inputs/outputs). The #1 connector is for switch inputs/outputs 1 to 4, #2 for digital inputs/outputs 5 to 8, #3 for switch inputs/outputs 9 to 12, and #4 for switch inputs/outputs 13 to 16. Used to connect the KP board to the CPU board. (Use cable REF-CX100-C1000-U for connection.) Used to supply power from the CPU board power supply to an extension communication board (option). (Use cable REF-CX100-C0100-U for connection.) Used to connect a digital input/output driver base (DB) board (option) to the CPU board. Used to supply power from the CPU board power supply to the connected DB board (option). (Use cable REF-CX100-C0100-U for connection.) Used to supply 12 V DC from the power supply of the analog/digital and digital input/output circuits to the CPU board. (Use cable REF-CX100-C0322-U for connection.) Used to connect the digital input/output board to the CPU board with a cable. (Use cable REF-CX100-C1301-U for connection.)

7 8

KP board connector Communication power connector DB board connector DB board power connector DC (12V) connector

9 10

11

12

Digital input/output board connector

- 15 -

QT108300

Parts on CPU Boards (continued)


No. 13 14 15 16 17 Parts Analog output board connector Extension AD board connector Analog/digital board power connector Battery holder Reset switch Function Used to connect an analog output board (option) to the CPU board. Used to connect an extension AD converter board (option) to the CPU board. Used to supply power from the CPU board to an extension analog/digital board (option). (Use cable REF-CX100-C0100-U for connection.) Used to hold the memory backup battery (lithium primary cell CR2032). Used to reset CP4 system.

Operate the reset switch carefully.

18 19

CPU lamp DIP switch

Blinks red at regular intervals while the CPU is running normally. The top switch is numbered 1 and the bottom one is numbered 8. Slide each switch to the right to set it to ON.

Slide each switch until it clicks.

20

Input selector switch for CH 15 and CH 16

Used to switch between terminal blocks 15A and 15B for analog input CH15 and between 16A and 16B for analog input CH16.(15B and 16B are selected by default.) Moving the switch to the right selects terminal block 15A/16A, and moving it to the left selects terminal block 15B/16B.

Move the switch until it clicks.

21

Heat sink

The heat sink is hot. Do not touch it by hand.

22 23

COM 0 operation lamp COM 1 terminal block

Lights green during transmission; lights red during reception. Provides terminals for 4-wire RS-485 communication ports.

- 16 -

QT108300

Parts on CPU Boards (continued)


No. 24 Parts COM 1 terminating resistor switches Function These switches turn ON/OFF the terminating resistors in the CPU board. They provides termination for the transmission and receiving lines independently. Move the switch up to turn ON the terminating resister.

Move the switch until it clicks.

25 26

COM 1 operation lamp COM 0 connector

Lights green during transmission; lights red during reception. Provides RS-232C Communication Ports. For setting for the ports, see Section 5.8 Adjustments in COMMUNICATION SETUP Window (Option 8 of ADJUSTMENT Menu (F5)).

2.2.1

Reset Switch on CPU Board

CP4 requires system resetting if the stored setting data is lost or before newly setting up the system. There are the following two methods for the system resetting. Hardware resetting method Software resetting method This section explains the hardware method. (For the software method, see Section 3.4 Software Resetting Method.)

The reset switch is in the location encircled in the above figure. Press and release the switch to reset CP4. CP4 will be rebooted (but the system is not set up by simply pressing this switch). The system can also be reset by turning OFF and then ON the CP4 power supply.

Resetting CP4 brings the controller in a momentary instable condition, following which CP4 is placed in a condition that would result just after turning power ON. As this condition is detrimental to the compressor unit if it occurs during operation, never perform system resetting while the compressor and accessory is in operation.

- 17 -

QT108300

2.2.2

Replacement of Memory Backup Battery on CPU Board

CP4 uses a primary cell as a power source to retain the setting data and keep driving the internal clock in the event of a power failure. The battery can supply power enough to back up the memory of setting data for about three years. The battery starts running down immediately after it is produced even if it is not used. If power failure occurs when the battery is completely discharged, all data including the setting and log data will be lost and the internal clock will be reset to zero. NOTE: The battery life may be shorter than three years in high-temperature or other unfavorable environments. To prevent this kind of problem, CP4 has a low battery detection function. If a low battery condition is detected, this function causes the BATTERY ALARM message to blink at the center of the top line in both status display screens (see Section 3.1 Display Screens).

If the BATTERY ALARM message is blinking, replace the battery immediately. If the CPU is reset following such an operation as turning on the power supply with the internal battery discharged, PC4 will automatically be restarted by special booting for the sake of safety. Once this has occurred, the compressor cannot be operated any further unless the memory backup battery is replaced with a battery of the normal voltage (see Section 3.5 Special Booting).

The memory backup battery can be replaced regardless of whether the system is under power or not. The setting data are not lost as long as the battery is replaced while the system is under power. However, if the battery is replaced while power is out, all stored setting data are lost and the internal clock is initialized. Use the following method to replace the internal battery.

Do this operation carefully not to let the battery touch any of the nearby components.

(1)

Insert your fingernail into the part indicated by the arrow and, while holding the old battery by its top and bottom, disengage only the clip on the left side of the holder. Now the battery is free for removal. Be sure to hold the battery; otherwise, it will drop from the board when the clip is released.

(The right figure shows the holder after removal of the battery.)

- 18 -

QT108300

(2)

While holding a new battery by its top and bottom, engage the battery with the clip (indicated by the arrow) at the right part in the holder. (The right figure shows the battery engaged with the clips. You should still keep holding the battery as it can drop out of the board if it is released.)

(3) (4)

Set the battery into its horizontal position in the holder. Lightly press the part indicated by the arrow to fit the battery snugly into position in the holder.

2.3 EPROM Board (REF-CX100-RM01)


The EPROM board to be installed on the CPU board has the following connector and sockets.

2 1 3

NOTE: The 32-megabit EPROM (software-written circuit board) is installed on the standard version. (The 40-pin socket for 4-megabit ROM is not used.)

Parts on EPROM Board


No. 1 2 Parts ROM board connector 40-pin socket for 4-megabit ROM Function Used to connect the ROM board to the CPU board. The connector is provided on the back of the CPU board. This socket is for mounting a programmable ROM circuit board. Mount the ROM board with the recess facing up. A ROM equivalent to 27C4002 (4 megabits) is connectable to this socket. (The use of an ST Micro M27C4002-12F1 is recommended.)

Mount/demount the ROM board carefully.

- 19 -

QT108300

Parts on EPROM Board (continued)


No. 3 Parts 42-pin socket for 32-megabit EPROM Function This socket is for mounting a programmable ROM circuit board. Mount the ROM board with the recess facing up. An EPROM equivalent to 27C322 (32 megabits) is connectable to this socket. (The use of an ST Micro M27C322-100F1 is recommended.)

Mount/demount the ROM board carefully.

2.3.1

Replacement of EPROM on CPU Board

Follow the procedure below when replacing (updating) the EPROM (software-written circuit). (1) (2) (3) (4) Take a note of the settings and other data. (This step may be not necessary depending on the type of the EPROM to be replaced.) Turn off the power supply of CP4. Check that the CPU lamp on the CPU board is OFF. (This is necessary to make sure the power supply has been turned off.) Using an EPROM extractor, remove the EPROM carefully from the ROM board.

Do not pry the EPROM using a flat head screwdriver or a similar tool; this may damage the ROM board.

(5)

Connect a new EPROM to the IC socket on the left side (as viewed from the front), with the recess facing upward (see the figure below).

Incorrect connection can cause an operational failure.

(6)

Reconfirm that the EPROM is installed correctly.

- 20 -

QT108300

(7)

Turn on the power supply of CP4. (According to the condition, CP4 may need to be initialized.) Insert the EPROM while aligning its recess with the recess in the IC socket.

Not used

2.4 Analog Input Boards (REF-CX100-AI01, REF-CX100-AI11)


The analog input boards for installation on the CPU board have the following terminal blocks and connectors. 4 (CH1 to CH3) 4 (CH4 to CH6) 4 (CH7 to CH9)

MYPRO-CPIV Ver.A.BC

3 1 2 2

4 (CH16A - CH16B) 4 (CH13 - CH15A) 4 (CH10 - CH12)

3 1 2 2

Parts on Analog Input Boards


No. 1 Name Analog input board connector 24 V DC connectors Function The connector on each analog input board is used to connect it to the CPU board. The connector is a 20-pin connector for both analog input boards. (Use cable REF-CX100-C1201-U for connection.) Used to connect 24 V DC from the analog input/output circuit power supply to the analog input board. (Use cable REF-CX100-C0401-U for connection; use cable REF-CX100-C0501-U for connection between the AI01 and AI11 boards.)

- 21 -

QT108300

Parts on Analog Input Boards (continued)


No. 3 Name Function Current/voltage selector Each of these switches selects either voltage or current for analog inputs. switches (JP1 to 9 and JP1 Set each switch to ON for current input or OFF for voltage input. (All of these switches are to 7) for analog inputs defaulted to OFF.)

Move the switch to each position until it clicks.

Analog input terminal blocks

Used to connect analog input wires. Each terminal block can supply sensors with power (although the power level is limited). Either current/voltage input or potentiometer input is selectable for CH15 and CH16. CH15A and CH16A are assigned to current/voltage inputs. CH15B is assigned to low-stage potentiometer inputs, and CH16B is assigned to high-stage potentiometer inputs. To use CH15 and CH16, connect desired input lines to the corresponding terminal blocks and then set the current/voltage selector switches for on the CPU board CH 15 and CH 16 as appropriate (see Section 2.2).

NOTE: Use also the above analog input boards when adding analog input channels (AD CH17 to CH32).

2.4.1

Current / Voltage Selection and Terminal Block Connections for Analog Input Boards

Set switches JP1 to JP9 (for CH1 to CH9) and switches JP1 to JP7 (for CH10 to CH14, CH15A, and CH16A) on the associated analog input boards to ON when the analog input sources provide current signals. Set these switches to OFF for voltage signal inputs. The analog input circuits (internal circuit of CP4) are schematically shown below. Analog input boards

Internal circuits of CP4

24V

Current/voltage selector switch

1 2 3 4

24V 1+ 1FG FG Input filter circuit 250 To A/D converter circuit

AG

When the current/voltage selector switch is set to ON, a 250-ohm resistor is connected to the input circuit as shown in the above diagram. DC current signals of 4 to 20 mA are then converted into 1 to 5 V DC voltage signals before being input to the analog-to-digital (A/D) converter circuit. When the selector switch is set to OFF, the current signals are input directly to the A/D converter circuit. Make connections on each terminal block as follows: - 22 -

QT108300

- Current signal sources using CP4s power supply: Connect + side of the input source to the 24V terminal of the terminal block and the - side to an appropriate one of the + terminals 1 to 16 on the terminal block. - Current signal sources using an outside power supply: Connect the + side of the input source to an appropriate one of the + terminals 1 to 16 on the terminal block and the - side to an appropriate one of the - terminals 1 to 16 on the terminal block. - Voltage signal sources: Connect the + side of the input source to an appropriate one of the + terminals 1 to 16 on the terminal block and the - side to an appropriate one of the - terminals 1 to 16 on the terminal block.

Move the switch until it clicks.

NOTE: The switch is set to OFF before shipment from the factory.

2.4.2

Input Type Selection for Channels 15 and 16 of Analog Input Boards

Like with the Mayekawas controller MYPRO-CPIII, CP4 has a means for setting the analog input channels 15 and 16 (CH15 and CH16) for receiving current/voltage inputs or potentiometer inputs. When the lever of the analog input selector switch marked JP3 on the CPU board is moved to the 15A side, Channel 15 is set for receiving current/voltage inputs (analog input terminal block CH15A is enabled). When the lever is moved to the 15B side, Channel 15 is set for receiving potentiometer inputs (analog input terminal block CH15B is enabled). The same applies to Channel 16 although the switch number and terminal board designations are different accordingly (see NOTE under the table below). The diagram below shows the analog-to-digital (A/D) converter circuit (internal circuit of CP4) to schematically depict the above explanation taking Channel 15 for example.

Current/voltage inputs CH15A from analog input board Potentiometer inputs CH15B from analog input board

CPU board

15A

Analog-todigital converter circuit

Potentiometer converter circuit

15B

Analog input selector switch JP3

- 23 -

QT108300

Selection of Input Source Type for Channel 15 (in the case of position inputs for low-stage unloader slide valve)
Input Source Potentiometer Current input source with power supplied from CP4 Current input source with power supplied from outside Voltage input source Connection Potentiometer inputs 1 to 3 are connected to terminals LF1 to LF3 of terminal block CH15B on analog input board. Connect + side to terminal 24V on CH15A terminal block of analog input board, and - side to terminal15A+. Connect + side of input to terminal 15A+ on CH15A terminal block of analog input board, and - side to terminal 15A-. Connect + side of input to terminal 15A+ on CH15A terminal block of analog input board, and - side to terminal 15A-. JP6 switch position on analog input board Any position ON ON OFF JP3 switch position on CPU board 15B 15A 15A 15A

NOTE: The above table also applies to selection of analog input type for channel 16 if channel number 15 is read as 16, switch number JP6 of the AI board as JP7, and switch number JP3 of CPU board as JP4.

Move the switch lever until it clicks.

2.5 Optional Analog Output Board (REF-CX100-DA01)


1 3 2

Parts on Analog Output Board


No. 1 2 Name Analog output board connector 24 V DC connector Function Used to connect this analog output board to the CPU board. The CPU boards connector is located on its back. Used to supply 24 V DC from the analog input/output circuit power supply to this analog output board. (Use cable REF-CX100-C0322-U for connection.) The trimming data (output adjustment data) for the analog section of the analog output circuit is written in a non-volatile memory. As each analog output board has this data memory, re-trimming is not necessary even if an analog output board is added or replaced. Used to connect wires for analog outputs (4 to 20 mA DC).

Trimming data memory

Analog output terminal block

- 24 -

QT108300

2.6 Optional Digital Input/Output Drive Base (DB) Board (REF-CX100-DB01)


2 3 1

5 4 6

Parts on Optional Digital Input/Output DB Board


No. 1 2 Name DB board connector 12 V DC connector Function Used to connect this DB board to the CPU board. Used to supply 12 V DC from AD digital input/output circuit power supply via the CPU board. (Use cable REF-CX100-C0100-U for connection.) Used to connect digital input/output driver (DIOD) boards. Connectors for four DIOD boards (16 terminals) are provided on this DB board. The #1 connector corresponds to I/O terminals 17 to 20, the #2 connector corresponds to I/O terminals 21 to 24, and so on. DIOD boards for connection to the connectors are as follows: #1 : REF-MCS200-SO* (4 outputs) #2 : REF-MCS200-SO* (4 outputs) #3 : REF-MCS200-SO* (4 outputs) #4 : REF-MCS200-SC2* (2 outputs and 2 inputs) (* indicates a revision number.) Used to set the ID (station number) of the DB board.

DIO driver connectors

Rotary switch

Do not move the switch from position 1.

Digital input/output board connector Reserved

Used to connect a digital input/output board and DB board with a cable. Digital input/output boards and cables used are the same as those for the CPU board. (Use cable REF-CX100-C1301-U for connection.) Currently not used

- 25 -

QT108300

2.7 Digital Input/Output Board (REF-MCS200-OIA0, REF-MCS200-OIE0 (Optional))


1 3 REF-MCS200-OIA0 4 5 6, 7 8 9 10 2 REF-MCS200-OIE0 (optional) 4 5

Parts on Digital Input/Output Board


No. 1 Name Digital input/output board connector Function Used to connect an optional DB board to the CPU board or to a digital input/output board using a cable. (Use cable REF-CX100-C1301-U for connection.) Digital input/output terminal Used to connect digital input/output wires. block Terminals 1A and 1B correspond to digital input/output CH 1; terminals 16A and 16B correspond to digital input/output CH 16. Digital input/output lamp Indicates whether digital input/output is ON or OFF (goes on when input/output is ON and goes off when input/output is OFF). LED 1 corresponds to digital input/output CH1; LED 16 corresponds to digital input/output CH16. Digital output circuit On the REF-MCS200-0IA0 board, digital input/output channels CH1 to CH10 are assigned to digital outputs. On the REF-MCS200-0IE0 board (option), digital input/output channels CH1 to CH14 are assigned to digital outputs (switch outputs). Digital input circuit On the REF-MCS200-0IA0 board, digital input/output channels CH11 to CH16 are assigned to digital inputs. On the REF-MCS200-0IE0 board (option), digital input/output channels CH15 and CH16 are assigned to digital inputs. Relay sockets These relay sockets provided for digital outputs allow the use of mechanical relays or solid state relays. Relay The following relays are usable. Mechanical relay: OMRON G6B-1114P-US, 12 V DC (rated output load: 5A at 250 V AC/30 V DC) Solid state relay: G3S-201PL-PD-US, 12 V DC (rated output load: 1.2 A at 100 to 240 V AC) TNR (ceramic variable Provided to protect contacts of the relays. resistor) Circuit protector Provided to protect the relays from overcurrent. Output is interrupted if current exceeding 1 A flows through relay contacts. Remove the overcurrent condition first and then push in the white knob of the circuit protector to recover relay outputs.

6 7

8 9

- 26 -

QT108300

Parts on Digital Input/Output Board (continued)


No. 10 Name Frame ground (FG) terminal Function Provided to keep continuity between ground (terminal) and the printed circuit board.

Securely connect the FG terminal to ground (terminal); otherwise, the digital input/output board does not work normally.

NOTE: This digital input/output board is not installed on the back surface of the MYPRO-CPIV Control Panel.

2.8 Optional Communication Board (REF-CX100-RS01)


1

5 7

3 6 4

Parts on Optical Communication Board


No. 1 2 3 Name Function Extension Communication Used to connect this optional extension communication board to the CPU board. board connector COM2 and COM3 lamps Left lamp is for COM2 port and right lamp is for COM3 port. Each lamp lights green during transmission and lights red during reception. Communication power Used to supply power from CPU board power supply to this extension communication supply connector board. (Use cable REF-CX100-C0100-U for connection.) COM2 terminal block Terminal block for 4-wire RS-485 communication ports COM2 terminating switch Used to terminate the transmission and receiving line independently. Moving the switch up terminates the line.

4 5

Move the switch until it clicks.

COM3 terminal block

Terminal block for 4-wire RS-485 communication ports

- 27 -

QT108300

Parts on Optical Communication Board (continued)


No. 7 Name COM3 terminating switch Function Used to terminate transmission and receiving lines independently. Moving the switch up terminates the line.

Move the switch until it clicks.

2.9 Optional Analog-to-Digital (AD) Converter Board (REF-CX100-AD01)


2

3 4 1

Parts on Optical AD Converter Board


No. 1 2 Name Extension AD converter board connector Analog input board connector Input selector switch for CH15 and CH16 Function Used to connect this extension AD converter board to the CPU board. Used to connect the two types of analog input board and the AD converter board like with the CPU board. (Use cable REF-CX100-C1201-U for connection.) This switch is used to switch analog input between 15A and 15B terminal boards and between 16A and 16B terminal boards. Moving the switch to the right selects 15A or 16A; moving it to the left selects 15B or 16B.

Move the switch until it clicks.

AD board power supply connector

Used to supply power from the CPU board to this AD converter board. (Use cable REF-CX100-C0100-U for connection.)

- 28 -

QT108300

Chapter 3 Operation
3.1 Display Screens
CP4 has two types of status display screen: the Main Graphic Screen and Main Status Screen. You can swap these screens by pressing the TAB key while no function menu and windows are displayed.

3.1.1

Acronyms and Abbreviations Used for Indicated Items

In these two screens, the indicated items are represented using the acronyms and abbreviations shown in the following tables. The tables also show the channel numbers for analog and digital inputs and outputs. For digital input/output channel numbers, their aliases are also shown.

Real analog inputs


Acronym SP DP OP AFP ST DT OT OS AFFP IP IT SDP LVL MA EBT LBT LSV HSV SSP SVOP PSV SP1 GT1 RLD SP2 GT2 OPT1 OPT2 OPT3 OPT4 Full Spelling SUCTION PRESSURE DISCHARGE PRESSURE OIL SUPPLY PRESSURE AFTER FILTER PRESSURE SUCTION TEMPERATURE DISCHARGE TEMPERATURE OIL SUPPLY TEMPERATURE OIL SEPARETER TEMPERATURE AFTER FINE FILTER PRESSURE IMTERMEDIATE PRESSURE INTERMEDIATE TEMPERTURE SYSTEM DISCHARGE PRESSURE LIQUID LEVEL MOTOR ELECTRIC CURRENT ENTERING BRINE TEMPERATURE LEAVING BRINE TEMPERATURE (LOW STAGE) SLIDE VALVE POSITION HIGH STAGE SLIDE VALVE POSITION SYTEM SUCTION PRESURE SLIDE VALVE OIL SUPPLY PRESSURE Vi PORT SLIDE VALVE POSITION SUCTION PRESSURE1 CHILLER GAS TEMPERATURE1 REMOTE CAPACITY CONTROL TARGET SUCTION PRESSURE2 CHILLER GAS TEMPERATURE2 OPTION ANALOG INPUT 1/4 OPTION ANALOG INPUT 2/4 OPTION ANALOG INPUT 2/4 OPTION ANALOG INPUT 4/4 Input Channel No. AI 1 AI 2 AI 3 AI 4 AI 5 AI 6 AI 7 AI 8 AI 8 AI 9 AI10 AI11 AI11 AI12 AI13 AI14 AI15 AI16 AI16 or AI19 AI16 AI16 AI17 AI18 AI20 AI25 AI26 AI8, AI9, AI10, AI11, AI13, AI14, AI21, AI22, AI23 or AI24 AI8, AI9, AI10, AI11, AI13, AI14, AI21, AI22, AI23 or AI24 AI8, AI9, AI10, AI11, AI13, AI14, AI21, AI22, AI23 or AI24 AI8, AI9, AI10, AI11, AI13, AI14, AI21, AI22, AI23 or AI24

- 29 -

QT108300

Virtual analog inputs (derived from real analog inputs through calculation)
Acronym OP FP P SSH ISH DSH D/S Vi CRVi CAP SVP ATP OP2 SH2 FFP N.C. Full Spelling OIL DIFFERENTIAL PRESSURE FILTER DIFFERENTIAL PRESSURE DIFFERENTIAL PRESSURE SUCTION SUPERHEAT INTERMEDIATE SUPERHEAT DISCHARGE SUPERHEAT DISCHARGE/SUCTION PRESSURE RATIO CALCULATED Vi CURRENT Vi COMPRESSOR CAPACITY SLIDE VALVE PERCENTAGE AUTO STAGE TARGET PRESSURE OIL DIFFERENTIAL PRESSURE2 SUCTION SUPERHEAT2 FINE FILTER DIFFERENTIAL PRESSURE NOT CONNECTED AI65 AI66 AI67 AI68 AI69 AI70 AI71 AI72 AI73 AI74 AI75 AI76 AI77 AI78 AI79 Assigned Input Channel No.

Digital inputs/outputs
Acronym COMP OILP I/CS LOAD UNLD HILD INJS HIUL INJY OILH EVPS ViBP ViLD OILD OILF OILR ViUL FAIL EMGC MSRB ITL1 ITL2 ITL3 RMST MPLD EVPY MPUL CHLP SVBP SBYP HBYP I/CY O/P2 ALRM EVS2 LHLD EVY2 LHUL CND1 AUX Full Spelling COMPRESSOR OILPUMP LIQUID SUPPLY SOLENOID VALVE for ECONOMIZER/INTERCOOLER (LOW STAGE) LOADING SOLENOID VALVE (LOW STAGE) UNLOADING SOLENOID VALVE HIGH STAGE LOADING SOLENOID VALVE LIQUID SUPPLY SOLENOID VALVE for LIQUID INJECTION HIGH STAGE UNLOADING SOLENOID VALVE YOSAKU EXPANSION VALVE for LIQUID INJECTION OIL HEATER LIQUID SUPPLY SOLENOID VALVE for CHILLER BYPASS SOLENOID VALVE for Vi PORT LOADING SOLENOID VALVE for Vi PORT OIL DRAIN SOLENOID VALVE OIL FEED SOLENOID VALVE OIL RETURN SOLENOID VALVE UNLOADING SOLENOID VALVE for Vi PORT FAILURE EMERGENCY STOP MAIN STARTER READ BACK INTERLOCK-1 INTERLOCK-2 INTERLOCK-3 REMOTE START INPUT LOADING SOLENOID VALVE for PORT-M YOSAKU EXPANSION VALVE for CHILLER UNLOADING SOLENOID VALVE for PORT-M CHILLER PUMP BYPASS SOLENOID VALVE for Vi SLIDE VALVE BYPASS SOLENOID VALVE for STARTING BYPASS SOLENOID VALVE for HOT GAS YOSAKU EXPANSION VALVE for ECONOMIZER/INTERCOOLER OIL PUMP2 ALARM LIQUID SUPPLY SOLENOID VALVE2 for CHILLER LOADING SOLENOID VALVE for PORT-L/H YOSAKU EXPANSION VALVE2 for CHILLER UNLOADING SOLENOID VALVE for PORT-L/H OUTPUT1 for CONDENSER(VFD) AUXILIARY - 30 Input/Output Cannel No. DO1 DO2 or DO20 DO2 or DO8 DO3 DO4 DO5 DO5 DO6 DO6 DO7 DO7 or DO17 DO7 DO8 DO9 DO9 DO9 DO9 DO10 DI11 DI12 DI13 DI14 DI15 DI16 DO17 or DO26 DO18 DO18 or DO27 DO19 DO19 DO20 or DO28 DO20 DO21 DO21 DO22 DO23 DO23 or DO29 DO24 DO24 or DO30 DO25 DO25 Alias Y0 Y 1 or Y13 Y 1 or Y 7 Y2 Y3 Y4 Y4 Y5 Y5 Y6 Y 6 or Y10 Y6 Y7 Y8 Y8 Y8 Y8 Y9 XA XB XC XD XE XF Y10 or Y19 Y11 Y11 or Y1A Y12 Y12 Y13 or Y1B Y13 Y14 Y14 Y15 Y16 Y16 or Y1C Y17 Y17 or Y1D Y18 Y18

QT108300

Digital inputs/outputs (continued)


Acronym CND2 CND3 CND4 IJY2 CND5 EVS3 CND6 EVY3 RMLD RMUL Full Spelling OUTPUT2 for CONDENSER OUTPUT3 for CONDENSER OUTPUT4 for CONDENSER YOSAKU EXPANSION VALVE2 for LIQUID INJECTION OUTPUT5 for CONDENSER LIQUID SUPPLY SOLENOID VALVE3 for CHILLER OUTPUT6 for CONDENSER YOSAKU EXPANSION VALVE3 for CHILLER REMOTE LOAD INPUT REMOTE UNLOAD INPUT DO26 DO27 DO28 DO28 DO29 DO29 DO30 DO30 DI31 DI32 Input/Output Cannel No. Alias Y19 Y1A Y1B Y1B Y1C Y1C Y1D Y1D X1E X1F

PID controller
Acronym LSV P LSV T SCTSH SPLMT LBLMT INTSH INJCT LVGBT CNDNS HI SV VFD P VFD T SCSH2 SP2LM LEVEL SV MV Full Spelling (LOW STAGE) SLIDE VALVE on PRESSURE (LOW STAGE) SLIDE VALVE on CHILLER LEAVING BRINE TEMPERATURE CHILLER EXPANSION VALVE on SUCTION SUPERHEAT LIMIT on SUCTION PRESSURE for CHILLER EXPANSIN VALVE LIMIT on CHILLER LEAVING BRINE TEMPERATURE for CHILLER EXPANSIN VALVE ECONOMIZER/INTERCOOLER EXPANSION VALVE on INTERMEDIATE SUPERHEAT LIQUID INJECTION FLOW CONTROL VALVE on CHILLER LEAVING BRINE TEMPERATURE VFD CONDENSER FAN HIGH STAGE SLIDE VALVE on INTERMEDIATE PRESSURE VFD COMPRESSOR on PRESSURE VFD COMPRESSOR on CHILLER LEAVING BRINE TEMPERATURE CHILLER EXPANSION VALVE2 on SUCTION SUPERHEAT2 LIMIT on SUCTION PRESSURE2 for CHILLER EXPANSIN VALVE2 LEVEL SET VALUE MANIPULATION VALUE

Others
Acronym A/O, AO AI C7 C8 CH. COM, COMM COMP. CTRL D/O ECONO. EXP.VALVE H.SLIDE VALVE HI HRS HSV I/O INTER L.SLIDE VALVE LB LO MV MVH MVL OIL P. P. ANALOG OUTPUT ANALOG INPUT CHARACTER BIT 7 CHARACTER BIT 8 CHANNEL COMMUNICATION COMPRESSOR CONTROL DIGITAL OUTPUT ECONOMIZER/INTER COOLER EXPANSION VALVE HIGH STAGE SLIDE VALVE HIGH HOURS HIGH STAGE SLIDE VALVE POSITION INPUT/OUTPUT INTERMEDIATE LOW STAGE SLIDE VALVE CHILLER LEAVING BRINE TEMPERATURE LOW MANIPURATING VALUE MANIPULATING VALUE HIGH LIMIT MANIPULATING VALUE LOW LIMIT OIL PUMP PAGE - 31 Full Spelling

QT108300

Others (continued)
Acronym PE PN PO PRES. PRESS. S1 S2 SETPT SH SP SV TEMP VFD W/ W/O Full Spelling EVEN PARITY NON PARITY ODD PARITY PRESSURE PRESSURE STOP BIT 1 STOP BIT 2 SET POINT SUPERHEAT SUCTION PRESSURE SLIDE VALVE POSITION or SOLENOID VALVE TEMPERATURE VARIABLE FREQUNCY DRIVE WITH WITHOUT

3.1.2

Main Graphic Screen

The Main Graphic Screen shows the compressors current status using graphics. Colors and symbols help you to check the compressors operating conditions and alarms. The Main Graphic Screen has priority over the Main Status Screen, the other compressor status screen. To select the Main Status Screen, press the TAB key when no function menu or window is displayed.

Title block Warning display

DATE Low battery alarm Status display

Timer ALARM/FAILURE display Function menu display

Colors and symbols are used as follows: Refrigerating system and oil pump in operation: Displayed in green. Refrigerating system and oil pump not in operation: Displayed in gray. Refrigerating system automatically stopped: Displayed in red. In FAILURE (critical failure) condition: Indicated by a blinking In ALARM (non-critical failure) condition: Indicated by a blinking symbol. symbol.

- 32 -

QT108300

If a low battery alarm BATTERY ALARM is displayed showing that the memory backup battery is discharged, replace the battery immediately (see Section 2.2.2 Replacement of Memory Backup Battery on CPU Board). If the CPU is reset following such an operation as turning on the power supply with the internal battery discharged, PC4 will automatically be restarted by special booting for the sake of safety. Once this has occurred, the compressor cannot be operated any further unless the memory backup battery is replaced with a battery of the normal voltage (see Section 3.5 Special Booting).

3.1.3

Main Status Screen

The Main Status Screen shows the current status related to operation of the compressor unit using letters and numeric values. To change the display to the Main Graphics Screen, press the TAB key when no function menu or window is displayed.

1 3

2 9 5

6 7 8

Display of Main Status Screen


No. 1 2 3 4 Name Title block DATE OPERATION MODE window CAPACITY CONTROL window MAIN STATUS window COMMUNICATION window Function Displays controllers name. Displays current date and time. Also indicates panel inside temperature. Displays current operation control mode, compressor status, and operation start/stop settings. Displays current status of capacity control. This window also gives an indication if increase of the compressors capacity is prohibited or it is forcedly reduced. Displays current values of individual analog inputs, calculated values derived from analog inputs, total operating time count, and days operating time count. Displays current communication status.

5 6

- 33 -

QT108300

Display of Main Status Screen (continued)


No. 7 Name ALARM/FAILURE display area Function Displays currently issued alarms. The alarms cannot be cleared unless the ALARM CLEAR key is pressed (certain alarms cannot be cleared by the ALARM CLEAR key.). This field is blank if no alarm is issued. (see Section 7.1 Settings in ALARM/FAILURE Windows 1/3 to 3/3) Displays function menus corresponding to function keys (F1 to F7). (see Section 1.2 Menu-Window Organization (Menu Tree)) Displays BATTERY ALARM warning when the memory backup battery is discharged.

8 9

Function display area Low battery alarm

If the low battery alarm BATTERY ALARM is displayed, replace the memory backup battery immediately.

OPERATION MODE window


The OPERATION MODE window indicates the current selections and states concerning the operation control mode and other items related to control of the compressor.

Items of OPERATION MODE Window


Item D/O TEST OPERATION (Manual operation (see Section 6.2)) Selection/State NO YES LOCAL MODE (Operation control mode (see Section 6.1)) REMOTE COMM STAGE NO AUTO START/STOP (Automatic operation (see Section 6.1)) YES STG STOP ANTI CYCLE AUTO STOP CUT IN SYSTEM START OIL PUMP START START RUN CUT OUT PUMP OUT -ON -OFF -ON -OFF -ON -OFF -ON -OFF Description D/O TEST OPERATION is disabled (automatic operation is possible). D/O TEST OPERATION is enabled (automatic operation is impossible). START and STOP keys on the front panel are used to start and stop the compressor. Compressor starts/stops according to the remote start/stop inputs at DI-16. Compressor starts/stops according to commands given by a remote device through communications. Compressor starts/stops according to the automatic staging (AUTO STAGE) control (option). (see Section 6.7) Automatic start/stop control of the compressor according to the set values is disabled. Automatic start/stop control of the compressor according to the set values is enabled. Automatic start/stop control according to the automatic staging (AUTO STAGE) control (option) is enabled. Compressor is stopped. Compressor is in anti-cycle state. Compressor is automatically stopped. Operation sequence of compressor is started. System is being activated. Oil pump is started. Compressor is being started. Compressor is running. Stop control sequence is started. Liquid recovery is in progress.

COMP STATE (Compressor state)

- 34 -

QT108300

Items of OPERATION MODE Window (continued)


Item CUT IN (Operation start pressure) CUT OUT (Operation stop pressure) SCHEDULE (Schedule No.) SETPOINT (Set point No.) Selection/State Pressure or temperature Description Indicates current setting for the start (CUT IN) pressure/temperature. This item also indicates new setting resulting from switching/change made to SCHEDULE (see Section 6.4) or COMM (see Section 6.1). Indicates current setting for the stop (CUT OUT) pressure/temperature. This line also indicates new setting resulting from switching/change made to SCHEDULE (see Section 6.4) or COMM (see Section 6.1). Displays current SCHEDULE No. (see Section 6.4). Displays current SETPOINT No. (see Section 6.4).

Pressure or temperature 1 to 7 1 to 4

CAPACITY CONTROL window


This window displays the current states of the capacity control.

Items of CAPACITY CONTROL Window


Item SETPOINT (Capacity control set value) PID OUT (Capacity controller output) Status Pressure or temperature % rpm LOAD STATE (Capacity control state) UNLOAD LIMIT UNLOAD DP (Discharge pressure limiter) SP (Suction pressure limiter) IP (Intermediate pressure limiter) NOTE: - If a limiter is activated, the capacity control is limited even when the control target pressure or temperature is higher than the capacity control set value (SETPOINT). - When a limiter is activated, words LIMIT and UNLOAD are displayed in white. When the limiter is deactivated, they are displayed in gray. LIMIT UNLOAD LIMIT UNLOAD LIMIT UNLOAD Description Indicates the current set value for capacity control. This item also indicates new setting resulting from switching/change made to SCHEDULE (see Section 6.4) or COMM (see Section 6.1). Indicates calculated value currently used by the capacity controller. Rotating speed that corresponds to the manipulating value is indicated for a variable frequency drive (VFD) compressor. Indicates the unloader slide valves increase movement (as finally determined from combination of the positioner, limiter, and sequence controls). Indicates the unloader slide valves decrease movement (as finally determined from combination of the positioner, limiter, and sequence controls). Indicates that an increase in compressors capacity caused by an increase in electric current of the compressor motor power is prohibited. Indicates that the compressors capacity is forcibly decreased upon increase in electric current of the compressor motor power. Indicates that an increase in compressors capacity caused by an increase in discharge pressure is prohibited. Indicates that the compressors capacity is forcibly decreased upon increases in discharge pressure. Indicates that an increase in compressors capacity caused by an decrease in suction pressure is prohibited. Indicates that the compressors capacity is forcibly decreased upon decreases in suction pressure. Indicates that an increase in compressors capacity caused by an increase in intermediate pressure is prohibited (option). Indicates that the compressors capacity is forcibly decreased upon increases in intermediate pressure (option).

MA (Motor amperage limiter)

- 35 -

QT108300

COMMUNICATION window
This window displays the status of communications for each port.

Items of COMMUNICATION Window


Item OFF Status NEUTRAL NEUTRAL COMM-0 (Communication port 0) REQUESTED ACTIVE REQUESTING NO REQUEST ERROR FAILED NOTE: Indication for communication ports COM-2 and COM-3 are provided only when an extension communication board is installed. Description Communications are disabled. Communications are enabled but no signal is being transmitted through the communication line. Communications are enabled, and a request message is being received. Communications are enabled, and a request message is being sent. Communications are enabled but there is no request. Communications are enabled but error occurred (during reception). Communications are enabled but there is no response to request message.

MAIN STATUS window


This window displays various measurements and other analog input data.

Items of MAIN STATUS Window


Item SP ( SSP ) ( SP1 ) Description Actual suction pressure measurement at AI-01 Actual system suction pressure measurement at AI-16 or -19 Actual measurement of evaporators gas outlet pressure 1 at AI-17 Actual measurement of evaporators gas outlet pressure 2 at AI-25 Actual discharge pressure measurement at AI-02 Actual system discharge pressure measurement at AI-11 Actual liquid level measurement at AI-11 Actual supply oil pressure measurement at AI-03 Item ST SSH ( GT1 ) ( SH2 ) ( SP2 ) DP ( SDP ) ( LVL ) OP ( GT2 ) DT DSH Description Actual measurement of suction temperature at AI-05 Calculated value of suction superheating temperature at VAI-04 Actual measurement of evaporators gas outlet temperature 1 at AI-18 Calculated value of suction superheating temperature 2 at VAI-14 Actual measurement of evaporators gas outlet temperature 2 at AI-26 Actual measurement of discharge temperature at AI-06 Calculated value of discharge superheating temperature at VAI-06 Actual measurement temperature at AI-07 of supply oil

OT

- 36 -

QT108300

Items of MAIN STATUS Window (continued)


Item Description Actual measurement of after-oil-filter oil pressure at AI-04 Item ( OS ) ( AFFP ) Actual measurement of supply oil pressure ( SVOP ) for slide valve at AI-17 Actual intermediate pressure ( IP ) measurement at AI-09 Calculated value of after-fine-filter (FFP) differential pressure at VAI-15 Calculated value of supply oil differential OP pressure at VAI-01 Calculated value of differential pressure at P VAI-03 Calculated value of after-oil-filter FP differential pressure at VAI-02 Actual position measurement of low-stage LSV slide valve at AI-15 Actual measurement of remote capacity ( RLD ) command input at AI-20 REFRIGERANT Refrigerant type RUN Running time of last operation cycle TODAY Todays running time After-resetting (after-overhaul) running RUN TIME time TOTAL TIME Total (non-resettable) running time Actual measurement of optional analog ( OPT1 ) input 1/4 Actual measurement of optional analog ( OPT3 ) input 3/4 NOTE: - In the above table AI-xx indicates an analog input channel number, while VAI-xx indicates a virtual analog input channel number. Virtual analog values are generated through calculation inside CP4 and used as inputs. - The parenthesized items are indicated only when the corresponding options have been selected. (For the method for selecting options, see Chapter 4 Setups (SETUP Menu (F6)).) - The following virtual input values are derived from the associated actual measurements as follows: Calculated supply oil differential pressure OP Case 1 (all conditions except those of Case 2):
OP = OP (actual supply oil pressure) - DP (actual discharge pressure)

Description Actual measurement of separated oil temperature at AI-08 (North American markets) Actual measurement of after-fine-filter differential pressure at AI-08 (EU markets) Calculated value of supply oil differential pressure 2 at VAI-17 Actual measurement of intermediate temperature at AI-10 Calculated value of intermediate superheat temperature at VAI-05 Actual chiller inlet temperature at AI-13 Actual chiller outlet temperature at AI-14 Actual electric current value of compressor motor at AI-12 Actual measurement of high-stage slide valve position at AI-16

AFP

(OP2 ) ( IT ) ( ISH ) ( EBT ) ( LBT ) MA ( HSV )

STOP

Time of duration of final stop

( OPT2 ) ( OPT4 )

Actual measurement of optional analog input 2/4 Actual measurement of optional analog input 4/4

Case 2 (when the compressor is of a Single J Group or an FM160 Group, or when the compressor has no oil pump or the oil pump is not in operation):
OP = OP (actual supply oil pressure) - SP (actual suction pressure)

Calculated differential pressure P Case 1 (all single-stage compressors except Single J Group compressors with operating oil pumps):
P = AFP (actual after-oil-filter pressure) - SP (actual suction pressure)

Case 2 (two-stage compressor Compound-1 or Compound-2):


P = AFP (actual after-oil-filter pressure) - IP (actual intermediate pressure)

Case 3 (Single J Group compressors with operating oil pumps):


P = OP (actual supply oil pressure) - SP (actual suction pressure)

Case 4 (Single J Group or FM160 Group compressors with no oil pumps or oil pumps not in operation): Differential pressure calculation is disabled. Calculated after-oil-filter differential pressure FP Case 1 (all compressors except Single J Group and FM160 Group compressors):
FP = DP (actual discharge pressure) - AFP (actual after-oil-filter oil pressure)

Case 2 (Single J Group compressors):


FP = DP (actual discharge pressure) - OP (actual supply oil pressure)

- 37 -

QT108300

Case 3 (FM160 Group compressors):


FP = AFP (actual after-oil-filter pressure) - OP (actual supply oil pressure)

Calculated after-fine-filter differential pressure FFP


FFP = DP (actual discharge pressure) - AFFP (actual after-fine-filter oil pressure)

Calculated supply oil differential pressure 2 OP2


OP2 = SVOP (actual supply oil pressure for slide valve) - DP (actual discharge pressure)

Function Menus
When one of the function keys (F1 to F7) is pressed, a menu listing the options (window titles) available in it is displayed as shown in the following example.

1
12345678901234567890123456789012345678901234567890123456789012345678901234567890

Function Menus
No. 1 2 Name Function display area Function menu Function When one of the function keys F1 to F7 is pressed, the name of corresponding function (title of the menu) is displayed in reverse video. When one of the function keys F1 to F7 is pressed, the menu listing the options (windows) for the function is displayed.

- 38 -

QT108300

Windows
When any of the options in a function menu is selected, the window corresponding to the selection will open as shown in the following example.

Windows
No. 1 Name Window Function When an option is selected from a function menu, the corresponding window opens. The window shows its title and the setting items it contains.

3.2 To Make Settings Selection from Options


Use the TAB key to select the window where setting is to be made. The first item of the selected window is displayed in reverse video. To select an item for setting within the window, use the , , , or key.

Any item with a box for such an item. 1.

in the setting area has two or more options for your selection. Use the following method to make setting

Use the TAB key to move the cursor into the window that contains the item for which you desire to make setting.

- 39 -

QT108300

2.

Move the cursor to the item using the or key.

3.

Press the ENTER key; a list of options appears.

4.

Select the desired option from the list using the or key.

5.

Press the ENTER key to confirm your selection. The selected option then turns red. (The cursor will move to the next item.)

6.

Press the SAVE key to save your selection into memory. (The selected option will turn into the normal display color when saved.)

NOTE: Without pressing the SAVE key, the setting will not have any effect on the control.

3.3 To Make Setting Entry Using Keys


Use the TAB key to select the window where setting is to be made. The first item of the selected window is displayed in reverse video. To select an item for setting within the window, use the , , , or key.

Any item having a setting area enclosed between brackets requires the use of numeral keys for entering a value. Use the following method to make entries for such an item.

- 40 -

QT108300

NOTE: If you select psi gauge to display pressures, then inch Hg is automatically selected as units of vacuums for both monitoring and setting. 1. Use the TAB key to move the cursor to the window that contains the item for which you desire to make setting.

2.

Move the cursor to the item using the , , , or key.

3.

Enter the desired value using numeric keys.

When entering a value in units of inch Hg, press the minus (-) key first to enter a number proceeded by -.

4.

Press the ENTER key to confirm the entry. The entered value then turns red. (The cursor will move to the next item.)

For entry in units of inch Hg, the unit display changes to Hg when you press the ENTER key to confirm the entry.

5.

Press the SAVE key to save the entry into memory.

NOTE: - Without pressing the SAVE key, the setting will have no effect on the control. Saving by pressing the SAVE key is necessary also for units of values to make the setting valid. - When you enter values in units of inch Hg, confirming the entry by pressing the ENTER key determines inch Hg as units for display.

- 41 -

QT108300

3.4 Software Resetting Method


It is necessary to perform special booting of CP4 before you can select optional control functions and make setting for these functions, but CP4 requires system resetting before you can perform or cancel special booting. There are the following two system resetting methods: - Hardware method - Software method This section describes the software method (For the hardware method, see Section 2.2.1 Reset Switch on CPU Board.). Procedure With CP4 activated when the compressor unit is not operating, close all menus and press the SHIFT, ALT, and DELETE keys simultaneously. (Pressing these keys when the compressor unit is in operation is invalid.)

The screen shown above appears. (Pressing the ESC key in this state cancels the above operation of the three keys, causing normal operation of CP4 to resume.) Press the ENTER key; system resetting will be executed.

Resetting the system brings CP4 in a momentarily instable condition, following which CP4 is placed in a condition that would result just after turning power ON. As this condition is detrimental to the system if it occurs during operation, never perform system resetting while the compressor or any of the accessories is in operation.

- 42 -

QT108300

3.5 Special Booting


In addition to normal booting, special booting is used to start PC4. Special booting is the method used before performing the system setup and initializing individual control settings. When PC4 is started using special booting, the compressors control sequence and other sequence are placed into a halt, rendering the compressor inoperative.

If CPU is reset following turning power on or other action that takes place under a low battery condition, the CP4 automatically performs special booting for the sake of safety. Once this occurs, further operation of the compressor unit is prohibited unless the battery is replaced with a normal voltage battery (see Section 2.2.2 Replacement of Memory Backup Battery on CPU Board).

Special booting also automatically takes place after performing any of the setting changes described in Section 4.2 Settings in ANALOG INPUT SCALING Window (Option 2 of SETUP Menu (F6)). Special booting is necessary before performing the following operation: - Selection of an optional control function - System setup - Option setups - Initialization of settings The figure below shows the first screen that appears immediately after power-up or resetting of CP4.

For normal booting, either wait 5 seconds with the above screen displayed or press the ESC key. For special booting, press the SHIFT, ALT, and DELETE keys at the same time while this display is on the screen. The screen will then display the following messages.

- 43 -

QT108300

(The above screen is for the case without using the hardware key.) When any of the numeric keys 1 to 4 is pressed while this display is on the screen, the items indicated to the right of each number in the following table are initialized (reset to the initial values). Numeric key 1 Initialized items The following settings are returned to the initial settings: Control settings, OPTION SETUP items, SYSTEM SETUP items, and OPTION SELECT items. (Use of the hardware key is required. This special device is not supplied with the product and used for adjustments necessary before shipment of the product from the factory.) The following settings are returned to the initial settings: Control settings, OPTION SETUP items and SYSTEM SETUP items. The following settings are returned to the initial settings: Control settings and OPTION SETUP items. The following settings are returned to the initial settings: Control settings.

2 3 4 NOTE:

For the OPTION SETUP, SYSTEM SETUP, and OPTION SELECT items, see Chapter 4. After the initialization, or if do not want the initialization, pressing the ESC key causes the following screen to appear, where you can make setting for each item.

Message appearing when special booting is performed.

- 44 -

QT108300

When special booting is executed, the screen displays the CONTROL PROGRAM HAS BEEN STOPPED BY SPECIAL BOOT. message, indicating that the internal sequences such as the compressor control sequence are brought to a halt (all digital outputs turn off and all analog outputs are at 0 %). To cancel special booting and restart PC4 by normal booting perform the following operation: Close all menus and press the SHIFT, ALT, and DELETE keys simultaneously. The post-resetting screen showing the BOOT PROCESS IS IN PROGRESS message will then appear. Wait 5 seconds without doing anyting or press the ESC key to initiate the normal booting.

Resetting the system brings CP4 in a momentarily instable condition, following which CP4 is placed in a condition that would result just after turning power ON. As this condition is detrimental to the system if it occurs during operation, never perform system resetting while the compressor or any of the accessories is in operation.

The settings for the items in the OPTION SELECT, SYSTEM SETUP, and OPTION SETUP windows (see Chapter 4) must be cnsistent with the settings made on the compressor unit. If there are discrepancies in setting between the controller and the compressor unit, the operational control of the compressor may become improper and the compressors protection functions may not work at all. When canceling the special booting (i.e. shifting to the normal booting), be sure to turn OFF the operation command inputs in order to prevent the compressor from starting unexpectedly. Whenever new settings or changes to settings are made for the OPTION SELECT, OPTION SETUP and SYSTEM SETUP items, be sure to also confirm the relevant settings for other functions before starting the compressor unit.

- 45 -

QT108300

Chapter 4 Setups (SETUP Menu (F6))


4.1 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6))
The SYSTEM SETUP window is for setting the type of the compressor, type of the refrigerant used, units of the entered and displayed values, and other parameters related to the setup of CP4. Special booting is needed to enable this window. (Simply doing normal booting does not make the SETUP menu appear on the screen even when the F6 key is pressed.) In addition, entry of a LEVEL-3 password is required to access to the SYSTEM SETUP window.

Do not make setting to enable any parameter item that assumes prior installation of an optional extension board if the board itself is not installed. Doing such setting may cause PC4 to issue an EMERGENCY STOP FAILURE alarm that cannot be canceled by the CLEAR ALARM key. If the alarm is issued, the compressor cannot continue operation.

NOTE: Even when PC4 is started by normal booting, you can check the current setting for each item using the SHOW SYSTEM SETUP window (Option 1 of the DIAGNOSTIC menu (F7)), although no setting change is possible in this window.

NOTE: In the following table, the setting options marked * are the default settings.

Items in SYSTEM SETUP Window


Item I/O PLATFORM (Input/output specification) Setting Option * NORTH AMERICA EUROPE ASIA * YES NO Description North American specification. (Oil separator temperature (OS) can be displayed.) European specification. (The after-fine-filter pressure (AFFP) can be displayed.) Asian specification. (Neither OS nor AFFP can be displayed.) With oil separator temperature sensor Without oil separator temperature sensor - 46 -

OIL SEPARATOR TEMP. SENSOR

QT108300

Items in SYSTEM SETUP Window (continued)


Item AFTER FINE FILTER PRESS. SENSOR LANGUAGE Setting Option * YES NO * ENGLISH FRENCH GERMAN PORTUGUESE RUSSIAN SPANISH * SINGLE ECONOMIZER W/O SENSOR ECONOMIZER W/SENSOR COMPOUND-1 (1610 & 1612) COMPOUND-2 (2016 & HIGHER) SINGLE UD-V (VARIABLE Vi) 400 SERIES SINGLE J SINGLE J ECONOMIZER W/O SENSOR SINGLE J ECONOMIZER W/ SENSOR FM160 FM160 ECONOMIZER W/O SENSOR FM160 ECONOMIZER W/ SENSOR * OBVERSE REVERSE W/O OIL PUMP * W/ 1-OIL PUMP W/ 2-OIL PUMPS * LEAD Y01/LAG Y14 LEAD Y14/LAG Y01 * FULL LUBE PRE LUBE PARTIAL LUBE MPascal Abs Mpascal Gauge Kgf/cm2 Abs Kgf/cm2 Gauge bar Abs bar Gauge psi Abs * psi Gauge K o C * oF Description With after-fine-filter pressure sensor Without after-fine-filter pressure sensor Single-stage compressor models Economizer (without intermediate temperature and pressure sensors) Economizer (with intermediate temperature and pressure sensors) (Intermediate pressure (IP), intermediate temperature (IT) and intermediate superheat (ISH) are displayed.) Two-stage compressor models (1610 and 1612) (Intermediate pressure (IP), intermediate temperature (IT) and intermediate superheat (ISH) are displayed.) Two-stage compressor (2016 and higher number models) (High-stage slide valve position (HSV), intermediate pressure (IP), intermediate temperature (IT), and intermediate superheat (ISH) are displayed.) Compressor with automatic Vi control 400 series compressors (unloader side valve oil supply pressure (SVOP) and oil differential pressure 2 (OP2) are displayed.) J series compressors J series with economizer (without intermediate temperature and pressure sensors) J series with economizer (with intermediate temperature and pressure sensors) (Intermediate pressure (IP), intermediate temperature (IT), and intermediate superheat (ISH) are displayed.) FM160 model compressors FM160 model compressors with economizer (without intermediate temperature and pressure sensors) FM160 model compressors with economizer (with intermediate temperature and pressure sensors) (Intermediate pressure (IP), intermediate temperature (IT), and intermediate superheat (ISH) are displayed.) Obverse side of mAYEKAWA MYCOM refrigerating system Reverse side of mAYEKAWA MYCOM refrigerating system Without oil pump With one oil pump With two oil pumps Output for leading pump: Y01; output for lagging pump: Y14 Output for leading pump: Y14; output for lagging pump: Y01 Pump-pressurized oil feed Differential-pressure oil feed Pump-pressurized oil feed only at startup Absolute pressure in MPa Gauge reading in MPa Absolute pressure in Kgf/cm2 Gauge reading in Kgf/cm2 Absolute pressure in bar Gauge reading in bar Absolute pressure in psi Gauge reading in psi Absolute temperature Centigrade temperature Fahrenheit temperature

COMPRESSOR (Compressor type)

LOAD INDICATOR LOCATION (Unloader side valve position indicator location) OIL PUMP (Number of oil pumps) OIL PUMP LEAD/LAG OIL FEED TYPE

PRESSURE DISPLAY (Units of pressure display)

TEMPERATURE DISPLAY (units)

- 47 -

QT108300

Items in SYSTEM SETUP Window (continued)


Item REFRIGERANT (Type) Setting Option R22 R23 R134a R404A R407C R410A R502 R507A R717 R290 R744 USER DEFINED Change to LOCAL MODE Keep Current MODE Change to LOCAL STOP Keep Current CONDITION AUTO RESET KEY PAD YES NO NORMAL OPEN NORMAL CLOSE Description Chloradifluoromethane (CHCIF2) Trifluoromethane (CHF3) 1,1,2,2-Tetrafluoromethane (C2H2F4) Blend of R-125/R-143a/R-134a Blend of R-32/R-125/R-134a Blend of R-32/R-125 Blend of R-22/R-115 R-125/R-143a Ammonia(NH3) Propane(C3H8) Carbon dioxide (CO2) Undefined refrigerant (Superheat is not displayed.) Automatic change to the LOCAL mode Staying in the current operation control mode Changed to the STOP state in the LOCAL mode Staying in the current operation control mode and state. Alarm is automatically reset. Alarm is reset by CLEAR ALARM key. Alarm is output. Alarm is not output. Normally open; closed on alarm Normally closed; open on alarm

OPERATION MODE ON FAILURE OPERATION MODE RESTORE ON POWER UP ALARM RESET ALARM OUTPUT

* * * *

ALARM/FAILURE OUTPUT * TYPE NOTE:

ALARM indicates a non-critical alarm allowing continued operation of the compressor unit. FAILURE indicates a critical alarm causing an immediate shutdown of the compressor unit.

4.2 Settings in ANALOG INPUT SCALING Window (Option 2 of SETUP Menu (F6))
The ANALOG INPUT SCALING window is for setting the scaling (the range between the upper and lower limits and units) of the values of the sensors connected to the analog input channels and the units in which these values are indicated. This window is also used to set the upper and lower limits of the compressor motor current (in terms of the primary current to secondary current ratio (CT ratio)) and the scaling of optional analog inputs. Special booting is needed to enable this window. Simply doing normal booting does not cause the SETUP menu to appear even when the F6 key is pressed. In addition, entry of the LEVEL-3 password is required to access to this window. NOTE: Even after a start of CP4 by normal booting, you can check the current setting for each item using the SHOW SYSTEM SETUP window (Option 2 of DIAGNOSTIC menu (F7)) although no setting change is possible in the window.

- 48 -

QT108300

Items in ANALOG INPUT SCALING Window


Item SENSOR (Units of sensor values) Parameter NO UNIT MPascal Abs Mpascal Gauge Kgf/cm2 Abs Kgf/cm2 Gauge bar Abs bar Gauge psi Abs psi Gauge K o C o F Ampere % mm/SEC /SEC rpm Hz LEFT RIGHT Description Units are not displayed. Absolute pressure in MPa Gauge reading in MPa Absolute pressure in Kgf/cm2 Gauge reading in Kgf/cm2 Absolute pressure in bar Gauge reading in bar Absolute pressure in psi Gauge reading in psi Absolute temperature Temperature in Centigrade Temperature in Fahrenheit Compressor motor current in ampere Percent mm/second *2 inch/second *2 Number of rotations/minute *2 Hertz (cycles/second) *2 Enter a value (in the range from -99999 to 99999) at the time of 0% input. *1 (However, | LEFT - RIGHT | 2047) Enter a value (in the range from -99999 to 99999) at the time of 100% input. (However, | LEFT - RIGHT | 2047) *1 Displays the current value after scaling.

SCALING (Scaling of sensor values)

PROCESS VALUE (Current value) NOTE: *1 *2

This limit is ignored when Ampere is selected for a sensor item. Effective only for the analog inputs that are assigned in the OPTION ANALOG INPUT window (Option 3 of SETUP menu (F6)).

When any of the settings is changed in the ANALOG INPUT SCALING window, the CPU will automatically reset itself upon closure of the window. After every closure of the window under this condition, CP4 automatically initiates special booting to prevent unexpected start of the compressor.

4.3 Settings in OPTION ANALOG INPUT Window (Option 3 of SETUP Menu (F6))
This window allows assigning up to four unoccupied analog input channels to sensors so that their values (together with their units) can be displayed on the screen. When analog input channels are assigned to sensors in this window, not only the sensor data can be displayed on the screen and read via communications, but also it becomes possible to assign an ALARM (non-critical alarm) and FAILURE (critical alarm) thresholds to the sensor outputs in both upward and downward directions. Special booting is needed to enable this window. (Simply doing normal booting does not cause the SETUP menu (F6) to appear on the screen.) In addition, entry of the LEVEL-3 password is required to access to this window. NOTE: Even after a start of CP4 by normal booting, you can check the current setting for each item using the SHOW OPTION ANALOG INPUT window (Option 3 of DIAGNOSTIC menu (F7)) although no setting change is possible in the window.

- 49 -

QT108300

Unless channel numbers corresponding to the sensors in parentheses below already occupy the boxes 1/4 to 4/4 under CHANNEL in the window, you can assign a channel numbers to a vacant channel. (Default values are xxxx, indicating no assignment.) - AI 8 (oil separator temperature, after-fine-filter pressure) - AI 9 (intermediate pressure) - AI10 (intermediate temperature) - AI11 (system discharge output, liquid level) - AI13 (brine inlet temperature) - AI14 (brine outlet temperature) - AI16 (high-stage slide valve position, system suction pressure) - AI21: Does not work even if assigned unless optional AD board REF-CX100-AD01 is installed. - AI22: Does not work even if assigned unless optional AD board REF-CX100-AD01 is installed. - AI23: Does not work even if assigned unless optional AD board REF-CX100-AD01 is installed. - AI24: Does not work even if assigned unless optional AD board REF-CX100-AD01 is installed. The following units can be assigned to the option analog inputs. Item SENSOR Unit NO UNIT (default) TEMPERATURE PRESSURE CURRENT RATE VIBRATION REVOLUTION FREQUENCY No unit Temperature sensor Pressure sensor Current sensor 0.0 - 100.0 % Vibrometer sensor Revolution sensor Frequency Description

NOTE: When setting the scaling for inputs of the assigned sensors, See Section 4.2 Settings in ANALOG INPUT SCALING Window (Option 2 of SETUP Menu (F6)) Window. Following types of ALARM or FAILURE are selectable for the assigned optional analog input item. For the method, see Section 7.1 Settings in ALARM/FAILURE Windows 1/3 to 3/3.

- 50 -

QT108300

Item ALARM or FAILURE

Type NOT USE (default) LOW HIGH HIGH & LOW

Description No ALARM and FAILURE are assigned Low ALARM or Low FAILURE is assigned High ALARM or High FAILURE is assigned Low and High ALARM, or Low and High FAILURE is assigned

4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))
This window allows you to make USE/NOT USE setting and other selection for each optional control function. Special booting is needed to enable this window. In addition, entry of the LEVEL-2 password is required to access to this window.

Do not enable any of the items that assume prior installation of an optional extension board if the board itself is not actually installed. Doing such setting may cause PC4 to generate an EMERGENCY STOP FAILURE alarm that cannot be canceled by the CLEAR ALARM key. If the alarm is issued, the compressor cannot continue operation.

NOTE: Even after a start of CP4 by normal booting, you can check the current setting for each item using SHOW OPTION SETUP 1/2 window (Option 5 of the DIAGNOSTIC menu (F7)) , although no setting change is possible in the window.

Option selection for each of the items in the OPTION SELECT Item column in the following table is possible only when that item is enabled (that is, ENABLE is selected for the item in the OPTION SELECT window). See Section 4.6 Settings in OPTION SELECT Window (Option 6 of SETUP Menu (F6)) for details. (Also refer to Section 1.3.) NOTE: - The setting options marked * in the following table are the default selections. - For interpretation of the acronyms and abbreviations in the Description column, see Section 3.1.

- 51 -

QT108300

Items in OPTION SETUP 1/2 Window


OPTION SELECT Item REMOTE CAPACITY CONTROL CONDENSER VFD CONTROL Item REMOTE CAPACITY CONTROL Setting Option * NONE DIGITAL ANALOG * NOT USE USE * LOCAL DISCHARGE PRESSURE SYSTEM DISCHARGE PRESSURE * ON/OFF SINGLE SET ON/OFF MULTI SET * NOT USE USE * LOCAL DISCHARGE PRESSURE SYSTEM DISCHARGE PRESSURE * ON/OFF SINGLE SET ON/OFF MULTI SET * NOT USE 2UNITS - 8UNITS * NOT USE USE * NOT USE USE * NOT USE USE * NOT USE USE DO10,11,12,16,17(UD-V) USE DO19,1A,1B,1C,1D(UD-V) USE J SERIES * NOT USE USE NONE/THERMAL EXPANSION * YOSAKU 1-VALVE YOSAKU 2-VALVES MOTORIZED CONTROL VALVE * DISCHARGE TEMPERATURE DISCHARGE SUPERHEAT * NOT USE USE * NOT USE USE * LSV & SP HSV & IP Description Not used Control using digital inputs Control using analog inputs (RLD is displayed.) Not used Used System discharge pressure is displayed. Single target ON/OFF control Multiple target ON/OFF control System discharge pressure is displayed. Single target ON/OFF control Multiple target ON/OFF control IP, IT, ISH, and HSV are displayed. (AUTO Vi window is displayed in Main Status Screen.) YOSAKU expansion valve x 1 YOSAKU expansion valve x 2 4 - 20 mA driven expansion valve Liquid supply control depending on both high-stage capacity and suction pressure Liquid supply control depending on both high-stage capacity and intermediate pressure

CONDENSER CONTROL CONDENSER CONTROL TARGET

CONDENSER CONTROL METHOD CONDENSER 3STEPS CONTROL or CONDENSER 6STEPS CONTROL CONDENSER CONTROL CONDENSER CONTROL TARGET

CONDENSER CONTROL METHOD AUTO STAGING VFD COMPRESSOR AUTO STAGER VFD COMPRESSOR (Inverter capacity control) VFD COMPRESSOR OUTPUT LIMIT (Inverter output range limit control) HIGH STAGE CAPACITY CONTROL AUTO Vi CONTROL

HIGH STAGE CAPACITY CONTROL AUTO Vi CONTROL

LIQUID INJECTION OIL COOLING CONTROL

LIQUID INJECTION OIL COOLING CONTROL INJECTION VALVES (Type of control valves)

CONTROL TARGET

HOT GAS BYPASS CONTROL STARTING BYPASS CONTROL When COMPOUND-2(2016 & HIGHER) is selected for COMPRESSOR in SYSTEM SETUP window

HOT GAS BYPASS CONTROL STARTING BYPASS CONTROL ECONIMIZER/INTERCOOL ER LIQUID SUPPLY CONTROL

- 52 -

QT108300

Items in OPTION SETUP 1/2 Window (continued)


OPTION SELECT Item ECONOMIZER/INTERCOOL ER EXPANSION VALVE CONTROL Item ECONOMIZER/INTERCOOL ER EXPANSION VALVE CONTROL EXPANSION VALVES Setting Option * NOT USE USE NONE/TERMAL EXPANSION YOSAKU MOTORIZED CONTROL VALVE NOT USE USE NOT USE USE LOCAL SUCTION PRESSURE SYSTEM SUCTION PRESSURE CHILLER ENTERING TEMPERATURE CHILLER LEAVING TEMPERATURE LOCAL SUCTION PRESSURE SYSTEM SUCTION PRESSURE CHILLER LEAVING TEMPERATURE COMBINED LOCAL SP/LB COMBINED SYSTEM SP/LB LOCAL DISCHARGE PRESSURE SYSTEM DISCHARGE PRESSURE Description (IP, IT, and ISH are displayed.) YOSAKU expansion valve 4 - 20 mA driven expansion valve (System suction pressure is displayed.) (EBT is displayed.) (LBT is displayed.) SSP is displayed. LBT is displayed. SDP is displayed.

* COMPRESSOR OIL SEAL CONTROL LEVEL CONTROL CONTROL TARGET (CUT IN/OUT) * * *

COMPRESSOR OIL SEAL CONTROL LEVEL CONTROL CONTROL TARGET (CUT IN/OUT)

CONTROL TARGET (CAPACITY CONTROL)

CONTROL TARGET (CAPACITY CONTROL)

4.5 Setting in OPTION SETUP 2/2 Window (Option 5 of SETUP Menu (F6))
This window allows you to make USE/NOT USE setting and other selection for each optional control function. Special booting is needed to enable this window. In addition, entry of the LEVEL-2 password is required to access to this window.

Do not enable any of the items that assume prior installation of an optional extension board if the board itself is not actually installed. Doing such setting may cause PC4 to generate an EMERGENCY STOP FAILURE alarm that cannot be canceled by the CLEAR ALARM key. If the alarm is issued, the compressor cannot continue operation.

NOTE: Even after a start of CP4 by normal booting, you can check the current setting for each item using SHOW OPTION SETUP 2/2 window (Option 6 of the DIAGNOSTIC menu (F7)), although no setting change is possible in the window.

- 53 -

QT108300

Option selection for each of the items in the OPTION SELECT Item column in the following table is possible only when that item is enabled (that is, ENABLE is selected for the item in the OPTION SELECT window). See Section 4.6 Settings in OPTION SELECT Window (Option 6 of SETUP Menu (F6)) for details. NOTE: - The setting options marked * in the following table are the default selections. - For interpretation of the acronyms and abbreviations in the Description column, see Section 3.1.

Items in OPTION SETUP 2/2 Window


OPTION SELECT Item CHILLER CONTROL Item CHILLER CONTROL LIQUID SUPPLY SV Setting Option * NOT USE USE * 1 2 3 NONE/THERMAL EXPANSION YOSAKU 1-VALVE YOSAKU 2-VALVES * 1-MOTORIZED CONTROL VALVE 2-MOTORIZED CONTROL VALVES * SH ONLY SH W/ SP LIMIT SH W/ LB LIMIT SH W/ SP & LB LIMIT CHILLER GAS PRESS. * NO SENSOR YES CHILLER GAS TEMP. * NO SENSOR YES CHILLER ENTERING TEMP. * NO SENSOR YES Description 1 valve 2 valves 3 valves None or thermal expansion valve YOSAKU expansion valve x 1 YOSAKU expansion valve x 2 4 - 20 mA driven expansion valve 4 - 20 mA driven expansion valve x 2 (SP1, GT1, SP2, and GT2 are displayed.) Control depending on superheat alone Limit control depending on superheat and suction pressure Limit control depending on superheat and chiller outlet temperature Limit control depending on suction pressure and chiller outlet temperature (SP1 is displayed.) (GT1 is displayed.) (EBT is displayed.)

EXPANSION VALVES

EXPANSION VALVE CONTROL

- 54 -

QT108300

Items in OPTION SETUP 2/2 Window (continued)


OPTION SELECT Item CHILLER CONTROL (continued) Item CHILLER LEAVING TEMP. SENSOR CHILLER LEAVING TEMP. CONTROL CHILLER PUMP MODE Setting Option * NO YES * NOT USE USE * NOT USE CONTINUOUS AUTO START/STOP Description (LBT is displayed.) Continuous operation Automatic start/stop

4.6 Settings in OPTION SELECT Window (Option 6 of SETUP Menu (F6))


This window allows you to make enable/disable setting for each optional control function. Special booting is needed to enable this window. In addition, entry of a LEVEL-3 password is required to access to this window.

NOTE: The setting options marked * in the following table are the default selections.

Items in OPTION SELECT Window


OPTION SELECT Item REMOTE CAPACITY CONTROL CONDENSER VFD CONTROL Setting Option * DISABLE ENABLE * DISABLE VFD ONLY VFD + 2STEPS VFD + 3STEPS VFD + 5STEPS * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE Description Enabled (Variable frequency drive only) Enabled (Variable frequency drive and 2-step control) Enabled (Variable frequency drive and 3-step control) Enabled (Variable frequency drive and 5-step control) -

CONDENSER 3STEPS CONTROL CONDENSER 6STEPS CONTROL CHILLER CONTROL AUTO STAGING VFD COMPRESSOR HIGH STAGE CAPACITY CONTROL

- 55 -

QT108300

Items in OPTION SELECT Window (continued)


OPTION SELECT Item AUTO Vi CONTROL LIQUID INJECTION OIL COOLING CONTROL HOT GAS BYPASS CONTROL STARTING BYPASS CONTROL ECONOMIZER/INTERCOOL ER EXPANSION VALVE CONTROL LEVEL CONTROL COMPRESSOR OIL SEAL CONTROL 400 SERIES COMPRESSOR CONTROL Setting Option * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE * DISABLE ENABLE Description -

- 56 -

QT108300

Chapter 5 Adjustments (ADJUSTMENT Menu (F5))


5.1 Settings in SLIDE VALVE SETUP Window (Option 1 of ADJUSTMENT Menu (F5))
The settings in this window are necessary to enable automatic calibration of the 0 % and 100 % position signals of the unloader slide valve. NOTE: CP4 cannot complete the automatic calibration processing if any of the following conditions exists: - The potentiometer for detecting the slide valve position is defective. - The potentiometer is installed at an inappropriate angle. - Connection to analog input channels is incorrect. - Any of the analog input selections is incorrect (see Section 2.4.2 Input Type Selection for Channels 15 and 16 of Analog Input Boards). The setting in this window is possible only when YES is selected for D/O TEST OPERATION in the OPERATION MODE window (Option 1 of the SETPOINT menu (F1)). If NO is selected, the NOT AVAILABLE message shown in the following figure appears, indicating that the setting in the SLIDE VALVE SETUP window is not possible.

When YES is selected for D/O TEST OPERATION, the screen displays as follows.

- 57 -

QT108300

Setup Procedure The setup procedure in this window is different according to the compressor type. Use the appropriate one of the following four different procedures. a. Single-stage compressors (except compressors with an automatic Vi adjustment function and J-Series compressors) and two-stage compressors without a function for detecting the high-stage unloader valve position 1. Press the ENTER key to activate the SLIDE VALVE SETUP function

(Display showing the current settings for the unloader slide valve) 2. The output from DO-04 (Y03) of the digital input/output board on CP4 turns ON, energizing the low-stage capacity reduction solenoid valve to start unloading the compressor. (The output from DO-02 (Y01) also turns on to command operation of the oil pump.) Press the TAB key when the capacity has reached 0.0 % to set the SLIDE VALVE MINIMUM value. The SLIDE VALVE Location value changes from 0 to 4095 as the input changes from 0 % to 100 %.

(Screen for setting SLIDE VALVE MINIMUM value) 3. The output from DO-03 (Y02) of the digital input/output board on CP4 turns on, energizing the low-stage capacity increase solenoid valve to start loading of the compressor. Press the TAB key when the capacity has reached 100.0 %. NOTE: The processing does not advance to the next step unless the SLIDE VALVE Location value at this time is larger than the value at the time of the SLIDE VALVE MINIMUM value in the above step.

(Screen for setting SLIDE VALVE MAXIMUM value) 4. The output from DO-04 (Y03) of the digital input/output board on CP4 turns on, energizing the low-stage capacity reduction solenoid valve to start unloading the compressor. When the compressor is unloaded down to 5.0 %, the output from DO-04 (Y03) to the low-stage capacity reduction solenoid valve automatically turns OFF. (The oil pump operation command output from DO-02 (Y01) also turns OFF. The SLIDE VALVE SETUP window then closes and the display returns to the ADJUSTMENT menu.)

(Screen showing automatic movement of the slide valve to unload the compressor)

- 58 -

QT108300

Setup operation in this SLIDE VALVE SETUP window involves actual operation of the oil pump. Check for safety in the compressor unit area before pressing the keys.

NOTE: Pressing the ESC key at any time can cancel the setup procedure halfway. b. Two-stage compressors (when COMPOUND-2 (2016 & HIGHER) has been selected for the COMPRESSOR item in the SYSTEM SETUP window) 1. Press the ENTER key to activate the SLIDE VALVE SETUP function.

(Display showing the current settings for the unloader slide valve) 2. The output from DO-04 (Y03) of the digital input/output board on CP4 turns on, energizing the low-stage capacity reduction solenoid valve to start unloading of the compressor. (The output from DO-02 (Y01) also turns on to command operation of the oil pump.) Press the TAB key to set the low-stage SIDE VALVE MINIMUM value when the capacity has reached 0.0 %. The SLIDE VALVE Location value changes from 0 to 4095 as the input changes from 0 % to 100 %.

(Screen for setting the low-stage SLIDE VALVE MINIMUM value) 3. The output from DO-03 (Y02) of the digital input/output board on CP4 turns on, energizing the low-stage capacity increase solenoid valve to start loading of the compressor. Press the TAB key to set the low-stage SLIDE VALVE MAXIMUM when the capacity has reached 100.0 %. NOTE: The processing does not advance to the next step unless the SLIDE VALVE Location value at this time is larger than the value at the time of the (low-stage) SLIDE VALVE MINIMUM value in the above step.

(Screen

for

setting

the

low-stage

SLIDE

VALVE

MAXIMUM value)

- 59 -

QT108300

4.

The output from DO-06 (Y05) of the digital input/output board on CP4 turns on, energizing the high-stage capacity reduction solenoid valve to start unloading of the compressor. Press the TAB key to set the high-stage SLIDE VALVE MINIMUM value when the capacity has reached 0.0 %.

(Screen

for

setting

the

high-stage

SLIDE

VALVE

MINIMUM value) 5. The output from DO-05 (Y04) of the digital input/output board on CP4 turns on, energizing the high-stage capacity increase solenoid valve to start loading of the compressor. Press the TAB key when the capacity has reached 100.0 %. NOTE: The processing does not advance to the next step unless the SLIDE VALVE Location value at this time is larger than the value at the time of the high-stage SLIDE VALVE MINIMUM value in the above step.

(Screen

for

setting

the

high-stage

SLIDE

VALVE

MAXIMUM value) 6. The outputs from DO-04 (Y03) and DO-06 (Y05) of the digital input/output board on CP4 turn ON, energizing the low-stage capacity reduction solenoid valve and high-stage capacity reduction solenoid valve to start unloading of the compressor. When the compressor is unloaded down to 5.0 %, the outputs from both DO-04 (Y03) and DO-06 (Y05) to the corresponding low- and high-stage capacity reduction solenoid valves automatically turn OFF. (The oil pump operation command output from DO-02 (Y01) also turns OFF. The SLIDE VALVE SETUP window then closes and the display returns to the ADJUSTMENT menu.)

(Screen showing automatic movement of the slide valves for unloading)

Setup operation in the SLIDE VALVE SETUP window involves actual operation of the oil pump. Check for safety in the compressor area before pressing the keys.

NOTE: Pressing the ESC key at any time can cancel the setup procedure halfway.

- 60 -

QT108300

c.

Compressors with an automatic Vi adjustment function (when SINGLE UD-V (Variable Vi) has been selected for COMPRESSOR in the SYSTEM SETUP window) 1. Press the ENTER key to activate the SLIDE VALVE SETUP function.

(Display showing the current settings for the unloader slide valve) 2. At the end of a fixed 5-second period taken for confirming the rise in oil supply differential pressure, the outputs from DO-18 (Y11), DO-23 (Y16), and DO-04 (Y03) of the digital input/output board on CP4 all turn on, energizing the Vi slide (M port) plug solenoid valve, Vi slide (LH port) increase solenoid valve, and capacity control decrease solenoid valve, respectively. (The output from DO-02 (Y01) also turns on to command operation of the oil pump.) Wait for 60 seconds (the Vi port is brought into the H port in this period).

(Adjustment is in progress to bring Vi port into H port) 3. Among the above outputs of the digital input/output board on CP4, the one from DO-18 (Y11) for the Vi slide (M port) plug solenoid valve and the one from DO-23 (Y16) for the Vi slide (LH port) increase solenoid valve are both turned OFF, while the rest from DO-04 (Y03) for the capacity control decrease solenoid valve remains ON, letting the compressor be unloaded. Press the TAB key to set the SLIDE VALVE MINIMUM (0 %) value when the capacity and the unloader slide valve position have reached 0.0 %. The SLIDE VALVE Location value changes from 0 to 4095 as the input changes from 0 % to 100 %.

(Screen for setting SLIDE VALVE MINIMUM (0 %)) 4. Of the outputs from the digital input/output board on CP4, output from DO 04 (Y03) for the capacity decrease control solenoid valve turns off, while that from DO-03 (Y02) for the capacity increase control solenoid valve turns on to start loading of the compressor. Press the TAB key to set the SLIDE VALVE MAXIMUM at H PORT value when the capacity has reached 100.0 %. NOTE: The processing does not advance to the next stage unless the SLIDE VALVE Location value is larger than the value at the time of the SLIDE VALVE MINIMUM (0 %) setting in the above step.

(Screen for setting SLIDE VALVE MAXIMUM at H PORT)

- 61 -

QT108300

5.

Of the outputs from the digital input/output board on CP4, the one from DO-03 (Y02) for the capacity increase control solenoid valve turns OFF, and the ones from DO-17 (Y10) for the Vi slide (M port) drain solenoid valve and from DO-24 (Y17) for the Vi slide (LH port) decrease solenoid valve both turn ON. Wait for 60 seconds (the Vi port is brought into the M port during this period).

(Adjustment is in progress to bring Vi port into M port) 6. Among the outputs of the digital input/output board on CP4, the one from DO-17 (Y10) for the Vi slide (M port) drain solenoid valve and the one from DO-24 (Y17) for the Vi slide (LH port) decrease solenoid valve both turn OFF, while the one from DO-03 (Y02) for the capacity control increase solenoid valve turns ON, letting the compressor be loaded. Press the TAB key to set the SLIDE VALVE MAXIMUM at M PORT value when the unloader slide valve position reached 100.0 %. NOTE: The processing does not advance to the next stage unless the SLIDE VALVE Location value at this time is larger than the value at the time of the H port setting in the above step.

(Screen for setting SLIDE VALVE MAXIMUM at M PORT) 7. Of the outputs from the digital input/output board on CP4, the output from DO-03 (Y02) for capacity increase solenoid valve turns OFF, while the output from DO-18 (Y11) for the Vi slide (M port) plug solenoid valve and the one from DO-24 (Y17) Vi slide (LH port) decrease solenoid valve both turn ON. Wait for 60 seconds (the Vi port is brought into the L port during this period).

(Adjustment is in progress to bring Vi port into L port) 8. Among the outputs of the digital input/output board on CP4, the one from DO-18 (Y11) for the Vi slide (M port) plug solenoid valve and the one from DO-24 (Y17) for the Vi slide (LH port) decrease solenoid valve both turn off, while the one from DO-03 (Y02) for the capacity control increase solenoid valve turns on, letting the compressor be loaded. Press the TAB key to set the SLIDE VALVE MAXIMUM 100 % value when the capacity and unloader slide valve position have reached 100.0 %. NOTE: The processing does not advance to the next stage unless the SLIDE VALVE Location value at this time is larger than the value at the time of the M port setting in the above step.

(Screen for setting SLIDE VALVE MAXIMUM 100 % value)

- 62 -

QT108300

9.

Of the outputs from the digital input/output board on CP4, the output from DO-03 (Y02) for capacity increase control solenoid valve turns off and the output from DO-04 (Y03) for the capacity decrease control solenoid valve turns on. When the compressor is unloaded to 5.0 % as a result, the output from DO-04 (Y13) for the capacity decrease control solenoid valve automatically turns off. (The oil pump operation command output from DO-02 (Y01) also turns off, the SLIDE VALVE SETUP window closes, and the display returns to the ADJUSTMENT menu.)

(Screen showing automatic movement of the slide valve for unloading) NOTE: Depending on the settings made in the OPTION SETUP 1/2 and OPTION SETUP 2/2 windows (Options 4 and 5 of the SETUP menu (F6)), the assignments for digital outputs may change to the following: Vi slide (M port) drain solenoid valve output Vi slide (M port) plug solenoid valve output Vi slide bypass solenoid valve output Vi slide (LH port) increase solenoid valve output Y19 Y1A Y1B Y1C

Vi slide (LH port) decrease solenoid valve output Y1D

Setup operation in the SLIDE VALVE SETUP window involves actual operation of the oil pump. Check for safety in the compressor area before pressing the keys.

NOTE: Pressing the ESC key at any time can cancel the setup procedure halfway. d. J Series compressors (when SINGLE J, SINGLE J ECONOMIZER W/O SENSOR, or SINGLE J ECONOMIZER W/ SENSOR has been selected for COMPRESSOR in the SYSTEM SETUP window) 1. Press the ENTER key to activate the SLIDE VALVE SETUP function.

(Display showing the current settings for unloader slide valve)

- 63 -

QT108300

2.

CP4 retains the following output states for 60 seconds in order to ensure that the Vi slide value is set to the H port poison and the unloader slide valve moves completely to the unloaded (0 %) position. Y01: Oil pump ON Y02: Unloader slide valves increase solenoid valve OFF Y04: Unloader slide valves decrease solenoid valve ON Y07: Vi slide valves increase solenoid valve ON Y08: Vi slide valves decrease solenoid valve OFF Wait until the display changes at the end of 60 seconds.

(Display while variable Vi auxiliary slide valve is being adjusted to H port position) 3. After the display has changed, CP4 retains the following output states again in order to record the 0 % position of the unloader slide valve in memory. Y01: Oil pump ON Y02: Unloader slide valves increase solenoid valve OFF Y04: Unloader slide valves decrease solenoid valve ON Y07: Vi slide valves increase solenoid valve ON Y08: Vi slide valves decrease solenoid valve OFF Press the TAB key to set the SLIDE VALVE MINIMUM (0 %) value when the position indicator of the unloader slide valve has become 0.0 %.

(Screen for setting SLIDE VALVE MINIMUM (0 %))

4.

After you have pressed the TAB key, CP4 retains the following output states now in order to move the unloader slide value to the 100 % position. Y01: Oil pump ON Y02: Unloader slide valves increase solenoid valve ON Y04: Unloader slide valves decrease solenoid valve OFF Y07: Vi slide valves increase solenoid valve ON Y08: Vi slide valves decrease solenoid valve OFF Press the TAB key to set the SLIDE VALVE MAXIMUM at H PORT value when the position of the unloader slide valve has become 100.0 %. NOTE: The processing does not advance to the next stage unless the SLIDE VALVE Location value is larger than the value for the SLIDE VALVE MINIMUM value in the above step.

(Screen for setting SLIDE VALVE MAXIMUM at H PORT)

- 64 -

QT108300

5.

CP4 retains the following output states for 60 seconds now in order to set the Vi slide valve to the L port position. Y01: Oil pump ON Y02: Unloader slide valves increase solenoid valve OFF Y04: Unloader slide valves decrease solenoid valve OFF Y07: Vi slide valves increase solenoid valve OFF Y08: Vi slide valves decrease solenoid valve ON Wait until the display changes at the end of 60 seconds.

(Screen displayed while Vi slide valve is being adjusted to L port position) 6. After the display has changed, CP4 retains the following output states now in order to fix the 100 % position (for L port) of the unloader slide valve. Y01: Oil pump ON Y02: Unloader slide valves increase solenoid valve ON Y04: Unloader slide valves decrease solenoid valve OFF Y07: Vi slide valves increase solenoid valve OFF Y08: Vi slide valves decrease solenoid valve ON Press the TAB key to set SLIDE VALVE MAXIMUM value when the position of the unloader slide valve has become 100.0 %. NOTE: The processing does not advance to the next step unless the SLIDE VALVE Location value is larger than the value for the 100 % position of the unloader slide valve at the H port and also the Vi Location value is smaller than the value for the Vi slide valve at the H port.

(Screen while SLIDE VALVE MAXIMUM is being set)

7.

After you have pressed the TAB key, CP4 retains the following output states now in order to bring the unloader slide valve back to the fully unloaded position. Y01: Oil pump ON Y02: Capacity increase solenoid valve OFF Y04: Capacity decrease solenoid valve ON Y07: Vi slide increase solenoid valve OFF Y08: Vi slide decrease solenoid valve OFF (After the unloader slide valve has returned to the fully unloaded position, CP4 set all the above outputs to OFF. The SLIDE VALVE SETUP window closes and the display returns to the ADJUSTMENT menu.)

(Screen showing the unloader slide valve being brought to the fully unloaded position automatically)

- 65 -

QT108300

Setup operations in the SLIDE VALVE SETUP window involve actual operation of the oil pump. Check for safety in the compressor area before pressing the keys.

NOTE: Pressing the ESC key at any time can cancel the setup procedure halfway.

5.2 Settings in SET TIME Windows (Option 2 of ADJUSTMENT Menu (F5))


When you open the SET TIME window, three sub-windows with the following titles appear on the screen: SET TIME, DISPLAY TIMER, and OTHER TIMER. These sub-windows allow you to make settings related to the date/time and timers.

- 66 -

QT108300

Items in SET TIME Windows


Sub-window Title Item Description Press ENTER key after selecting this item. Second count will change to 00 of the nearest minute as follows: The second count from 0 to 29 will adjust to 00 with the minute count unchanged. The second count from 30 to 59 will adjust to 00 with the minute count advanced by one. Select a day of week from the setting options. Enter the number for current month (1 for January, 2 for February, and so on). Enter the number for the current date. Enter the number for the current year. Enter the number for the current hour. Enter the number for the current minute. Enter the number for the current second. This item is for setting the time before the menus and windows automatically close (default setting: 8 minutes). A function menu and a window, if opened, will be closed upon the lapse of the set time unless a key on the front panel is pressed before the time expires. NOTE: If 0 is set, the menus and windows remain opened regardless of the time. This item is for setting the time before the screen backlight automatically goes out (default setting: 10 minutes). The backlight will turn off upon the lapse of the set time unless a key on the front panel is pressed before the time expires. NOTE: - The backlight will light again if you press any of the front panel keys. - If 0 is set, the backlight remains on regardless of the time. This item is for setting a desired time during which the entered password remains valid (default: 30 minutes). The entered password, if it is correct, remains valid until the set time expires. PASSWORD LIFE NOTE: - Entry of the password is requested again before you can open a window after the expiration of the time. - If 0 is set, the password remains valid regardless of the time. This item is for setting the time of sampling interval for the trend log. The number of sampling points for the trend log is fixed at 1,440. This means the time over which the sampling is made becomes longer as you set a longer time as the interval. You can set 0 or any time between 1 and 21,600 seconds. OTHER TIMER TREND LOG NOTE: If 0 is set for the interval, data will not be updated. Example: - When the interval is set to 60 seconds (1 minute), the trend log time becomes 24 hours. - When the interval is set to 1 second, the trend log time becomes 24 minutes.

30SEC

SET TIME

WEEK MONTH DAY YEAR HOUR MINUITE SECOND

CLOSE MENU

DISPLAY TIMER

BACK LIGHT OFF

- 67 -

QT108300

5.3 Settings in PASSWORD Window (Option 3 of ADJUSTMENT Menu (F5))


This window allows you to change any of the previously registered LEVEL-1 to LEVEL-3 passwords. First, enter the old password in the brackets [ ] under OLD on the old appropriate line. If the password you entered is valid, you are authorized to enter a new password in the corresponding brackets under NEW. For the method of the entry, see Section 3.3 To Make Setting Entry Using Keys.

You can also invalidate the currently valid password (i.e., to designate it to LEVEL-0). To do this, first press the SAVE key while no window is open. The window shown below will appear.

If you certainly desire to invalidate the password, then select YES using the appropriate arrow key and press the ENTER key to confirm the selection. The password will then be brought to LEVEL-0 and be invalidated. You have to then press the ESC key to close the window, as it is not closed automatically. If you want to stop the invalidation, then simply select NO. The window automatically closes and the original password remains valid.

- 68 -

QT108300

5.4 Settings in ANALOG INPUT ADJUSTMENT Window (Option 4 of ADJUSTMENT Menu (F5))
This window allows you to adjust the offset and filter coefficient values that are needed for proper indication and processing of each analog input data.

Item Headings in ANALOG INPUT ADJUSTMENT Window


Item Heading CH. DESCRIPTION Description Under this heading, the display shows a list of the analog input items assigned to the individual channels. If you enter positive or negative values in the LOW and HIGH brackets under this heading, CP4 makes scaling after adding these values to actual analog input data and use them as actual measurements. (see NOTE below) Positive or negative LOW and HIGH values may be up to 50 % of full scale. If you decrease this value, the processing responses more quickly to change in actual measurements but has more influence of noise and other interferences. The reverse is true when you increase this value. Any number between 0.00 and 0.99 can be entered. Select CH. 1 - 16 or CH. 17 - 32; the items for 16 channels are displayed for each selection. Under this heading, values represented in industrial units are indicated. These values reflect the offset calculation made to the FILTER COEFFICIENT values and scaling. NOTE: The diagram to the left shows the case in which the displayed values are too small in the entire
OFFSET HIGH

OFFSET

FILTER COEFFICIENT CHANEL SELECT PROCESS VALUE

Displayed process value Maximum value in sensor range

measurement

range.

To

make

the

values

appropriate for display, positive numbers should be entered in both LOW and HIGH brackets. If the displayed values are too large over the entire range, negative numbers must be entered.

Minimum value in sensor range OFFSET LOW 0% Actual process value 100

- 69 -

QT108300

5.5 Settings in ANALOG OUTPUT ADJUSTMENT Window (Option 5 of ADJUSTMENT Menu (F5))
This window allows you to adjust the offset value for analog outputs. The adjustment is possible only when an optional digital-to-analog converter board (AO board) is installed. The offset values have already been adjusted before shipment from the factory and the adjustments are retained in the non-volatile random access memory on the AO board. Use this window if fine adjustment to the preset values is needed.

Item Headings in ANALOG OUTPUT ADJUSTMENT Window


Item Heading OUT OFFSET Description Displays the current output (in %) with offset value incorporated. The offset values are incorporated in the calculated analog output values to create actual output values. Any values up to 10.0 can be set for LOW and HIGH offset values.

If the output values are too small over the entire range, enter positive numbers as both the LOW and HIGH offset values. Enter negative numbers in the opposite case. If you perform special booting, it becomes possible to enter a value in the OUT brackets (indicating the current output percentage) to make the value be output as an actual output. To make this entry, first perform special booting and then select the ANALOG OUTPUT ADJUSTMENT window (Option 5 of ADJUSTMENT menu (F5)). This selection, however, is impossible if an optional DA board is not installed.

- 70 -

QT108300

5.6 Settings in ANALOG OUTPUT ASSIGNMENT Window (Option 6 of ADJUSTMENT Menu (F5))
This window allows you to make new channel assignments or change the existing assignments for analog outputs. This window cannot be selected if no optional AO board is installed.

NOTE: In the following table, the assignments for the items in parentheses ( ) are valid if the associated optional inputs are available.

Item in ANALOG OUTPUT ASSIGNMENT Window


Heading Title DIRECTION (Polarity) DIRECT REVERSE NOT USE A/O01 REPLACEMENT Item Description Controller outputs 0 to 100% are output as 4 to 20 mA DC signals. Controller outputs 0 to 100% are output as 20 to 4 mA DC signals. Not used If the analog output item having been assigned to A/O01 is to be reassigned to another channel, selecting A/O01 REPLACEMENT during the setting for the new channel automatically reassigns the item to the new channel. If the analog output item having been assigned to A/O02 is to be reassigned to another channel, selecting A/O02 REPLACEMENT during the setting for the new channel automatically reassigns the item to the new channel. If the item having been assigned to A/O03 is to be reassigned to another channel, selecting A/O03 REPLACEMENT during the setting for the new channel automatically reassigns the item to the new channel. If the item having been assigned to A/O04 is to be reassigned to another channel, selecting A/O04 REPLACEMENT during the setting for the new channel automatically reassigns the item to the new channel. Outputs actual suction pressure measurements at AI01. Outputs actual discharge pressure measurements at AI02. Outputs actual oil supply pressure measurements at AI03. Outputs actual after-filter-pressure measurements at AI04. Outputs actual suction temperature measurements at AI05. Outputs actual discharge temperature measurements at AI06. Outputs actual oil supply temperature measurements at AI07. Outputs actual oil separator temperature measurements or after-fine-filter pressure measurements at AI08. Outputs actual intermediate pressure measurements or optional input at AI09.

A/O02 REPLACEMENT

A/O03 REPLACEMENT

ASSIGNMENT A/O04 REPLACEMENT SUCTION PRESSURE DISCHARGE PRESSURE OIL SUPPLY PRESSURE AFTER FILTER PRESSURE SUCTION TEMPERATURE DISCHARGE TEMPERATURE OIL SUPPLY TEMPERATURE ( OIL SEPARATOR TEMPERATURE ) ( AFTER FINE FILTER PRESSURE ) ( INTERMEDIATE PRESSURE ) ( OPTION */4 )

- 71 -

QT108300

Item in ANALOG OUTPUT ASSIGNMENT Window (continued)


Heading Title Item ( INTERMEDIATE TEMPERATURE ) ( OPTION */4 ) ( SYSTEM DISCHARGE PRESSURE ) ( OPTION */4 ) COMPRESSOR MOTOR CURRENT ( CHILLER ENTERING PROCESS TEMPERATURE ) ( OPTION */4 ) ( CHILLER LEAVING PROCESS TEMPERATURE ) ( OPTION */4 ) ( LOW STAGE ) SLIDE VALVE POSITION (( HIGH STAGE ) SLIDE VALVE POSITION) ( SLIDE VALVE OIL PRESSURE ) ( SYSTEM SUCTION PRESSURE ) ( OPTION */4 ) ( SUCTION PRESSURE1 ) ( CILLER LEAVING GAS TEMPERATURE ) ( SYSTEM SUCTION PRESSURE ) ( REMOTE SLIDE VALVE POSITION INPUT ) ( OPTION */4 ) ( OPTION */4 ) ( OPTION */4 ) ( OPTION */4 ) ( SUCTION PRESSURE2 ) ( CHILLER GAS TEMPERATURE2 ) INVALID OIL DIFFERENTIAL PRESSURE FILTER DIFFERENTIAL PRESSURE DIFFERENTIAL PRESSURE SUCTION SUPERHEAT ( INTERMEDIATE SUPERHEAT ) DISCHARGE SUPERHEAT ( DISCHARGE/SUCTION PRESSURE RATIO ) ( CALCULATED Vi ) ( Vi POSITION ) ( COMPRESSOR CAPACITY ) ( SLIDE VALVE PERCENT ) ( AUTO STAGE TARGET PRESSURE ) ( OIL DEFFERENTIAL PRESSURE2 ) Description Outputs actual intermediate temperature measurements or optional input at AI10. Outputs actual system discharge pressure measurements at AI11. Outputs actual compressor motor current measurements at AI12. Outputs actual measurements of chiller inlet temperature or of optional input from AI13. Outputs actual chiller outlet temperature measurements or optional input at AI14. Outputs actual low-stage capacity measurements at AI15. Outputs actual measurements of high-stage slide valve position, slide valve oil pressure, system suction pressure, or optional input at AI16. Outputs actual measurements of evaporator gas outlet pressure at AI17. Outputs actual measurements of evaporator gas outlet temperature at AI18. Outputs actual system suction pressure measurements at AI19. Outputs actual measurements of remote slide valve position input at AI20. Outputs actual optional input measurements at AI21. Outputs actual optional input measurements at AI22. Outputs actual optional input measurements at AI23. Outputs actual optional input measurements at AI24. Outputs actual measurements of evaporator gas outlet pressure 2 at AI25. Outputs actual measurements of evaporator gas outlet temperature 2 at AI26. No default assignments for inputs at AI27 to AI32. Outputs calculated oil differential pressure (OP-DP) at VAI01. Outputs calculated filter differential pressure (DP-AFP) at VAI02. Outputs calculated differential pressure (AFP-SP or AFP-IP) at VAI03. Outputs calculated suction superheat (ST-SP saturation temperature or GT1-SP1 saturation temperature) at VAI04. Outputs calculated intermediate superheat (IT-IP saturation temperature) at VAI05. Outputs calculated discharge superheat (DT-DP saturation temperature) at VAI06. Outputs discharge pressure divided by suction pressure at VAI07. Outputs calculated Vi at VAI08. Outputs Vi position at VAI09. Outputs compressor capacity at VAI10. Outputs percent position of slide valve at VAI11. Outputs suction pressure for automatic staging control at VAI12. Outputs calculated oil differential pressure 2 (slide valve oil supply pressure (SVOP) discharge pressure (DP)) at VAI13. Outputs calculated suction superheat 2 (chiller gas temperature (GT) 2 suction pressure (SP) 2 saturation temperature) at VAI14. No default assignments for inputs at VAI15 to VAI16

ASSIGNMENT (continued)

( SUCTION SUPERHEAT2 ) INVALID

- 72 -

QT108300

Item in ANALOG OUTPUT ASSIGNMENT Window (continued)


Heading Title Item CAPACITY CONTROL PID OUT ( CAPACITY-CONTROL PID OUT ) Description Outputs manipulating value for low-stage capacity control based on suction pressure control at REG01. Outputs manipulating value for low-stage capacity control based on process output control at REG02. Outputs one of the following values whichever is the minimum: - Manipulating value of evaporator expansion valve for suction superheat control at REG03, - Manipulating value of limiter for suction pressure control at REG04, and - Manipulating value of limiter for process outlet temperature control at REG05 Outputs manipulating value of intercooler YOSAKU expansion valve for intermediate superheat control at REG06. Outputs manipulating value of liquid injection YOSAKU expansion valve for discharge temperature or discharge superheat control at REG07. Outputs manipulating value for process flow rate control based on process outlet temperature control at REG08. Outputs manipulating value for condenser fan speed control based on discharge pressure control at REG09. Outputs manipulating value for high-stage capacity control based on intermediate pressure control at REG10. Outputs manipulating value for VFD control based on suction pressure control at REG11. Outputs manipulating value for VFD control based on process outlet temperature control at REG12. Outputs one of the following values whichever is the minimum: - Manipulating value of evaporator expansion valve for suction superheat 2 control at REG13, and - Manipulating value of limiter for suction pressure 2 control at REG14 Outputs manipulating value of flow rate regulator valve for liquid level control at REG15. No default assignment for input at REG16.

( SUCTION SUPERHEAT CONTROL PID OUT )

( INTERMEDIATE SUPERHEAT CONTROL PID OUT ) ( LIQUID INJECTION CONTROL PID OUT ) ASSIGNMENT (continued) ( CHILLER LEAVING TEMPERATURE CONTROL PID OUT ) ( DISCARGE PRESSURE CONTROL PID OUT ) ( HIGH STAGE CAPACITY CONTROL PID OUT ) ( VFD COMPRESSOR CONTROL PID OUT ) ( VFD-COMPRESSOR CONTROL PID OUT )

INVALID

( LEVEL CONTROL PID OUT ) INVALID

- 73 -

QT108300

5.7 Settings in AUXILIARY INPUT TIMER Window (Option 7 of ADJUSTMENT Menu (F5))
This window allows you to make timer settings for various digital ON/OFF inputs at the auxiliary input channels.

NOTE: In the following table, INTERLOCK-3 is valid only when the associated optional function is provided.

Items in AUXILIARY INPUT TIMER Window


Window Title Item Description This item is for setting the limit delay time until the operation confirmation input at DI-12 (X0B) turns ON after the operation command output at DO-01 (Y00) has turned ON during the startup sequence of the compressor. If the operation confirmation input does not turn ON even after the limit time, START FAIL alarm is issued. This item is for setting the limit time for which the operation confirmation input at DI-12 (X0B) may remain OFF during operation of the compressor. If the operation confirmation input remains OFF longer than the limit time, START FAIL alarm is issued. This item is for setting the limit delay time until the operation confirmation input at DI-12 (X0B) turns OFF after the operation command output at DO-01 (Y00) has turned OFF during the shutdown sequence of the compressor. If the operation confirmation input does not turn off even after the limit time, START FAIL alarm is issued. This item is for setting the limit time for which the signal from auxiliary input 1 at DI-12 (X0B) may remain OFF during operation of the compressor. If the input signal remains OFF longer than the limit time, Interlock1 Failure alarm is issued. This item is for setting the limit time for which the signal from auxiliary input 2 at DI-14 (X0D) may remain OFF after the oil pump operation command output at DO-02 (Y01) has turned ON. If the signal remains OFF even after the limit time, Interlock2 Failure alarm is issued. When chiller pump is not used: If the signal from auxiliary input 3 at DI-15 (X0E) remains OFF longer than the limit time you set for this item after all operating conditions of the compressor has been met, then Interlock3 Failure alarm is issued. When chiller pump is used: If the signal from auxiliary input 3 at DI-15 (X0E) remains OFF longer than the limit time you set for this item after the chiller pump operating command at DI-19 (Y12) has turned ON, then Interlock3 Failure alarm is issued. - 74 -

COMP. MSRB (Starting)

COMP. MSRB (Running)

COMP. MSRB (Stopping)

AUXILIARY INPUT TIMER

INTERLOCK-1 (Auxiliary input 1)

INTERLOCK-2 (Auxiliary input 2)

( INTERLOCK-3 ) (Auxiliary input 3)

QT108300

5.8 Adjustments in COMMUNICATION SETUP Window (Option 8 of ADJUSTMENT Menu (F5))


This window allows you to make all necessary settings for each communication port.

NOTE: Settings for communication ports COM2 and COM3 are possible only when an optional extension board is installed.

Items in COMMUNICATION SETUP Window


Item COMMUNICATION ADDRESS Description Select START to make communications active for the port being set. Select STOP to deactivate communications for the port. Enter different one of the numbers from 0 to 99 as the station number for each CP4 constituting a communication control network. Select a baud rate from among the options: 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, and 115,200. NOTE: Determine the baud rate so that the total of the baud rates for all communication ports of one CP4 does not exceed 192,000 bps. Select a desired combination of character format specifications to apply to the communications established. You can select a one from a total of 12 combination options: Data length: 7 or 8 bits Parity check: None, Odd, or Even Stop bit: 1 or 2 bits

RATE (Data transmission speed)

FORMAT (Communication character format)

- 75 -

QT108300

Items in COMMUNICATION SETUP Window (continued)


Item MODBUS RTU MODBUS ASCII Description Selecting this protocol allows the remote communication device to read/write data from/into the devices of CP4 using MODBUS RTU (binary data) protocol. Selecting this protocol allows the remote communication device to read/write data from/into the devices of CP4 using MODBUS ASCII (ASCII data) protocol. Selecting this choice activates the communication protocol specially used for the AUTO STAGE optional automatic staging control (AUTO STAGE). This option is selectable only for communication port 0 (COM0). If this protocol is selected, the terminal software on the remote personal computer can receive all TREND LOG data displayed in the TREND LOG window (Option 1 of LOGS menu (F4)) in the form of a file by using 1k-Xmodem protocol. This option is selectable only for communication port 0 (COM0). Selecting protocol allows the terminal software on the remote personal computer to display the screen of CP4 and makes it possible to control the CP4 through the keyboard TERMINAL of the computer. In addition, the remote personal computer can receive all data displayed in TREND LOG window (Option 1 of LOGS menu (F4)) in the form of a file by using 1k-Xmodem protocol. This option is not selectable for communication port 0 (COM0). Selecting this CP3 protocol allows the remote communication device to read/write data from/into PROTOCOL 0 devices of CP4 by using MYPRO-CPIII protocol 0. This option is not selectable for communication port 0 (COM0). Selecting this CP3 protocol allows the remote communication device to read/write data from/into PROTOCOL 1 devices of CP4 by using MYPRO-CPIII protocol 1. This item is for setting the delay time until a response is sent from CP4 after it has received a command from the communication master station (remote communication device). (You can set any delay time between 0 and 100 milliseconds at 10 millisecond increments.) This setting is possible only for communication port 0 (COM0). Select either of the following options, whichever is appropriate as the type of communication line connection. DIRECT: Communication line is connected directly to the remote computer. MODEM: Communication line is connected to the remote computer via a MODEM. This setting is possible only for communication port 0 (COM0). When LOG is selected for this item, transmission of all the data displayed in TREND LOG window (Option 1 of LOGS menu (F4)) will be started by using the 1k-Xmodem protocol if you put the cursor on TERMINAL at the terminal software on the remote computer and press the ENTER key. (This function works only when TERMINAL has been selected for the PROTOCOL item and RUN has been selected for the COMMUNICATION item.)

PROTOCOL

RESPONSE (Response delay) WIRING (Type of communication connections)

TERMINAL (Trend log transmission command)

- 76 -

QT108300

Chapter 6 Control Selections (SETPOINTS Menu (F1))


6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))
This window allows you to make settings related to the operation control modes of the compressor unit(s).

Items in OPERATION MODE Window


Item Description Select the operation control mode of the compressor unit(s) from the following options: LOCAL: Start/stop control of the compressor unit is performed using the START and STOP keys on the front panel. REMOTE: Start/stop control of the compressor unit is performed by ON/OFF of external command through DI-16 (X0F). COMM: Start/stop control of the compressor unit(s) is performed by ON/OFF commands (X140) from a remote control device through communications. AUTO STAGE: Start/stop control of the compressor units is performed according the commands (see Section 8.2.4 MODBUS Protocol) sent from the master station (see Section 6.7 Settings in AUTO STAGE Window (Option 7 of SETPOINTS Menu (F1)) for the automatic staging control). This mode is selectable only when the automatic staging control (option) is provided. The setting for this item is necessary to enable or disable the automatic start/stop (CUT IN/CUT OUT) control that takes place according to the settings made in the SET POINTS window (see Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))). YES:Automatic CUT IN/CUT OUT control is enabled. NO:Automatic CUT IN/CUT OUT control is disabled. The setting for this item is necessary to enable or disable manual intervention on the digital ON/OFF outputs for testing purposes. To be able to select YES, you must have selected LOCAL for the OPERATION item and NO for the COMPRESSOR AUTO START/STOP item in the above. D/O TEST OPERATION YES:Manual intervention is enabled. NO:Manual intervention is disabled. NOTE: About the manual ON/OFF control of the compressor, see Section 6.2 Manual Control from D/O TEST OPERATION Window (Option 2 of SETPOINTS Menu (F1)).

OPERATION

COMPRESSOR AUTO START/STOP

- 77 -

QT108300

According to the selection for the OPERATION item in the OPERATION MODE window, the following conditions automatically take place when the STOP key is pressed on the front panel of PC4. When the LOCAL, REMOTE, or COMM mode (not the AUTO STAGE mode) has been selected, pressing the STOP key causes no change to the operation control mode in the case of the LOCAL mode, but the mode automatically changes to LOCAL in the case of the REMOTE and COMM modes. The compressor, if operating, will then stop after the liquid recovering sequence. (It remains stopped thereafter.) To restart the compressor, simply press the START key if you need not change the mode from LOCAL to another, or turn ON the relevant operation control command after changing the mode from LOCAL to the desired mode. When the AUTO STAGE mode has been selected, pressing the STOP key does not cause any change to the setting for the OPERATION item in the OPERATION MODE window, but the selection of ENABLE you made for the CONTROL item in the AUTO STAGE window automatically changes to DISABLE. In this case, if the compressor under control is running when the STOP key is pressed, the compressor will then stop after completing the liquid recovering sequence. Even the STOP key is pressed on the master station and its CONTROL item setting in the AUTO STAGE window is consequently changed to DISABLE, the automatic staging control continues to work on all the other stations (slave stations). To recover the AUTO STAGE mode control after pressing the STOP key, it is necessary (for the case of the master station and the case of a slave station) to perform the steps below. (Simply pressing the START key on the station does not recover the automatic staging control.) 1. From the SETPOINTS menu (F1), open the AUTO STAGE window. 2. Select ENABLE for the CONTROL item in the window.

6.2 Manual Control from D/O TEST OPERATION Window (Option 2 of SETPOINTS Menu (F1))
Using the D/O TEST OPERATION window, you can monitor the ON/OFF state of each digital input/output. This window can also be used for testing the condition of digital ON/OFF outputs by manually turning them ON/OFF. Both monitoring and testing using this window is possible when the following conditions are all met: - LOCAL is selected for the OPERATION item in the OPERATION MODE window (see Section 6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))). - The compressor is in a stopped state (the state of operation confirmation input (MSRB) at DI-12 (X0B) is OFF). - NO is selected for the COMPRESSOR AUTO START/STOP item in the OPERATION MODE window (see Section 6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))). - YES is selected for the D/O TEST OPERATION item in the OPERATION MODE window (see Section 6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))).

- 78 -

QT108300

(The above screen shows the case with the standard digital input/output assignments.) Monitoring the ON/OFF state of digital outputs/inputs When white characters are displayed against a blue background, the corresponding digital outputs are in the OFF state. When blue characters are displayed against a white background, the corresponding digital outputs are in the ON state. When gray characters are displayed against a blue background, the corresponding digital inputs are in the OFF state. When blue characters are displayed against a gray background, the corresponding digital inputs are in the ON state. Manually turning ON/OFF the selected digital output Select the desired digital output channel by moving the cursor () with the right/left arrow keys on the front panel. (Only an output channel can be selected). Then use the SAVE or ENTER key as follows: - If you press the SAVE key, the selected digital output turns ON and OFF alternately each time you press the key. - If you press the ENTER key, the selected digital output turns ON momentarily. The output remains ON while the key is held pressed. NOTE: When this D/O TEST OPERATION window is closed, all the states you have changed in this window are cleared (all digital outputs are set to OFF).

For the sake of safety, the following design considerations are incorporated: Only the momentary turning ON of output by the use of the ENTER key is permitted for the compressor operation command (COMP) output at DO-01 (Y00). (Alternating ON and OFF with the SAVE key is impossible.) If the operation confirmation input (MSRB) at DI-12 (X0B) turns ON while the compressor operation command output at DO-01 (Y00) is being momentarily turned ON by pressing the ENTER key, the compressor operation command output at DO-01 (Y00) automatically turns OFF.

- 79 -

QT108300

6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))


This window includes four sub-windows, entitled SYSTEM START, MISCELLANEOUS, PUMP OUT, and SET POINTS. These sub-windows allow you to make settings of parameters related to compressor operation.

Items in SET POINTS Window


Sub-window Title SYSTEM START Item SYSTEM START DELAY CUT IN DELAY (Compressor start delay time) CUT OUT DELAY (Compressor stop delay time) CUT OUT LSV% (Compressor stop capacity) OIL P. START DELAY MISCELLANEOUS (Settings for start-up) COMP. START DELAY Description Set the delay time before start of the system after turning ON of the operation command for each of the operation control mode. Set the delay before the CUT IN control is actually performed after a rise exceeding the CUT IN value for the CUT IN/OUT control target. Set the delay before the CUT OUT control is actually performed after a drop exceeding the CUT OUT value for the CUT IN/OUT control target. Set the minimum low-stage capacity at which compressor operation command at DO-01 (Y00) turns OFF. Set the delay before turning ON of oil pump start command at DO-02 (Y01) after system startup. Set the delay before turning ON of compressor operation command at DO-01 (Y00) after turning ON of oil pump start command at DO-02 (Y01). Set the delay before the restart check sequence begins when the compressor fails to start with the unloader slide valve at 5% or higher position. Set the delay before the oil return solenoid valve at DO-09 (Y08) turns OFF after turning OFF of compressor start command at DO-01 (Y00). NOTE: This item is displayed only when PRE LUBE is selected for the OIL FEED TYPE item in the SYSTEM SETUP window (Option 1 of SETUP Menu (F6)). YES: Enables a stop only when the low-stage capacity is 0% after liquid recovery sequence. NO: Enables a stop even when the low-stage capacity is not 0% after liquid recovery sequence. Set the minimum delay before liquid recovery sequence terminates for when suction pressure drops below the liquid recovery termination suction pressure set for PUMP OUT PRESS below. NOTE: Setting for MINIMUM DELAY must be smaller than setting for MAXIMUM DELAY.

COMP. RE-START DELAY

OIL FEED OFF DELAY

CAPACITY 0% STOP (Stop when low-stage capacity is 0 %) PUMP OUT (Settings for liquid recovery sequence)

MINIMUM DELAY (Minimum delay before termination of liquid recovery sequence)

- 80 -

QT108300

Items in SET POINTS Window (continued)


Sub-window Title Item Description Set the maximum delay before liquid recovery sequence terminates for when suction pressure remains above the liquid recovery termination suction pressure.

PUMP OUT

SET POINTS

MAXIMUM DELAY (Minimum delay before termination of liquid recovery sequence) NOTE: Setting for MINIMUM DELAY must be smaller than setting for MAXIMUM DELAY. PUMP OUT PRESS Set the suction pressure at which the liquid recovery sequence (Liquid recovery termination terminates. suction pressure LSV% Set the low-stage capacity of the compressor during the liquid (Low-stage slide valve position recovery sequence. during liquid recovery sequence) STOP LSV% Set the low-stage capacity of the compressor at the end of liquid (Low-stage slide valve position at recovery sequence. end of liquid recovery sequence) Set an operation starting value during automatic operation (a CUT IN SETPOINT pressure or temperature value according to the selection made for the CONTROL TARGET (CUT IN/OUT) item in the OPTION (Start value during automatic operation) SETUP 1/2 window (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)))). Set a value for capacity control during operation (a pressure or temperature value according to the selection made for the CONTROL TARGET (CAPACITY CONTROL) item in the OPTION SETUP 1/2 window (see Section 4.4 Settings in CONTROL PRESS. OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (Value for capacity control during (F6)))). operation) NOTE: The setting for this item is valid when the capacity control is set to automatic. (It is invalid for manual capacity control.) Set an operation stopping value during automatic operation (a pressure or temperature value according to the selection made for the CONTROL TARGET (CUT IN/OUT) item in the OPTION SETUP 1/2 window (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)))).

CUT OUT SETPOINT (Stop value during automatic operation)

NOTE: In the SET POINTS sub-window, you can enter a specific value under each of the SET POINT numbers 1 to 4 (indicated as SETPT #1 to SETPT #4 on the display). The entered values are associated with these numbers and the numbers can be used for setting in the SCHEDULER window (see Section 6.4). (The values under COMM are the set values written from the remote station through communications. These values become valid when COMM is selected for the OPERATION item in the OPERATION MODE window (see Section 6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))). They cannot be changed from the front panel using numeral keys.) In the SCHEDULER window, you specify any of numbers SETPT #1 to #4 in combination with the schedule patterns to program a schedule for automatic operation control of the compressor so that the compressor can be operated at different settings depending on the day of week and time in a day. (For the method of specifying the set point numbers, see Section 6.4 Settings in SCHEDULER Window (Option 4 of SETPOINTS Menu (F1)).)

6.4 Settings in SCHEDULER Window (Option 4 of SETPOINTS Menu (F1))


The SCHEDULER window includes a total of eight sub-windows: SCHEDULER (ASSIGN DAYS) and SCHEDULE 1, SCHEDULE 2, SCHEDULE 3, SCHEDULE 4, SCHEDULE 5, SCHEDULE 6, and SCHEDULE 7. (The last seven sub-windows present schedule patterns.) By making entries in these sub-windows, you can program a compressor operation schedule according which operation of the compressor is controlled automatically. During the programming, you select an appropriate one of the numbers (SETPT #1 to #4) to which different pressure or temperature settings are associated in the SET POINTS window (see Section 6.3) for both automatic starting/stopping (CUT IN

- 81 -

QT108300

/ CUT OUT) control and automatic capacity control. After this, you allot the selected number to each day of the week and each time of the day. In these sub-windows, you can also make ALARM / FAILURE selection and assignment using one of the numbers (#1 and #2) to which different warning points are associated in the ALARM/FAILURE windows (see Section 7.1 Settings in ALARM/FAILURE Windows 1/3 to 3/3).

Items in SCHEDULER Windows


Sub-window Title Item Description SUNDAY to SATURDAY Assign one of the schedule pattern numbers (SCHEDULE1 to SCHEDULE7) (Schedule number to each day of the week. assignment) If YES is selected for the COMPRESSOR AUTO START/STOP item in the OPERATION MODE window (see Section 6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))), CP4 makes automatic start/stop (CUT IN / CUT OUT) control according to your selection from the following options: SET POINT #1: Setting for SETPT #1 in SET POINTS window (Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) is always used. SET POINT #2: Setting for SETPT #2 in SET POINTS window (Section 6.3 Settings in SET POINTS Window (Option 3 of CUT IN / CUT OUT SETPOINTS Menu (F1))) is always used. (CUT IN / CUT OUT SET POINT #3: Setting for SETPT #3 in SET POINTS window (Section number selection) 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) is always used. SET POINT #4: Setting for SETPT #4 in SET POINTS window (Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) is always used. SCHEDULER: SETPT #1 to SETPT #4 settings are used as you have programmed for a scheduled automatic control. COMM: Settings written by the remote computer through communications are used.

SCHEDULER (ASSIGN DAYS)

- 82 -

QT108300

Items in SCHEDULER Windows (continued)


Sub-window Title Item Description CP4 makes automatic capacity control of the compressor according to your selection from the following options: SET POINT #1: Setting for SETPT #1 in SET POINTS window (Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) is always used. SET POINT #2: Setting for SETPT #2 in SET POINTS window (Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) is always used. CONTROL TARGET SET POINT #3: Setting for SETPT #3 in SET POINTS window (Section (Capacity control number 6.3 Settings in SET POINTS Window (Option 3 of selection) SETPOINTS Menu (F1))) is always used. SET POINT #4: Setting for SETPT #4 in SET POINTS window (Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) is always used. SCHEDULER: SETPT #1 to SETPT #4 settings are used as you have programmed for a scheduled automatic control. COMM: Settings written by the remote computer through communications are used. SET POINT #1: ALARM/FAILURE warning is issued based on the settings made for ALARM #1 and FAILURE #1 in ALARM/FAILURE window (Section 7.1 Settings in ALARM/FAILURE ALARM/FAILURE Windows 1/3 to 3/3). (Alarm number selection) SET POINT #2: ALARM/FAILURE warning is issued based on the settings made for ALARM #2 and FAILURE #2 in ALARM/FAILURE window (Section 7.1 Settings in ALARM/FAILURE Windows 1/3 to 3/3). Assign one of the SETPT #1 to SETPT #4 settings (made in the SET POINTS window (Section 6.3)) to each of the schedule patterns SCHEDULE 1 to SCHEDULE 7. If YES is selected for the COMPRESSOR AUTO START/STOP item in the OPERATION MODE SET# window (see Section 6.1 Settings in OPERATION MODE Window (Option 1 (SET POINT # selection) of SETPOINTS Menu (F1))), CP4 makes both automatic start/stop (CUT IN / CUT OUT) and automatic capacity control from the first START time to the START time of the time segment (time span) specified below it according to your set point assignment by a number (one of #1 to #4). Divide a day into 8 time segments and enter the start time of each time segment in hours and minutes to program a schedule for a day of the week. (The end of the time segment is the START time entered on the bottom line.) If YES is selected for the COMPRESSOR AUTO START/STOP item START in the OPERATION MODE window (see Section 6.1 Settings in (start time setting) OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))), CP4 makes both automatic start/stop (CUT IN / CUT OUT) and automatic capacity control from the first START time according to your set point assignment by a number (one of #1 to #4).

SCHEDULER (ASSIGN DAYS)

SCHEDULER (ASSIGN DAYS) (continued)

SCHEDULE1 to 7 (Schedule patterns)

NOTE: - You cannot specify the same time for different START times within the same SCHEDULE number. - If you divide a day into segments of smaller number than eight, set the same number in SET # of two or more time segments. (The same number is set for all SET # by default.) - Any set time must be earlier than that on the next lower line. Otherwise, time entries are not accepted.

- 83 -

QT108300

6.5 Setting in OTHER SETPOINT Window (Option 5 of SETPOINTS Menu (F1))


This window includes three sub-windows, ANTI CYCLE, OIL HEATER, and OIL DRAIN SV. They allow you to set the anti-cycle timer and other parameters for optional functions.

NOTE: The displayed items may be different from those shown above depending on the setting.

Items in OTHER SETPOINT Window


Sub-window Title Item ANTI CYCLE TIME (Restart prohibition time) INTERVAL TIME (Operation-to-operation interval) HEATER ON OS (Oil heater ON temperature) HEATER OFF OS (Oil heater OFF temperature) SV OFF DELAY (Oil drain solenoid valve OFF delay) INTERVAL (Interval operation) Description Set the time after start of the compressor during which the start for the next operation is prohibited. (This limits the number of start/stop times in a unit time.) Set the time from the end of a compressor operation to the start of the next operation. (This limits the stop-to-start interval.) Set an oil separator temperature at which OIL HEATER output at DO-07 (Y06) turns ON. Set an oil separator temperature at which OIL HEATER output at DO-07 (Y06) turns OFF. Set the delay before OIL DRAIN SV at DO-09 (Y08) turns OFF after turning OFF of compressor operation command at DO-01 (Y00). Select either of the following options concerning interval operation of the oil pump. DISABLE (Interval operation disabled) ENABLE (Interval operation enabled) Select either of the following options in which interval operation of the oil pump is to be enabled. AUTO ONLY: Enabled only when YES is selected for the COMPRESSOR AUTO START/STOP item (see Section 6.1). ALL: Enabled only when NO is selected for the COMPRESSOR AUTO START/STOP item (see Section 6.1). NOTE: Setting for this item is valid only when ENABLE is selected for the INTERVAL item.

ANTI CYCLE *1

OIL HEATER *2

OIL DRAIN SV *3

SEAL PROTECTION *4 (Oil pump operation for protecting oil seals)

AUTO ONLY/ALL (Operation mode subjected to oil pump interval operation)

- 84 -

QT108300

Items in OTHER SETPOINT Window (continued)


Sub-window Title Item Description Set the interval at which the oil pump is operated. (Interval operation of the oil pump takes place when the count of compressor non-operation time is longer than the time set here.) NOTE: Setting for this item is valid only when ENABLE is selected for the INTERVAL item. Set the length of running time for each interval operation of the oil pump. PUMP RUN (Oil pump running time) NOTE: Setting for this item is valid only when ENABLE is selected for the INTERVAL item in the above. Select either of the following options to determine whether to allow or not a delay before start of the oil pump after stopping of the compressor. DISABLE: Delay is not allowed. ENABLE: Delay is allowed. Set the delay before the oil pump stops after turning OFF of the compressor operation command at DO-01 (Y00). NOTE: Setting for this item is valid only when ENABLE is selected for the COMP. STOP item in the above. Set the delay before the start bypass solenoid valve is deenergized after operation confirmation input at DI-12 (X0B) turns ON. Set the low-stage capacity at which the hot gas bypass solenoid valve turns ON. Set the low-stage capacity at which the hot gas bypass solenoid valve turns OFF. Set the delay before the hot gas bypass solenoid valve turns ON after the low-stage capacity has reached the set value. Set the suction pressure at which the hot gas bypass solenoid valve turns ON. Set the delay before the hot gas bypass solenoid valve turns ON after the suction pressure has reached the set value.

SEAL PROTECTION (Oil pump operation for protecting oil seals) (continued)

*4

START PERIOD (Oil pump operation interval)

SEAL PROTECTION *4 (Oil pump operation for protecting oil seals)

COMP. STOP (Operation of oil pump after stop of compressor)

OIL PUMP DELAY

STARTING BYPASS SV *5 (Start bypass solenoid valve)

HOT GAS BYPASS SV *6 (Hot gas bypass solenoid valve)

SV OFF DELAY (Delay before solenoid valve turns OFF) SV ON LSV% (Capacity at which solenoid valve turns ON) SV OFF LSV% (Capacity at which solenoid valve turns OFF) SV ON DELAY (LSV%) (Delay before solenoid valve turns ON) SV ON SP (Pressure at which solenoid valve turns ON) SV ON DELAY (SP) (Delay before soienoid valve turns ON)

NOTE: *1 Any settings for ANTI CYCLE are invalid if, in the OPERATION MODE window (Section 6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))), LOCAL is selected for the OPERATION item and NO is selected for the COMPRESSOR AUTO START/STOP item. *2 Display of and setting for the items in the OIL HEATER sub-window is possible only when NORTH AMERICA is selected for the I/O PLATFORM item in the SYSTEM SETUP window (see Section 4.1 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6))). *3 Display of and setting for the item in the OIL DRAIN SV sub-window is possible only when NORTH AMERICA is selected for the I/O PLATFORM item and COMPOUND-2 (2016 & HIGHER) is selected for the COMPRESSOR item, both in the SYSTEM SETUP window (see Section 4.1 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6))). *4 Display of and setting for the items in the SEAL PROTECTION sub-window is possible only when USE is selected for the COMPRESSOR OIL SEAL PROTECTION item in the OPTION SETUP 1/2 window (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))).

- 85 -

QT108300

*5

Display of and setting for the item in the STARTING BYPASS SV sub-window is possible only when USE is selected for the STARTING BYPASS CONTROL item in the OPTION SETUP 1/2 window (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))).

*6

Display of and setting for the items in the HOT GAS BYPASS SV sub-window is possible only when USE is selected for the HOT GAS BYPASS CONTROL item in the OPTION SETUP 1/2 window (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))). The hot gas bypass solenoid valve turns ON when the following conditions are concurrently met during operation of the compressor: The capacity remains equal to or smaller than the value set for SV ON LSV% for the period set for SV ON DELAY (LSV%). The suction pressure remains equal to or smaller than the value set for SV ON SP for the period set for SV ON DELAY (SP). The hot gas bypass solenoid valve turns OFF when the capacity becomes equal to or larger than the value set for SV OFF LSV%.

6.6 Settings in AUTO Vi Window (Option 6 of SETPOINTS Menu (F1))


This window (consisting of two sub-windows) allows you to set the parameters related to the automatic Vi control function (option). Installation of an extension digital input/output board is required to use the automatic Vi control function according to the selection you make in the OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))). (The extension digital input/output board is required if USE DO10, 11, 12, 16, 17 (UD-V) or USE DO19, 1A, 1B, 1C, 1D (UD-V) is selected for the AUTO Vi CONTROL item in the window.) The following table shows the Vi-related data displayed on the Main Status Screen, together with the function menu, windows, and items that show these data. COMPRESSOR in SYSTEM SETUP window (Option 1 of SETUP menu (F6)) SINGLE UD-V(VARIABLE Vi) SINGLE J, SINGLE J ECONOMIZER W/O SENSOR, SINGLE J ECONOMIZER W/ SENSOR AUTO Vi CONTROL in OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) NOT USE USE J SERIES

- 86 -

QT108300

Unloader slide valve position (absolute value) Percentage (relative value) of unloader slide valve for currently selected port position

These sub-windows appear when one of SINGLE J, SINGLE J ECONOMIZER W/O SENSOR, SINGLE J ECONOMIZER W/ SENSOR, and SINGLE UD-V (VARIABLE Vi) is selected for COMPRESSOR in SYSTEM SETUP window (see Section 4.1).

Items in AUTO Vi Window


Sub-window Title AUTO Vi CONTROL (MONITOR) (Status display) Item CURRENT Vi (Vi for current port) CALCULATED Vi (Calculated Vi value) INITIAL Vi (Port for initial Vi control) Description Indicates the Vi value of the unloader slide valve in currently selected port position Indicates the current calculated Vi value. Select one of the following as the port from which automatic Vi control is started. 2.63(L) or 2.50(L) *: L port 3.65(M) or 3.50(M) *: M port 5.80(H) or 5.00(H) *: H port Set the frequency (time) at which sampling is made to determine the need for port switching. Set the number of samples for determining the need for port switching.

AUTO Vi CONTROL (SETPOINT) (Setting display)

AUTO Vi CONTROL (SETPOINT) (Setting display) (continued)

SAMPLE DELAY (Vi calculation cycle) SAMPLE QUANTITY (number of Vi samples) CONFIRM DELAY * (Delay before confirmation of port Set the delay before confirmation of the port position. position) MOVE DELAY Set the delay before switching of port. (Delay before change of Vi position) CONTROL * Select either fixing to L, M, or H port or automatic Vi control. (Selection of Vi port control)

NOTE: The items and options marked * are displayed when SINGLE J, SINGLE J ECONOMIZER W/O SENSOR, or SINGLE J ECONOMIZER W/ SENSOR is selected for the COMPRESSOR item in the SYSTEM SETUP window (see Section 4.1 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6))). They are not displayed if SINGLE UD-V (VARIABLE Vi) is selected.

- 87 -

QT108300

6.7 Settings in AUTO STAGE Window (Option 7 of SETPOINTS Menu (F1))


This window (consisting of two sub-windows) allows you to make parameter settings concerning the automatic staging control (an optional function that automatically increase or decrease the number of working screw compressor units in the system according to load and other conditions). An extension communication board (option) may be required according to the specification of your CP4 to implement the automatic staging functions. CP4 Configuration for Automatic Staging (AUTO STAGE) Control The automatic staging control involves multiple CP4s that are inter-connected through the standard communication port (COMM1) or optional communication port (COMM2 or COMM3) on each CP4. One of these CP4s is assigned to the master station and the others to the slave stations. Based on its own start/stop settings and the data from the pressure or temperature inputs associated with these settings, the master station determines the compressor units to be operated or stopped either in the AUTO mode (where the priority is determined according to the operation time (the station having the shortest operation time is given the top priority)) or in the MANUAL mode (where the priority is determined according to the pre-established listing of station addresses). The master station then sends start/operation and capacity-fixing commands to the slave stations that control the corresponding compressor units one after another. Starting Control The master station issues a start/operation command to the slave station of the highest priority if a pressure or temperature in its own compressor unit exceeds the corresponding target setting. Control to Increase the Number of Operating Units The slave station that has received the operation command from the master station starts operating its compressor unit. The slave station then uses the master stations capacity control values and the pressure/temperature data it receives continuously from the master station as its own to make capacity control (normal capacity control) of its compressor unit. When the capacity of the compressor unit in operation under the control of the slave station has reached its setting for capacity control upper limit (manipulating value high limit (MVH%)), the master station sends a command for fixing the capacity to the station and then issues a start command to the slave station of the next lower priority. Likewise, the number of working compressor units is increased as conditions are met one by one subsequently. Consequently, only the slave station that has last received a start command continues the capacity control according to the varying value data from the master station, while the capacity control values of all the other slave stations of working compressor units are fixed to the preset maximum values of the stations. Control to Decrease the Number of Operating Units When the capacity of the compressor unit in operation under control of the last-started (or the lowest-priority) slave station reaches its setting for capacity control lower limit (manipulating value low limit (MVL%)), the master station cancels the capacity-fixing command being sent until then to the slave station of the next higher priority and instead permits it making the normal capacity control. When the second lowest-priority station that has received the normal capacity control permission goes below the setting for its stoppage threshold (SV HOLD PREVIOUS), the master station cancels the operation command for the next lower priority station (the lowest-priority station), thus stopping the compressor unit under the control of the last-priority station. Likewise, the number of working compressor units is decreased one by one subsequently as conditions are met.

- 88 -

QT108300

Control for Stopping All Units The master station sends a stop command to all slave stations when any of the pressure or temperature inputs indicates a value exceeding the preset value.

The above screen is displayed only when you have selected USE for the AUTO STAGER item in the OPTION SETUP 1/2 window (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))). NOTE: In the following table, *M, *S, and *A indicate the following: *M: Selection or setting is enabled only on the master station. On a slave station, the relevant item is displayed but selection or setting is impossible. *S: Selection or setting is enabled only on a slave station. On the master station, the relevant item is displayed but selection or setting is impossible. *A: Selection or setting is enabled on both the master and slave stations.

- 89 -

QT108300

Items in AUTO STAGE Window


Sub-window Title Item Description Set the communication address of the master/slave station. (This setting can be changed when DISABLE is selected for the CONTROL item below.) 0: No automatic staging control is implemented at any station (communications between stations are disabled). 1: The station with address 1 assigned becomes the master station. 2 to 99: The station with any of these numbers assigned becomes a slave station. DISABLE: Automatic staging control is disabled. ENABLE: Automatic staging control is enabled. (When this option is selected, the settings for some of the related items become unchangeable.) Select either of the following options as the mode used for determining the starting priorities of compressor units. MANUAL: Priority is fixed to the setting for the LIST ADDRESS on the line below the priority numbers on the LIST (MANUAL) line. AUTO: Different priorities are automatically given to different stations according to their operation times (the station with the shortest operation time is given the top priority). This line displays the starting priority numbers used when MANUAL is selected for the LEAD LISTING item in the above. When MANUAL is selected for the LEAD LISTING item in the above, enter the station address numbers under the appropriate starting priority numbers each. This item normally displays the start (CUT IN) set point of the compressor unit controlled by the master station. (Either a pressure or temperature value is displayed according to the setting for the CONTROL TARGET (CUT IN / CUT OUT) item in the OPTION SETUP 1/2 window (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)))). The set point displayed here is the one set on the master station using the SETPOINT window (Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) and the SCHEDULER window (Section 6.4 Settings in SCHEDULER Window (Option 4 of SETPOINTS Menu (F1))). Displayed for this item on a slave station is the data sent from the master station through communications. Set the delay before one additional slave station compressor is started after the CUT IN / CUT OUT control target has exceeded the CUT IN set point. Displayed on a slave station for this item is the data sent from the master station through communications. This item normally displays the capacity control setting of the compressor unit controlled by the master station. (Either a pressure or temperature value is displayed according to the setting for the CONTROL TARGET (CONTROL) item in the OPTION SETUP 1/2 window (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)))). The set point displayed here is the one set on the master station using the SETPOINT window (Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) and the SCHEDULER window (Section 6.4 Settings in SCHEDULER Window (Option 4 of SETPOINTS Menu (F1))). Displayed on a slave station for this item is the data sent from the master station through communications. This item shows the current pressure or temperature value according to the control target selected on the master station for the CONTROL TARGET (CAPACITY CONTROL) item (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))).

ADDRESS *A (Communications address)

CONTROL *A (AUTO STAGE control)

LEAD LISTING *M (Starting priorities)

LIST (MANUAL) (Display of starting priorities) LIST ADDRESS *M (Setting starting priorities)

AUTO STAGE CUT IN SET POINT (Setting starting values)

DELAY *M (Delay before start of an additional compressor unit)

CONTROL SETPOINT (Capacity control set values)

TARGET (Current value of control target)

- 90 -

QT108300

Items in AUTO STAGE Window (continued)


Sub-window Title Item Description This item normally displays the CUT OUT set point of the compressor unit controlled by the master station. (Either a pressure or temperature value is displayed according to the setting for the CONTROL TARGET (CUT IN / CUT OUT) item in the OPTION SETUP 1/2 window (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)))). The set point displayed here is the one set on the master station using the SETPOINT window (Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1))) and the SCHEDULER window (Section 6.4 Settings in SCHEDULER Window (Option 4 of SETPOINTS Menu (F1))). Displayed on a slave station for this item is the data sent from the master station through communications. Set the delay before determining stoppage of all slave station compressors after dropping of CUT IN / CUT OUT control target value to or below the CUT OUT set value. The data displayed on a slave station for this item is the data sent from the master station through communications. Either PRESSURE or TEMPERATURE is displayed (master station) or selectable (slave stations). The display on the master station for this item shows PRESSURE or TEMPERATURE according the selection made in the CONTROL TARGET (CUT IN / OUT) item in the SYSTEM SETUP window (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))). On slave stations, select PRESSURE or TEMPERATURE whichever is the same as the selection the display on the master station. If the selection made on a slave station is different from (that) on the master station, incorrect CUT IN and CUT OUT set points will be displayed. Either PRESSURE or TEMPERATURE is displayed (master station) or selectable (slave station). On the master station, the display for this item shows PRESSURE or TEMPERATURE according to the selection made in the CONTROL TARGET (CAPACITY CONTROL) item in the SYSTEM SETUP window (Section 4.1 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6))). On slave stations, select PRESSURE or TEMPERATURE whichever is the same as the selection on the master station. If the selection made on a slave station is different from that on the master station, incorrect capacity control set points will be displayed. If USER DEFINED is selected for the REFRIGERANT item in the SYSTERM SETUP window (see Section 4.1), any selection for this item is impossible although its display is provided. This item is valid when TEMPERATURE is selected for the CONTROL TARGET (CAPACITY CONTROL) item (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))). Enter an appropriate negative value on slave stations. The master station only displays this item. Set the capacity of the compressor for the station using which the stoppage of the compressor of the next- lower- priority station is determined. Any setting is unacceptable if it exceeds the valve of the percentage set for MVH%-5.0% in CAPACITY RAMP CONTROL (F2). (see Section 8.1.2 Compressor Capacity Control Settings in CAPACITY CONTROL Window (Option 1 of CONTROLLER Menu (F2))) This item displays the starting priority in an ascending order, beginning with 1 at the top. This item displays the communication addresses of the stations corresponding to the starting priority numbers assigned. This item displays the current capacity of the compressor controlled by each station both numerically and in the form of a bar graph.

CUT OUT SET POINT (Displaying stop set values)

DELAY *M (Setting stop delay time)

CUT IN/OUT & *S CONTROL (Pressure/temperature display and selection for CUT IN and CUT OUT values) AUTO STAGE (continued)

CUT IN/OUT & CONTROL *S (Pressure/temperature display and selection for compressor capacity control values)

APPROACH T *S

SV HOLD PREVIOUS *A

MONITOR (State display)

LEAD (Starting priority) LIST (Communications address list) LOAD% (Current compressor capacity)

- 91 -

QT108300

Items in AUTO STAGE Window (continued)


Sub-window Title Item Description This item displays the current state of each station using the following words. UNKNOWN : Slave station which is not registered or does not respond to master station STOPPED : Stopped ANTI CYCLE : Stopped with restart restricted AUTO STOP : Automatically stopped PRE CUT IN : Compressor in preparation for start PRE SYSTEM : System in preparation for start PRE START : In preparation for start START : Started RUN : Running PRE CUT OUT : Compressor in preparation for stopping PUMP OUT : Liquid recovering in progress RUN MVH : Running with capacity at upper limit RUN MVL : Running with capacity at lower limit RUN UNDER HOLD : Below stop determination capacity READY TO RUN : Preparing for operation READY TO STOP : Preparing for stop FAILURE : FAILURE (critical alarm) occurred Displays the current operation control mode of each station. UNKNOWN : Slave station which is not registered or does not respond to the master station STAGE-OFF : Operation command from master station is OFF STAGE-ON : Operation command from master station is ON Displays the operating time count of the compressor unit controlled by each station.

STATE MONITOR (State display) (continued)

MODE (Operation command) RUN TIME HRS (Operation time count)

Selection of Pressure or Temperature Values as Control Targets for Start/Stop Control (CUT IN/OUT & CONTROL) and Capacity Control (CUT IN/OUT & CONTROL)
To implement the automatic staging control, you should use either pressure or temperature values as the control targets for both start/stop (CUT IN / CUT OUT) control and capacity (CONTROL) control. Using pressure or temperature values as the target values is determined depending on the combination of the selections you make for the following four items in both the OPTION SETUP 1/2 window (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))) and the AUTO STAGE window (this section): - Selection for the CONTROL TARGET (CUT IN/OUT) item in the OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) - Selection for the CONTROL TARGET (CAPACITY CONTROL) item in the OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) - On slave stations, selection of the CUT IN/OUT side for the CUT IN/OUT & CONTROL item in the AUTO STAGE window (Option 7 of SETPOINTS menu (F1)) - On slave stations, selection of the CONTROL side for the CUT IN/OUT & CONTROL item in the AUTO STAGE window (Option 7 of SETPOINTS menu (F1))

- 92 -

QT108300

a.

When pressure values are used for the start/stop (CUT IN/OUT) control: Select LOCAL SUCTION PRESSURE or SYSTEM SUCTION PRESSURE on the master station as follows. Selection Item Selection on Master Station Selection on Slave Station LOCAL SUCTION PRESSURE (When DISABLE is selected for AUTO STAGING (see Section 4.6 Settings in OPTION SELECT Window (Option 6 of SETUP Menu (F6))), the compressor unit automatically starts/stops upon reach to the LOCAL SUCTION PRESSURE value.) PRESSURE must be selected to match with the selection on the master station. Not used for control

The CONTROL TARGET (CUT IN/OUT) item in the OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) The CUT IN/OUT side of the CUT IN/OUT & CONTROL item in the AUTO STAGE window (Option 7 of SETPOINTS menu (F1)) APPROACH T in the AUTO STAGE window (this window) b.

LOCAL SUCTION PRESSURE SYSTEM SUCTION PRESSURE

or

PRESSURE is automatically selected. Unchangeable

When temperature values are used for the start/stop (CUT IN/OUT) control: Select CHILLER LEAVING BRINE TEMPERATURE or CHILLER ENTERING BRINE TEMPERATURE on the master station. (Slave stations have no CHILLER LEAVING BRINE TEMPERATURE and CHILLER ENTERING BRINE TEMPERATURE sensors.) Selection Item Selection on Master Station Selection on Slave Station LOCAL SUCTION PRESSURE (When DISABLE is selected for AUTO STAGING (see Section 4.6 Settings in OPTION SELECT Window (Option 6 of SETUP Menu (F6))), the compressor unit automatically starts/stops upon reach to the LOCAL SUCTION PRESSURE value.) TEMPERATURE must be selected to match with the selection on the master station. Any temperature value (negative value)

The CONTROL TARGET (CUT IN/OUT) item in the OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) The CUT IN/OUT side of the CUT IN/OUT & CONTROL item in the AUTO STAGE window (Option 7 of SETPOINTS menu (F1)) APPROACH T in the AUTO STAGE window (this window) (see NOTE) NOTE:

CHILLER LEAVING BRINE TEMPERATURE or CHILLER ENTERING BRINE TEMPERATURE

TEMPERATURE selected. Unchangeable

is

automatically

If the automatic staging control on a slave station becomes invalid due to interferences or other communication disturbances, the automatic start/stop control is continued using the saturation pressure value derived from the following two equations as the set value for the LOCAL SUCTION PRESSURE. [CUT IN SET POINT temperature setting written last by the master station] + [APPROACH T value] and [Set temperature for CUT OUT SET POINT] + [APPROACH T value] Therefore, you should enter an appropriate negative value. Any negative value can be input if it is within 20 % of the range. The range here means the measurable range of the temperature sensor selected for the CONTROL TARGET (CUT IN/OUT) item in the OPTION SETUP window (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))). (Normally, a temperature sensor measureable of temperatures between -50.0 and +50.0 C (i.e. 100 C in range) is used. So a temperature between -20 to +20.0 C can be set as the APPROACH T value.)

- 93 -

QT108300

c.

When pressure values are used for the capacity control: Select LOCAL SUCTION PRESSURE or SYSTEM SUCTION PRESSURE on the master station as follows. Selection Item Selection on Master Station Selection on Slave Station LOCAL SUCTION PRESSURE (When DISABLE is selected for AUTO STAGING (see Section 4.6 Settings in OPTION SELECT Window (Option 6 of SETUP Menu (F6))), the capacity of the compressor unit is controlled using the LOCAL SUCTION PRESSURE value.) PRESSURE must be selected match with the selection on the master station. Not used for the control.

The CONTROL TARGET (CAPACITY CONTROL) item in the OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) The CONTROL side of the CUT IN/OUT & CONTROL item in the AUTO STAGE window (Option 7 of SETPOINTS menu (F1)) APPROACH T in the AUTO STAGE window (this window) d.

LOCAL SUCTION PRESSURE SYSTEM SUCTION PRESSURE

or

PRESSURE is automatically selected. Unchangeable

When temperature values are used for the capacity control: Select CHILLER LEAVING BRINE TEMPERATURE. (Slave stations have no chiller leaving brine temperature sensors.) Selection Item Selection on Master Station Selection on Slave Station LOCAL SUCTION PRESSURE (When DISABLE is selected for AUTO STAGING (see Section 4.6 Settings in OPTION SELECT Window (Option 6 of SETUP Menu (F6))), the capacity of the compressor unit is controlled using the LOCAL SUCTION PRESSURE value.) TEMPERATURE must be selected to match with the selection on the master station. Any temperature (negative value)

The CONTROL TARGET (CAPACITY CONTROL) item in the OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) The CONTROL side of the CUT IN/OUT & CONTROL item in the AUTO STAGE window (Option 7 of SETPOINTS menu (F1)) APPROACH T in the AUTO STAGE window (this window). (see NOTE) NOTE:

CHILLER LEAVING TEMPERATURE

BRINE

TEMPERATURE selected. Unchangeable

is

automatically

If the automatic staging control on a slave station becomes invalid due to interferences or other communication disturbances, the capacity control is performed using the saturation pressure value derived from the following equation as the set values for the LOCAL SUCTION PRESSURE. [CONTROL IN SET POINT temperature setting written last by the master station] + [APPROACH T value] Therefore, you should enter an appropriate negative value. Any negative value can be input if it is within 20 % of the range. The range here means the measurable range of the temperature sensor selected for the CONTROL TARGET (CAPACITY CONTROL) item in the OPTION SETUP window (Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))). (Normally, a temperature sensor of a measureable range of between -50.0 to +50.0 C (i.e. 100 C) is used. So a temperature between -20 to +20.0 C can be set as the APPROACH T value.)

- 94 -

QT108300

Chapter 7 Alarms (LIMITS Menu (F3))


7.1 Settings in ALARM/FAILURE Windows 1/3 to 3/3
The ALARM/FAILURE windows can be accessed from the LIMITS menu by selecting Options 1 to 3. Windows ALARM/FAILURE 1/3 and ALARM/FAILURE 2/3 allow you to set two sets of values (ALARM #1 and #2 values and FAILURE #1 and #2 values) for each of all the items that require alarm settings except for optional analog inputs. Which of the #1 and #2 values is used depends on the selections you make for the ALARM/FAILURE item in the SCHEDULER window (see Section 6.4 Settings in SCHEDULER Window (Option 4 of SETPOINTS Menu (F1))). When making alarm settings for optional analog inputs, use the ALARM/FAILURE 3/3 window. NOTE: - ALARM refers to non-critical alarms that do not involve a compressor shutdown. The ALARM/FAILURE display area on the screen shows a message in dark red if any alarm of this type is issued. FAILURE refers to critical alarms that involve a compressor shutdown. The ALARM/FAILURE display area on the screen shows a message in red if any alarm of this type is issued. - OEM LIMITS refers to the upper or lower limit of each alarm set value. See Section 7.2 Settings in OEM LIMITS 1/2 and OEM LIMITS 2/2 Windows (Options 4 and 5 of LIMITS Menu (F3)) for setting of OEM LIMITS values.

7.1.1
NOTE:

ALARM/FAILURE 1/3 Window

- No alarm is issued if you set the same value for both FAILURE and ALARM. - No OEM LIMITS setting is possible in this window (see Section 7.2).

Indicates that #1 setting is selected.

ALARM/FAILURE display

- 95 -

QT108300

NOTE: Setting and display of the parenthesized items in the following table is optionally available.

Items of ALARM/FAILURE 1/3 Window


Item RE-START/TIMEOUT HIGH MA LOW SP DELAY MASK TIME HIGH SP DELAY (HIGH IP) (LOW OP2) HIGH DP LOW OP (LOW OP (OP - SP)) LOW P MASK TIME HIGH OF DELAY (HIGH FF) (DELAY) HIGH ST DELAY/ /MASK TIME HIGH DT HIGH OT (LOW OS) (MASK TIME) (LOW EB) (LOW LB) Description Set a period of time during which whether a RE-START ALARM is to be issued or not is determined. Set compressor motor overcurrent alarm point. Set low suction pressure alarm point. Set delay before low suction pressure alarm is issued. Set the mask time until low suction pressure alarm is issued after start of compressor. (This setting works for both ALARM and FAILURE.) Set high suction pressure alarm point. Set delay before high suction pressure alarm is issued. Set high intermediate pressure alarm point. Set point at which low OP2 slide valve oil differential pressure ([slide valve oil pressure] [discharge pressure]) alarm is issued. Set high discharge pressure alarm point. Set point at which low OP oil differential pressure ([oil pressure] [discharge pressure]) alarm is issued. Set point at which low OP oil differential pressure ([oil pressure] [suction pressure]) alarm is issued. Set P low alarm point. P is as defined below: Single-stage compressor: P = [after-oil-filter pressure] [suction pressure] Two-stage compressor: P = [after-oil-filter pressure] [intermediate pressure] Set a period of time during which P low alarm is to be masked after start of compressor. (This setting works for both ALARM and FAILURE.) Set point at which FP high alarm is issued. FP = [discharge pressure] [after-oil-filter pressure] Set delay before FP high alarm is issued. (This setting works for both ALARM and FAILURE.) Set point at which FFP high alarm is issued. FFP = [discharge pressure] [after-fine-filter pressure] Set delay before FFP high alarm is issued. (This setting works for both ALARM and FAILURE.) Set point at which high suction temperature alarm is issued. Set delay before high suction temperature alarm is issued. (This setting works for both ALARM and FAILURE.) Set period during which high suction temperature alarm is masked after start of compressor. (This setting works for both ALARM and FAILURE.) Set point at which high discharge temperature alarm is issued. Set point at which high oil temperature alarm is issued. Set point at which low oil separator temperature alarm (ALARM) is issued. Set period during which low oil separator temperature alarm (ALARM) is masked after start of compressor. (This setting works also for P MASK TIME.) Set point at which low chiller inlet process temperature alarm (ALARM) is issued. Set point at which low chiller outlet process temperature alarm is issued.

- 96 -

QT108300

7.1.2
NOTE:

ALARM/FAILURE 2/3 Window

- No ALARM is issued if you set the same value for both FAILURE and ALARM. - No OEM LIMITS setting is possible in this window (see Section 7.2).

Indicates that #1 setting is selected.

ALARM/FAILURE display

NOTE: Setting and display of the parenthesized items in the following table is optionally available.

Items of ALARM/FAILURE 2/3 Window


Item LOW SSH CANCEL/ /DELAY (LOW SH2) (CANCEL/) (/DELAY) (LOW ISH) LOW DSH DELAY MASK TIME (LOW CHILLER LEVEL) DELAY/ /MASK TIME Description Set point at which low suction superheat alarm is issued. Set point at which low suction superheat ALARM is cancelled. (Cancellation occurs with a fixed delay of 15 seconds). Set delay before low suction superheat FAILURE is issued. (In the case of ALARM, the delay time is fixed at 30 seconds.) Set point at which low suction superheat 2 alarm is issued. Set point at which low suction superheat 2 ALARM is cancelled. (Cancellation occurs with delay fixed at 15 seconds.) Set delay before low suction superheat 2 FAILURE is issued. (In the case of ALARM delay time is fixed at 30 seconds.) Set point at which low intermediate superheat alarm is issued. Set point at which low discharge superheat alarm is issued. Set delay before low discharge superheat alarm is issued. Set period during which low discharge superheat ALARM is masked after start of compressor. Set point at which low liquid level ALARM is issued. Set delay before low liquid level ALARM is issued. Set period during which low liquid level ALARM is masked after start of compressor.

- 97 -

QT108300

7.1.3

ALARM/FAILURE 3/3 Window

The ALARM/FAILURE 3/3 window allows you to set a HIGH or LOW threshold of ALARM/FAILURE alarm for each optional analog input. After the lapse of the specified masking time following the start of the compressor, an ALARM/FAILURE alarm is issued with the preset delay if the optional analog input value exceeds the HIGH or LOW limit set here. This window cannot be selected for display from the LIMITS menu if no ALARM/FAILURE is assigned to any analog input in the OPTION ANALOG INPUT window (Option 3 of the SETUP menu (F6); see Section 4.3 Settings in OPTION ANALOG INPUT Window (Option 3 of SETUP Menu (F6))). Unlike the alarms for standard analog input items handled in windows ALARM/FAILURE 1/3 and ALARM/FAILURE 2/3 where two values (#1 and #2) are preset for each of the items, only one value is set for each ALARM/FAILURE alarm item in the case of optional analog inputs. Another difference of ALARM/FAILURE alarms for optional analog inputs is that they are issued even when you set the same value for both FAILURE and ALARM. NOTE: No OEM LIMITS setting is possible with optional analog inputs for ALARM/FAILURE.

ALARM/FAILURE display

Items of ALARM/FAILURE 3/3 Window


Item LOW OPT1 DELAY/ /MASK TIME HIGH OPT1 DELAY/ /MASK TIME LOW OPT2 DELAY/ /MASK TIME HIGH OPT2 DELAY/ /MASK TIME LOW OPT3 DELAY/ /MASK TIME HIGH OPT3 DELAY/ Description Set point at which low OPT1 alarm is issued (OPT1 = option analog input 1). Set delay before low OPT1 alarm is issued (OPT1 = option analog input 1). Set period during which low OPT1 alarm is masked after start of compressor (OPT1 = option analog input 1). (This setting works for both ALARM and FAILURE.) Set point at which high OPT1 alarm is issued (OPT1 = option analog input 1). Set delay before high OPT1 alarm is issued (OPT1 = option analog input 1). Set period during which high OPT1 alarm is masked after start of compressor (OPT1 = option analog input 1). (This setting works for both ALARM and FAILURE.) Set point at which low OPT2 alarm is issued (OPT2 = option analog input 2). Set delay before low OPT2 alarm is issued (OPT2 = option analog input 2). Set period during which low OPT2 alarm is masked after the start of compressor (OPT2 = option analog input 2). (This setting works for both ALARM and FAILURE.) Set point at which high OPT2 alarm is issued (OPT2 = option analog input 2). Set delay before high OPT2 alarm is issued (OPT2 = option analog input 2). Set period during which high OPT2 alarm is masked after start of compressor (OPT2 = option analog input 2). (This setting works for both ALARM and FAILURE.) Set point at which low OPT3 is issued (OPT3 = option analog input 3). Set delay before low OPT3 alarm is issued (OPT3 = option analog input 3). Set period during which low OPT3 alarm is masked after start of compressor (OPT3 = option analog input 3). (This setting works for both ALARM and FAILURE.) Set point at which high OPT3 alarm is issued (OPT3 = option analog input 3). Set delay before high OPT3 alarm is issued (OPT3 = option analog input 3).

- 98 -

QT108300

Items of ALARM/FAILURE 3/3 Window (continued)


Item /MASK TIME LOW OPT4 DELAY/ /MASK TIME HIGH OPT4 DELAY/ /MASK TIME Description Set period during which high OPT3 alarm is masked after start of the compressor (OPT3 = option analog input 3). (This setting works for both ALARM and FAILURE.) Set point at which low OPT4 alarm is issued (OPT4 = option analog input 4). Set delay before low OPT4 alarm is issued (OPT4 = option analog input 4). Set period during which low OPT4 alarm is masked after start of compressor (OPT4 = option analog input 4). (This setting works for both ALARM and FAILURE.) Set point at which high OPT4 alarm is issued (OPT4 = option analog input 4). Set delay before high OPT4 alarm is issued (OPT4 = option analog input 4). Set period during which high OPT4 alarm is masked after start of compressor (OPT4 = option analog input 4). (This setting works for both ALARM and FAILURE.)

7.2 Settings in OEM LIMITS 1/2 and OEM LIMITS 2/2 Windows (Options 4 and 5 of LIMITS Menu (F3))
These windows (shown as ALARM/FAILURE & OEM LIMITS 1/2 and ALARM/FAILURE & OEM LIMITS 2/2 on the screen) allow you to set the upper and lower limits (OEM limits) of each ALARM/FAILURE setting. To access to these windows, you must perform special booting and enter the LEVEL-2 password (see Section 3.5 Special Booting for details about the password). NOTE: - ALARM refers to non-critical warnings that do not involve a compressor shutdown. The ALARM/FAILURE display area on the screen shows a message in dark red if any warning of this type is issued. - FAILURE refers to critical warnings that involve a compressor shutdown. The ALARM/FAILURE display area on the screen shows a message in red if any warning of this type is issued.

7.2.1

ALARM/FAILURE & OEM LIMITS 1/2 Window

This window allows you to set ALARM/FAILURE values in addition to OEM LIMITS values. The items displayed in this window are the same as those in the ALARM/FAILURE 1/3 window. See the description on the window in Section 7.1.1 ALARM/FAILURE 1/3 Window. NOTE: No alarm is issued if you set the same value for both FAILURE and ALARM.

Indicates that #1 setting is selected.

ALARM/FAILURE display

- 99 -

QT108300

7.2.2

ALARM/FAILURE & OEM LIMITS 2/2 Window

This window allows you to set ALARM/FAILURE values in addition to OEM values. The items displayed in this window are the same as those in the ALARM/FAILURE 2/3 window; see Section 7.1.2 ALARM/FAILURE 2/3 Window for information on the window. NOTE: No alarm is issued if you set the same value for both FAILURE and ALARM.

Indicates that #1 setting is selected.

ALARM/FAILURE display

7.3 Settings in RANGE OVER Window (Option 6 of LIMITS Menu (F3))


This window allows you to set the period of time during which an over-range / under-range alarm condition is to be detected and also the mask time during which a failure condition is not detected for each sensor. If settings are made for the individual sensors listed in this window, you can identify a sensor to be faulty if it is sending data showing a value above the upper limit (more than 95 % of the full scale) or below the lower limit (less than 5 % of the full scale). If zero (0) is entered in the [ ] SEC space for a sensor under the FAILURE DELAY item, no alarm is issued for the sensor.

ALARM/FAILURE display area

- 100 -

QT108300

Items in RANGE OVER Window


Item FAILURE MASK TIME Description No sensor alarm conditions are detected during this period of time after the start of compressor operation. PRESSURE SENSOR Set the failure mask time for the pressure sensor. TEMPERATURE SENSOR Set the failure mask time for the temperature sensor. Set the delay before output of alarm for each sensor. FAILURE DELAY (VALUE 0 INVALIDATES) (If it is set to 0, no alarm is issued for the sensor.) SUCTION PRESSURE OVER Upper limit alarm of suction pressure sensor at AI-01 DISCHARGE PRESSURE UNDER Lower limit alarm of discharge pressure sensor at AI-02 OIL SUPPLY PRESSURE OVER Upper limit alarm of oil supply pressure sensor at AI-03 AFTER FILTER PRESSURE OVER Upper limit alarm of after-oil-filter pressure sensor at AI-04 SUCTION TEMPERATURE OVER Upper limit alarm of suction temperature sensor at AI-06 SUCTION TEMPERATURE UNDER Lower limit alarm of suction temperature sensor at AI-06 DISCHARGE TEMPERATURE UNDER Lower limit alarm of discharge temperature sensor at AI-07 OIL SUPPLY TEMPERATURE UNDER Lower limit alarm of oil supply temperature sensor at AI-08 (INTERMEDIATE PRESSURE UNDER) *1 Lower limit alarm of intermediate pressure sensor at AI-09 (INTERMEDIATE TEMPERATURE UNDER) *1 Lower limit alarm of intermediate temperature sensor at AI-10 COMPRESSOR MOTOR CURRENT UNDER Lower limit alarm of compressor motor current sensor at AI-12 (LEAVING BRINE TEMPERATURE OVER) *2 Upper limit alarm of brine outlet temperature sensor at AI-14 Upper limit alarm of low stage unloader slide valve position sensor at LOW STAGE SLIDE VALVE POSITION OVER AI-15 LOW STAGE SLIDE VALVE POSITION Lower limit alarm of low stage unloader slide valve position sensor at UNDER AI-15: (HIGH STAGE SLIDE VALVE POSITION Upper limit alarm of high stage unloader slide valve position sensor at *3 OVER) AI-16 (HIGH STAGE SLIDE VALVE POSITION Lower limit alarm of high stage unloader slide valve position sensor at *3 UNDER) AI-16 (CHILLER GAS TEMPERATURE 1 & 2 Lower limit alarm of chiller gas temperature sensor at AI-18 or AI-26 *4 UNDER) (CHILLER GAS TEMPERATURE 1 & 2 OVER) Upper limit alarm of chiller gas temperature sensor at AI-18 or AI-26 *4 (SUCTION PRESSURE 1 & 2 UNDER) *5 (SUCTION PRESSURE 1 & 2 OVER) *5 NOTE: Display and setting of each parenthesized item above is enabled according the option settings you make as follows. *1 Enabled when any of the following is selected for the COMPRESSOR item in the SYSTEM SETUP window (Option 1 of the SETUP menu (F6); Section 4.1 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6))): ECONOMIZER W/ SENSOR COMPOUND-1 (1610 & 1612) COMPOUND-2 (2016 & HIGHER) SINGLE J ECONOMIZER W/ SENSOR FM160 ECONOMIZER W/ SENSOR *2 Enabled when YES is selected for the CHILLER LEAVING TEMP. SENSOR item in the OPTION SETUP 2/2 window (Option 5 of the SETUP menu (F6); Section 4.5 Setting in OPTION SETUP 2/2 Window (Option 5 of SETUP Menu (F6))). *3 Enabled when COMPOUND-2 (2016 & HIGHER) is selected for the COMPRESSOR item in the SYSTEM SETUP window (Option 1 of the SETUP menu (F6); Section 4.1 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6))). *4 *5 Enabled when YES is selected for the CHILLER GAS TEMP. SENSOR item in the OPTION SETUP 2/2 window (Option 5 of the SETUP menu (F6); Section 4.5 Setting in OPTION SETUP 2/2 Window (Option 5 of SETUP Menu (F6))). Enabled when YES is selected for the CHILLER GAS PRESS. SENSOR item in the OPTION SETUP 2/2 window (Option 5 of the SETUP menu (F6); Section 4.5 Setting in OPTION SETUP 2/2 Window (Option 5 of SETUP Menu (F6))). Lower limit alarm of chiller gas pressure sensor at AI-17 or AI-25 Upper limit alarm of chiller gas pressure sensor at AI-17 or AI-25

- 101 -

QT108300

Chapter 8 Operation
8.1 Control of Compressor Unit Operation 8.1.1 Start/Stop Control in Different Operation Control Modes

The start/stop control of the compressor unit is different according to the selection you make for the OPERATION item in the OPERATION MODE window (Option 1 of the SETPOINTS menu (F1); see Section 6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))). LOCAL: REMOTE: COMM: The START/STOP key on the front panel is used to make start/stop control of the compressor unit. Start/stop of the compressor unit is controlled by ON/OFF command inputs at DI-16 (X0F) by an external device. Start/stop of the compressor unit takes place according to ON/OFF commands at X140 transmitted from a remote controlling device through communications. AUTO STAGE: Each of the multiple compressor units operating under automatic staging control (AUTO STAGE; option) is started and stopped according to commands sent from the master station. a. Start: - Press the START key on the front panel of CP4. When the START key is pressed with the compressor in a non-operating condition and without any alarm issued, the system will be activated after a lapse of the SYSTEM START DELAY time*1. - The system starts operating after a lapse of the CUT IN DELAY time following its activation. - The oil pump operation command at DO-02 (Y01) turns ON with a delay of the OIL P. START DELAY time*1, causing the oil pump to start. - After the start of the oil pump, the following points are confirmed in the order of mention within the COMP. START DELAY time*1: The actual measurement of the supply oil differential pressure is larger than the setting for LOW OP alarm (for the LOW
*2 OP MASK TIME) .

Start/stop control in LOCAL mode

The compressors capacity does not exceed 5 %. - The compressor motor operation command at DO-01 (Y00) turns ON. - The compressor motor starts and the compressor operation confirmation input at DI-12 (X0B) turns ON to complete the compressor start sequence. *1 See Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1)). *2 See Section 7.1 Settings in ALARM/FAILURE Windows 1/3 to 3/3. Stop: - Press the STOP key on the front panel of CP4. Liquid recovering sequence starts as soon as the STOP key is pressed while the compressor is in operation. The compressor capacity set for PUMP OUT LSV%*1 is maintained during the liquid recovering operation. - After a delay of the PUMP OUT MINIMUM DELAY time*1, the compressor completes the liquid recovering sequence either after a lapse of the PUMP OUT MAXIMUM DELAY time*1 or after the suction pressure has dropped to the PUMP OUT PRESS pressure*1. At the end of the liquid recovering sequence, the compressor capacity is brought down to 0 % if YES is selected for CAPACITY 0% STOP*1. If NO is selected, the liquid recovering sequence finishes without reducing the compressor capacity to 0 %. - The compressor operation command at DO-01 (Y00) is turned OFF to complete the compressor stop control sequence. *1 See Section 6.3 Settings in SET POINTS Window (Option 3 of SETPOINTS Menu (F1)). - 102 -

QT108300

b.

Start/stop control in REMOTE mode - The compressor is started and stopped according to ON/OFF commands at DI-16 (X0F) from an external device.

c.

Start/stop control in COMM mode - The compressor is started and stopped according to ON/OFF commands at X140 transmitted from a remote computer transmitted through communications.

d.

Start/stop control in AUTO STAGE mode - The master station issues commands to start and stop the compressor units under the control of itself and the individual slave stations to achieve the automatic staging control. The commands are transmitted to each slave station through communications.

According to the selection for the OPERATION item in the OPERATION MODE window, the following conditions automatically take place when the STOP key is pressed on the front panel of PC4. When the LOCAL, REMOTE, or COMM mode (not the AUTO STAGE mode) has been selected, pressing the STOP key causes no change to the operation control mode in the case of the LOCAL mode, but the mode automatically changes to LOCAL in the case of the REMOTE and COMM modes. The compressor, if operating, will then stop after the liquid recovering sequence. (It remains stopped thereafter.) To restart the compressor, simply press the START key if you need not change the mode from LOCAL to another, or turn ON the relevant operation control command after changing the mode from LOCAL to the desired mode. When the AUTO STAGE mode has been selected, pressing the STOP key does not cause any change to the setting for the OPERATION item in the OPERATION MODE window, but the selection of ENABLE you made for the CONTROL item in the AUTO STAGE window automatically changes to DISABLE. In this case, if the compressor under control is running when the STOP key is pressed, the compressor will then stop after completing the liquid recovering sequence. Even the STOP key is pressed on the master station and its CONTROL item setting in the AUTO STAGE window is consequently changed to DISABLE, the automatic staging control continues to work on all the other stations (slave stations). To recover the AUTO STAGE mode control after pressing the STOP key, it is necessary (for the case of the masterstation and the case of a slave station) to perform the steps below. (Simply pressing the START key on the station does not recover the automatic staging control.) 1. From the SETPOINTS menu (F1), open the AUTO STAGE window. 2. Select ENABLE for the CONTROL item in the window.

- 103 -

QT108300

8.1.2

Compressor Capacity Control Settings in CAPACITY CONTROL Window (Option 1 of CONTROLLER Menu (F2))

The sub-windows of the CAPACITY CONTROL window allow you to make the following settings and monitoring related to the capacity control of the compressor. - Setting for the basic capacity control items - Setting for the unloader slide valve positioner - Setting for the capacity control limiters - Monitoring and setting of the upper limit at the start of the capacity control (CAPACITY RAMP CONTROL)

Setting in the CAPACITY CONTROL (MONITOR) sub-window


For the OPERATION item, select appropriate one concerning determination of the capacity from the following options: MANUAL AUTO REMOTE DIGITAL The increase solenoid valve turns ON and OFF when you select MANUAL LOAD using front panel keys. The decrease solenoid valve turns ON and OFF when you select MANUAL UNLOAD. CP4 automatically determines an appropriate compressor capacity according to the pressures or temperatures of the control target. The increase and decrease solenoid valves turn ON and OFF as the relevant digital input turns ON and OFF. (Option setting for REMOTE CAPACITY CONTROL is required (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))).) REMOTE ANALOG The value of the relevant analog input is used as the capacity value. (Option setting for REMOTE CAPACITY CONTROL is required (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))).) COMM The value stored in the relevant register is used as the capacity value.(The value is written in the register through communications.)

Setting in the CAPACITY CONTROL (SETPOINTS) sub-window


Enter an appropriate value (percentage) for the MV (LSV) DEAD BAND item to adjust the positioner function of the low-stage slide valve. If the difference between the setting for the capacity controllers manipulation value PID OUT (MV)% in the CAPACITY CONTROL (MONITOR) sub-window and the current low-stage slide valve position L. SLIDE VALVE exceeds the value for MV (LSV) DEAD BAND, CP4 issues an increase or decrease command to drive the corresponding solenoid valve. In general, the response of the slide valve position to change in manipulation value improves if you set a relatively small value for MV (LSV) DEAD BAND. However, the life of the digital output device becomes shorter since the number of ON/OFF times to energize and de-energize the solenoid valves becomes greater. In addition, if the slide valve must move quickly to meet the setting, not only the number of the ON/OFF times to drive the increase and decrease solenoid valves increases, but also

- 104 -

QT108300

these two valves alternately turn ON and OFF. As a result, it takes too long time before their positions settle. In the worst case, their positions would never settle. The limiter function is mainly for preventing overloading. By setting proper values for the following UNLOAD and LOAD FORBID items, you can limit the capacity increase movement. HI MA UNLOAD Decrease command is continuously issued as long as the compressor motor current is equal to or larger than the set value. HI MA LOAD FORBID No increase command is issued if the compressor motor current is equal to or larger than the set value. HI DP UNLOAD Decrease command is continuously issued as long as the discharge pressure is equal to or larger than the set value. HI DP LOAD FORBID No increase command is issued if the discharge pressure is equal to or larger than the set value. HI IP UNLOAD Decrease command is continuously issued as long as the intermediate pressure is equal to or larger than the set value. (Not displayed according to the option setting (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)))). HI IP LOAD FORBID No increase command is issued if the intermediate pressure is equal to or larger than the set value. (Not displayed according to option setting (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)))). LO SP UNLOAD Decrease command is continuously issued as long as the suction pressure is equal to or smaller than the set value. (This function prevents a drop in suction pressure rather than preventing overloading.) LO SP LOAD FORBID No increase command is issued if the suction pressure is equal to or smaller than the set value. (This function prevents a drop in suction pressure rather than preventing overloading.) CP4 uses the setting you make for the CTRL START DELAY item in this sub-window to allow for the time to keep the capacity at 0 % for the period from the start of compressor operation to the time when the capacity control is started. The setting for the FORCE FULL LOAD item is used to adjust the time until a 100 % load is reached during the forced 100 % operation implemented through communications. The manipulation value of the capacity controller displayed in PID OUT (MV) % starts increasing by the amount set for the FORCE FULL LOAD item every second beginning with the value at the ON time of the corresponding coil (in which data are written through communications). This means that the larger the set value, the shorter the time needed for the manipulating value of the capacity controller to reach 100 %.

Settings in the CAPACITY RAMP CONTROL sub-window


CP4 uses time vales as well as capacity values (expressed in manipulating values (MV)) you have entered in SEC and % for each of the capacity control steps (STEP-1 to STEP-8) in this sub-window in order to prevent the capacity from going beyond the upper limit during the initial period of capacity control.
Controller manipulating value 100.0% MVH%:%-8 %-7 %-6 %-5 %-4 %-3 %-2 %-1 Time Normal operation

MVL%

0.0%

CTRL START DELAY

SEC-1 SEC-2

SEC-3

SEC-4

SEC-5

SEC-6

SEC-7

SEC-8

Refrigerating system operation confirmation (OFF -> ON)

Start of capacity control

- 105 -

QT108300

STEP-1

The lower limit of the capacity changes over the time you set for this STEP along the line connecting the 0.0 % point and the MVL % point. (MVL stands for manipulating value low limit.) The upper limit of the capacity changes over the time you set for this STEP along the line connecting the 0.0 % point and the percentage point you set for STEP-1.

STEP-2 to STEP-8 The capacity lower limit remains at the MVL %. The capacity upper limit changes over the time you set for each STEP along the line connecting the percentage point of the preceding STEP and the percentage point of each STEP. After STEP-8 The capacity lower limit remains at the MVL % for normal operation. The capacity upper limit remains at the MVH % (the same percentage as the one set for STEP-8) for normal operation. (MVH stands for manipulating value high limit.) You can set any percentage between 0.0 % and 100.0 % for all STEPs from STEP-1 to STEP-7. However, if you set percentages smaller than MVL % for these STEPs, the ramp formed by the capacity upper limit may go below the MVL % line for a certain period of time. The capacity lower limit in this period becomes 0.0 %, and CP4 confines the manipulating value (MV) of the capacity controller within the shaded areas shown in the following diagram during this period.

Regulator MV Set%-(n+1) Set%-(n-1) MVL% Set%-n 0.0 Time SEC-(n-1) SEC-n SEC-(n+1) SEC-(n+2)

Even during STEP-1 to STEP-8, however, either the capacity control limiter may work in the same manner as for the normal operation or the manipulating value (PID OUT (MV)) may go beyond the shaded area while the compressor is in the limited-capacity operation, 100 %-capacity operation, or liquid recovery operation. The settings made in this sub-window for the following two items are not displayed if the VFD COMPRESSOR CONTROL is made valid (see Section 8.1.3 Settings in VFD COMPRESSOR CONTROL window (Option 2 of CONTROLLER Menu (F2))). To display and make settings for them, use the CAPACITY RAMP CONTROL sub-window in the VFD COMPRESSOR CONTROL window (Option 2 of CONTROLLER menu (F2)). REMOTE MVH% The value set for this item is used as the capacity upper limit while the relevant communication-writable coil is in the ON state. However, this function is invalid when any of the following conditions is met. - ENABLE is selected for MVL%/MVH% BY COMM (see below). - AUTO STAGE is selected for OPERATION (see Section 6.1 Settings in OPERATION MODE Window (Option 1 of SETPOINTS Menu (F1))). - REMOTE CAPACITY CONTROL is enabled (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))). - Liquid recovery sequence is in progress in the compressor. MVL%/MVH% BY COMM Select either DISABLE or ENABLE to make valid or invalid the function that allows using the two values (each stored in the relevant two communication-writable registers) as MVL% (capacity lower limit) and MVH% (capacity upper limit), respectively.

- 106 -

QT108300

8.1.3

Settings in VFD COMPRESSOR CONTROL window (Option 2 of CONTROLLER Menu (F2))

To achieve satisfactory speed control of the variable frequency drive (VFD) motor for proper compressor capacity control, you should make necessary selections/entries in the VFD COMPRESSOR CONTROL window according to the instructions in this section.

Settings in VFD COMPRESSOR (MONITOR) sub-window


For OPERATION, select an appropriate speed control method from the following options: MANUAL AUTO REMOTE DIGITAL REMOTE ANALOG COMM The speed increases or decreases as you select MANUAL PLUS or MANUAL MINUS using front panel keys. CP4 automatically determines an appropriate compressor speed according to the pressure or temperature of the control target. Not select able for this control. The value of the relevant analog input is used as the speed value. (Option settings are required (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))).) The value stored in the relevant communication-writable register is used as the speed value.

Settings in VFD COMPRESSOR (SETPOINTS) sub-window


As to the limiting functions to prevent overloading, the same method of setting as with the CAPACITY CONTROL window applies, except that the value set for FORCE UNLOAD is used when a forced decrease condition occurs depending on the UNLOAD set value. The manipulating value PID OUT (MV) % of the speed controller starts decreasing from the time when the forced decrease condition is reached by the value set for FORCE UNLOAD every second. This means that the larger the set value, the shorter the time taken for reducing the manipulating value of the speed controller. The value set for VFD START DELAY is used as the allowance period for confirming the transfer of control from the slide valve position control to the speed control after the unloader slide valve has reached the MVH% position. On the other hand, the value set for VFD STOP DELAY is used when transferring the capacity control back to the slide valve position control from the speed control after reach to MVL% of the manipulating value of the speed controller PID OUT (MV) % . As to the settings for FORCE FULL LOAD and CAPACITY RAMP CONTROL, the same explanation as with the CAPACITY CONTROL window (Option 1 of CAPACITY CONTROL menu (F2)) applies.

- 107 -

QT108300

Settings for OUTPUT LIMIT sub-window


CP4 uses the LOW and HIGH values you set for the output prohibition zones ZONE-1 to ZONE-3 for the purpose of limiting the speed output zones. The speed output zone limiting function works so as to make the analog output corresponding to the VFD COMPRESSOR CONTROL PID OUT output change following the paths shown below. If the LOW and HIGH values are different in the same zone, a step-like path results. If they are the same, a linear path results. (This function is defaulted as disabled.)

Analog output 100% HIGH ZONE-3 LOW HIGH ZONE-2 LOW HIGH ZONE-1 LOW 0% 0% LOW HIGH LOW HIGH LOW HIGH ZONE-1 ZONE-2 ZONE-3 100% PID OUT(MV)% Path followed when increasing the speed Path followed when decreasing the speed

8.1.4

Settings in VFD SETUP Window (SHIFT 3 of CONTROLLER Menu (F2))

This window allows you to set the scaling used for the display of the speed control outputs.

For the COMPRESSOR VFD CONTROL item, select REVOLUTION (rpm) or FREQUENCY (Hz) to select the speed scaling or the frequency scaling, respectively. Under MV0% - 100%, set the speed or frequency values that correspond to the 0 % and 100 % speed control outputs (MV = manipulating value).

- 108 -

QT108300

8.1.5

Settings in CONDENSER CONTROL Window (Option 0 of CONTROLLER Menu (F2))

When an optional digital input/output board (at DO 25 (Y18) DO 30 (Y1D)) and an optional analog output board (when disable is not selected for CONDENSER VFD CONTROL (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)))) are installed, CP4 makes the number and speed controls on the condenser fans or pumps using the discharge pressure as the control target and display the states on the screen of this sub-window. (However, this function does not work unless one of the following factory options is enabled: CONDENSER VFD CONTROL (VFD ONLY, VFD + 2 STEPS, VFD + 3 STEPS, or VFD + 5 STEPS), CONDENSER 3 STEPS CONTROL, and CONDENSER 6 STEPS CONTROL.) This control works when you make selections for the three items in the OPTION SETUP 1/2 window (Option 4 of SETUP menu (F6)) as follows (see Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6))): - Select USE for the CONDENSER CONTROL item to enable this control. - Select LOCAL or SYSTEM DISCHARGE PRESSURE for the CONDENSER CONTROL TARGET item as the control target. - Select ON/OFF SINGLE SET or ON/OFF MULTI SET for the CONDENSER CONTROL METHOD item as the control method. (When ON/OFF SINGLE SET is selected, the start/stop control is made using one set of start and start values to control the number of operating condenser fans or pumps. Selection of ON/OFF MULTI SET allows using different start/stop values for individual fans or pumps. If VFD ONLY is selected as the factory option, the number control of operating fans or pumps is not implemented, so ON/OFF MULTI SET is selected invariably.) The following examples show the CONDENSER CONTROL window displays appearing under different conditions. When ON/OFF SINGLE SET is selected for CONDENSER CONTROL METHOD with factory-set option VFD + 5 STEPS enabled

VFD LAG/VFD LEAD START STOP CYCLE TIME

Select VFD LAG (last ON) or LEAD (first ON) for DO 25:Y18 channel. Different control set value can also be used for LAG and LEAD. Set pressure for increasing the number of units Set pressure for decreasing the number of units Set cycle for checking whether to increase or decrease the number of units

- 109 -

QT108300

When ON/OFF MULTI SET is selected for CONDENSER CONTROL METHOD with factory-set option VFD + 5 STEPS enabled

SET POINT SELECT

Select SET POINT #1 or SET POINT #2 when using a pair of two different set points (one pair associated to #1 and the other associated to #2) by switching between them.

START #1 to START #6 Set pressure for each of digital outputs DO 25 (Y18) to DO 30 (Y1D) STOP NOTE: Depending on the enabled factory option, the START and STOP set pressures displayed are different as follows: Factory option VFD ONLY VFD + 2 STEPS VFD + 3 STEPS START and STOP set pressures displayed #1 #1 to #3 #1 to #4 Set pressure for each of digital outputs DO 25 (Y18) to DO 30 (Y1D)

- 110 -

QT108300

When ON/OFF SINGLE SET is selected for CONDENSER CONTROL METHOD with factory option CONDENSER 3 STEPS CONTROL or CONDENSER 6STEPS CONTROL enabled

START STOP

Set pressure for increasing the number of units Set pressure for decreasing the number of units

CYCLE TIME Cycle for checking whether to increase or decrease the number of units When ON/OFF MULTI SET is selected for CONDENSER CONTROL METHOD with factory-set option VFD 6 STEPS CONTROL enabled

START #1 to START #6 Start pressure for each of digital outputs DO 25 (Y18) to DO 30 (Y1D) STOP NOTE: When factory option VFD 3 STEPS CONTROL START is enabled, START and STOP set pressures are displayed for the #1 to #3 settings. Stop pressure for each of digital outputs DO 25 (Y18) to DO 30 (Y1D)

- 111 -

QT108300

8.2 Communications 8.2.1 System Configuration

CP4 of the standard specification has one RS-485 communication port. Using this communication port, CP4 can make serial communications with a remote communication device. Serial communication is possible among a maximum of 32 devices including the remote device, which are connected with a bus of up to 150 meters in total length. Conforming to the EIA 485 standard, the communication system uses a 4-wire, half-duplex system. The system is formed of one master station and multiple slave stations to make up a master-slave arrangement. Unlike the optional automatic staging control (AUTO STAGE) system, it is impossible for CP4 to become the master for serial communications among other CP4s. A remote communication device (such as a computer, programmable logic controller (PLC) network, or MYPRO-NPIV) is always required to implement the communications network functions. Up to 32 devices Slave No. 1
CP4

Slave No. 2
CP4

Slave No. 3
CP4

Master No. 32 Master station (Remote communication device with terminator)

(Terminator)

RS-485 6-core, 3-paired cable Up to 150 m long Through serial communications, the remote communication device (master station) can read various data of the individual CP4, including analog measurements, settings, calculated values (virtual analog inputs), and the status of each digital input/output and alarm. It is also possible for the master station to give the connected CP4s various commands including commands to change settings and those to start/stop the compressors under control of the slave stations. The system supports both MODBUS Protocol RTU Mode and MODBUS Protocol ASCII Mode.

8.2.2

Remote Communication Device and Communication Protocols

When the remote communications device sends a data write or data read command, the CP4 with the address specified in the command sends an answer. This constitutes one session of communication. (Any CP4 does not voluntarily initiate transmission.)

Flow of data on communications line


(1) Write/read Transmission from remote device Transmission from CP4 command (2) Answer Time

Answer delay time (1) A command is sent from remote device to CP4. (2) CP4 receives command and, if the command is addressed to the CP4, evaluates its content before sending back an answer. The arrangement between the command and answer used in (1) and (2) above is called protocol. Among multiple communications protocols, CP4 supports the two of them: MODBUS ASCII protocol and MODBUS RTU protocol. As both the protocols are standard protocols in industry, communications can easily be implemented without originally programming yourself if MODBUS-compatible SCADA Software and a PLC communication unit are used.

- 112 -

QT108300

8.2.3

Connecting Communication Terminating Resistors

The specifications of the RS-485 standard which the CP4s communication port (COM1) complies with require that the communication ports of the devices located at the physical ends be provided with termination resistors (these ports are called termination ports). The CPU board in each CP4 has a built-in termination resistor. To connect or disconnect the termination resistor, termination switches SW3 for the COM1 port is used. Turn the switch ON to connect the termination resistor, or turn it OFF to disconnect it.

Master-Slave System by 2-Wire Connections


CP4s RS-485 port Slave 2)
Termination resistor connection SW1 ON

CP4s RS-485 port Slave 1)


Termination resistor connection SW1 OFF

Remote devices port (Master)


Termination resistor

SDA SDB

110

RA 110 RB
Termination resistor connection SW2 OFF

RA 110 RB
Termination resistor connection SW2 OFF

RDA RDB SG FG

SA 110 SB SG FG Shielded 6-core, 3-pair cable 110

SA SB SG FG Shielded 6-core, 3-pair cable

In the above example of a 2-wire system, either of the termination resistor connection switches 1 and 2 of the Slave 2 station should be turned ON.

Be sure to connect the termination resistors by tuning ON their switches. This is necessary only for the termination ports. Without connecting termination resistors correctly for the necessary RS-485 ports, normal communications between the network devices is not guaranteed. When setting the switch, move it until it clicks.

- 113 -

QT108300

8.2.4

MODBUS Protocol

MODBUS protocol is a standard communications protocol in industry. With MODBUS protocol, two transmission modes are usable: RTU mode (BINARY system) and ASCII mode (ASCII system). The table below lists the differences between these modes. Item Data bit Statement start mark Statement end mark Statement length *1 Data time interval *2 Error check code NOTE: *1 *2 Statement length in RTU mode is assumed here as N. If individual sets of data that constitute a statement are separated each other longer than the indicated time during transmission, the receiver device interprets it as a halfway interruption of the transmission and ignores the statement. A communication error may be detected in such a case. *3 The bit time indicates the time taken to send one bit of data at the specified transfer rate. RTU mode 8 bits (BINARY) Unnecessary Unnecessary N 24-bit time *3 or less CRC-16 (cyclic redundancy check) ASCII mode 7 bits (ASCII) : (3Ah) CRLF (0Dh, 0Ah) 2N + 1 1 second or less LRC (longitudinal redundancy check) (h indicates a hexadecimal number.)

MODBUS protocol defines various function codes. CP4 supports the function codes shown in the following table. Number of device points that can be handled in one communication session 80 points 80 points 1 point 1 point --2 points 7 points

Function code 01h 03h 05h 06h 08h 0Fh 10h

Function Reads coil status information. Reads content of holding register. Changes status of single coil. Changes content of single holding register. Loopback test Changes status of multiple coils Changes the content of multiple holding registers.

NOTE: CP4 handles bit information as a coil. Number should be specified to designate each set of data under MODBUS protocol. Number includes a reference number, specified number, and start number. The following explains these numbers: The reference number is used to specify a coil or holding register when data of slave devices is referenced from the master device that supports MODBUS protocol. Use 00001 to 09999 to specify coils, and use 40001 to 49999 to specify holding registers. The specified number is used to specify data in command statements under the MODBUS protocol. Use 0001 to 9999 for both coils and hold registers. The specified number is used to specify data in actual command statements. The specified number is also called the start number in the sense that it indicates the data from which writing or reading is to be started. Each number is specified in hexadecimal notation in command statements.

- 114 -

QT108300

Calculation of designation number (start number) from reference number (Coil) (Holding register) Reference number (00001) - 00001 = Specified number (0000) Reference number (40001) - 40001 = Specified number (0000)

For the specified numbers and reference numbers of individual devices, refer to the Device List in Chapter 12.

- 115 -

QT108300

Chapter 9 Maintenance (LOGS Menu (F4))


9.1 Display in TRENO LOG Window (Option 1 of LOGS Menu (F4))
In this window, you can check the numerical data of the past 1,440 input/output (I/O) events (trend log) that were stored in memory at the cycle you specify in the SET TIME window (Option 2 of ADJUSTMENT menu (F5); see Section 5.2 Settings in SET TIME Windows (Option 2 of ADJUSTMENT Menu (F5))).

I/O number (abbreviated) Log No. Old

New

The trend log covers the past 1,440 I/O events including the following items: 1/4: Analog input measurements: 64 items (AI1 to AI64) 2/4: Internally calculated values: 16 items (AI65 to AI80) 3/4: PID controller set points and manipulation values (MV): 16 items each for set point (SV) and MV (PID1 to PID16) 4/4: digital I/O: 16 values or 32 items (DIO00 to DIO0F or DIO1F) (If 1,440 events (from the oldest No. 0000 to the latest No. 1439) are expired, the oldest value is overwritten by the next old value sequentially.) You can set any logging cycle from 0 to 21,600 seconds (6 hours). (For the method, see Section 5.2 Settings in SET TIME Windows (Option 2 of ADJUSTMENT Menu (F5))) Log data for the I/O events of 8 consecutive numbers can be checked for 10 input/output (I/O) items at a time. Use an appropriate one of the following key operations to change the display: : SHIFT + : : SHIFT + : : SHIFT + : : SHIFT + : Display shows the leading event of the I/O number increased by one. (The display shifts in the 1/4-to-4/4 direction (see above).) Display shows the leading event of the I/O number increased by eight. (The display shifts in the 1/4-to-4/4 direction (see above).) - 116 Display shows the leading event of the I/O number decreased by one. (The display shifts in the 4/4-to-1/4 direction (see above).) Display shows the leading event of the I/O number decreased by eight. (The display shifts in the 4/4-to-1/4 direction (see above).) Display starts from the event of the smaller (older) log number by one. Display starts from the event of the smaller (older) log number by 10. Display starts from the event of the larger (newer) log number by one. Display starts from the event of the larger (newer) log number by 10.

QT108300

9.2 Display in TREND GRAPH Window (SHIFT 1 of LOGS Menu (F4))


This window shows the data of the past 1,440 input/output (I/O) events (trend log) that were stored in memory at the cycle you specify in the SET TIME window (Option 2 of ADJUSTMENT menu (F5); see Section 5.2 Settings in SET TIME Windows (Option 2 of ADJUSTMENT Menu (F5))) in the form of a graph. To use this window, you should have assigned the desired I/O items (up to 16 items) to each of the two pages available for this window. On the desired graph page, you can visually check the operation of the compressor unit in details by scrolling the screen and moving the cursor while concurrently utilizing the numerical log data for the desired date and hour.

Display page number I/O number and abbreviation

100%

Data at cursor position Cursor ON OFF 0% Date/time of cursor position

The trend log covers the past 1,440 I/O events including the following items: 1/4: Analog input measurements: 64 items (AI1 to AI64) 2/4: Internally calculated values: 16 items (AI65 to AI80) 3/4: PID controller set points and manipulating values (MV): 16 items each for set point (SV) and MV (PID1 to PID16) 4/4: Digital inputs/outputs: 16 items or 32 items (DIO00 to DIO0F or DIO1F) (If 1,440 events (from the oldest No. 0000 to the latest No. 1439) are expired, the oldest value is overwritten by the next old value sequentially.) You can set any logging cycle from 0 to 21,600 seconds (6 hours). (For the method, see Section 5.2 Settings in SET TIME Windows (Option 2 of ADJUSTMENT Menu (F5)).) For the method of assigning I/O items to each display page, see Section 9.3 Settings in GRAPH ASSIGNMENT Window (SHIFT2 of LOGS Menu (F4)). Log data for the I/O events of 16 assigned numbers can be displayed for 480 I/O items at a time. Use an appropriate one of the following key operations to change the display: To change the page TAB: Changes the display page. To scroll (The screen circulates. When log No. 1439 (latest) is displayed at places other than the rightmost position, its right side log number is No. 0000 (oldest).) ALT + : key : SHIFT + : ALT + : key: SHIFT + : Display starts from an event of the smaller (older) log number by one (horizontally scrolls by one dot). Display starts from an event of the smaller (older) log number by 60 (horizontally scrolls by 60 dots). Display starts from an event of the smaller (older) log number by 480 (horizontally scrolls by one screen). Display starts from an event of the larger (newer) log number by one (horizontally scrolls by one dot). Display starts from an event of the larger (newer) log number by 60 (horizontally scrolls by 60 dots). Display starts from an event of the larger (newer) log number by 480 (horizontally scrolls by one screen).

- 117 -

QT108300

To move the cursor (The cursor moves only within the current screen.) ALT + : : SHIFT + : ALT + : SHIFT + : Cursor moves to an event of the smaller (older) log number by one (moves to the left by one dot). Cursor moves to an event of the smaller (older) log number by 60 (moves to the left by 60 dots). Cursor moves to the event of the leftmost log number in the screen. Cursor moves to an event of the larger (newer) log number by one (moves to the right by one dot). Cursor moves to an event of the larger (newer) log number by 60 (moves to the right by 60 dots). Cursor moves to the event of rightmost log number within the screen.

To stop and restart graph updating SAVE: Temporarily stops graph update. (Log data themselves are updated continuously.) ENTER: Resumes the update that has been stopped temporarily.

9.3 Settings in GRAPH ASSIGNMENT Window (SHIFT2 of LOGS Menu (F4))


Use this window to assign the input and output items to each of the graph pages displayed in the TREND GRAPH window (see Section 9.2 Display in TREND GRAPH Window (LOGS Menu (F4))).

In the PAGE SELECT field, select either P.1/2 or P.2/2 to determine the page to which the input/output items selected in the following are to be assigned. Select the input/output items to be assigned to numbers 1 to 16 on each page from the following: 1/4: Actual measurements of analog inputs: 64 items (AI1 to AI64) 2/4: Internally calculated (virtual) values: 16 items (AI65 to AI80) 3/4: PID controller set points and manipulating values (MV): 16 items each for SV (solenoid valve) set point and MV (PID1 to PID16) 4/4: Digital input/output: 16 items or 32 items (DIO00 to DIO0F or DIO1F)

- 118 -

QT108300

9.4 Displays in ALARM LOG Window (Option 2 of LOGS Menu (F4))


This window displays the record of the dates and times of issuance of the past 36 alarms, their names, and input/output conditions around the times of their issuance (alarm log) in the form of numerical data.

Log No.

Old

New

Time of occurrence and alarm name

Both ALARM and FAILURE are logged. Of the 36 alarms displayed here, the oldest is numbered as No. 00 and the latest is numbered as No. 35. If 37th alarm is logged, the alarm at the No. 00 place will be overwritten by the alarm that was previously at the No. 01 place. This occurs every time a new alarm is logged. Whether the alarm has been cleared or is currently active is shown by different colors. EMERGENCY STOP EMERGENCY STOP NONE An alarm that was issued in the past and has not been cleared An alarm that was issued in the past and has been cleared No alarm is logged for the number.

Up to 12 logged alarms can be displayed at a time. The display can be changed by key operations as follows: : SHIFT + : : SHIFT + : Displays alarms starting with a one of the smaller (older) log number by one. Displays alarms starting with a one of the smaller (older) log number by 12. Displays alarms starting with a one of the larger (newer) log number by one. Displays alarms starting with the one of the larger (newer) log number by 12.

If you press the ENTER key, the numerical data showing the input/output conditions around the time of issuance of the alarm (which is displayed on the bottom line in reverse video) is displayed. To check the input/output conditions around the time of the issuance of a specific alarm, first press the or key to make the alarm name be displayed in reverse video on the bottom line, and then press the ENTER key. The number of items of which the input/output conditions around the time of issuance of alarms is the same as for the TREND LOG window (see Section 9.1) for 1/4 to 4/4 as shown below. 1/4: Actual measurements of analog inputs: 64 items (AI1 to AI64) 2/4: Internally calculated values (virtual values): 16 items (AI65 to AI80) 3/4: PID controller set points and maneuvering values (MV): 16 items each for SV (solenoid valve) set point and MV (PID1 to PID16) 4/4: Digital inputs/outputs: 16 items or 32 items (DIO00 to DIO0F or DIO1F)

- 119 -

QT108300

Log No.: Alarm name Old I/O number. (abbreviation)

Time of alarm issuance

New

The +0 SEC line in reverse video indicates the time of issuance of each alarm. The input/output conditions are indicated as numeral data both for the point 9 seconds before the alarm time and for every second over the 5-second period after that time. Alarm log data that can be displayed at a time are those for the inputs/outputs of 12 consecutive numbers. The display can be changed by key operations as follows: : SHIFT + : : SHIFT + : The first I/O number is increased by one. (The display shifts in the 1/4-to-4/4 direction in the above.) The first I/O number is increased by 12. (The display shifts in the 1/4-to-4/4 direction in the above.) The first I/O number is decreased by one. (The display shifts in the 4/4-to-1/4 direction in the above.) The first I/O number is decreased by 12. (The display shifts in the 4/4-to-1/4 direction in the above.)

To return to the previous window, press the ENTER key.

- 120 -

QT108300

9.5 Display in EVENT LOG Window (Option 3 of LOGS Menu (F4))


This window displays the past 255 operation control events and digital input/output change events (event log). This enables you to track the operations of the compressor and what types of control were made in the past.

Log No. Old

New

The event log covers 256 past events such as operation of the CLEAR ALARM key and the dates/times of changes in switch input/output. Every time a new event occurs when 256 events (from the oldest No. 0000 to the latest No. 0255) have been expired, the newly occurring event causes the oldest No. 000 event to be overwritten by the previously No.0001 event.

- 121 -

QT108300

9.6 Display in DEVICE COUNTER MONITOR Window (Option 4 of LOGS Menu (F4))
This window displays the accumulated operation hours of the compressor and the operation counts of the YOSAKU expansion valves. These data help determine the replacement time and overhaul time of each device. (To make changes to display in this window, see Section 9.7 Resetting Made in DEVICE COUNTER SET Window (Option 5 of LOGS Menu (F4) ).)

Items in DEVICE COUNTER MONITOR Window


Item COMPRESSOR START/STOP COMPRESSOR RUN TIME CHILLER YOSAKU ECONOMIZER/INTERCOOLER YOSAKU LIQUID INJECTION YOSAKU-1 LIQUID INJECTION YOSAKU-2 Description Displays the number of times the compressor was started (from the non-operating state). Displays the operating hours of the compressor. Displays the number of times the chiller YOSAKU expansion valve was operated. (Option) Displays the number of times the economizer/intercooler YOSAKU expansion valve was operated. (Option) Displays the number of times the liquid injection YOSAKU-1 expansion valve was operated. (Option) Displays the number of times the liquid injection YOSAKU-2 expansion valve was operated. (Option)

- 122 -

QT108300

9.7 Resetting Made in DEVICE COUNTER SET Window (Option 5 of LOGS Menu (F4) )
This window allows you to clear the record of the accumulated operating hours of the compressor and the operation counts of YOSAKU expansion valves. Resetting the records to 0 is necessary after replacement or overhaul of devices. The LEVEL-2 password (see Section 5.3 Settings in PASSWORD Window (Option 3 of ADJUSTMENT Menu (F5))) must be entered to open this window.

The setting items are the same as those described in Section 9.6 Display in DEVICE COUNTER MONITOR Window (Option 4 of LOGS Menu (F4)).

- 123 -

QT108300

Chapter 10 Analysis (DIAGNOSTIC Menu (F7))


10.1 Display in SHOW SYSTEM SETUP Window (Option 1 of DIAGNOSTIC Menu (F7))
In this window, you can check the current settings in the SYSTEM SETUP window (no change is possible to the displayed data). See Section 4.1 Setting in SYSTEM SETUP Window (Option 1 of SETUP Menu (F6)) for the details of the settings themselves.

10.2 Display in SHOW ANALOG INPUT SCALINGT Window (Option 2 of DIAGNOSTIC Menu (F7))
In this window, you can check the current settings in the ANALOG INPUT SCALING window (no change is possible to the displayed data). See Section 4.2 Settings in ANALOG INPUT SCALING Window (Option 2 of SETUP Menu (F6)) for the details of the settings themselves. In this window, you can also check all current analog input values.

- 124 -

QT108300

10.3 Display in SHOW OPTION ANALOG INPUT Window (Option 3 of DIAGNOSTIC Menu (F7))
In this window, you can check the current settings in the OPTION ANALOG INPUT window (no change is possible to the display in this window). See Section 4.3 Settings in OPTION ANALOG INPUT Window (Option 3 of SETUP Menu (F6)) for the details of the settings themselves.

10.4 Display in SHOW DIGITAL I/O STATUS Window (Option 4 of DIAGNOSTIC Menu (F7))
In this window, you can check the current status of digital inputs and outputs (no change is possible to the display in this window). White characters against a blue background indicate digital outputs in the OFF state; blue characters against a white background indicate those in the ON state. Gray characters against a blue background indicate digital inputs in the OFF state; blue characters against a gray background indicate those in the ON state.

- 125 -

QT108300

10.5 Display in SHOW OPTION SETUP 1/2 Window (Option 5 of DIAGNOSTIC Menu (F7))
In this window, you can check the current settings in the OPTION SETUP 1/2 window (no change is possible to the displayed data). See Section 4.4 Settings in OPTION SETUP 1/2 Window (Option 4 of SETUP Menu (F6)) for the details of the settings themselves.

10.6 Display in SHOW OPTION SETUP 2/2 Window (Option 6 of DIAGNOSTIC Menu (F7))
In this window, you can check the current settings in the OPTION SETUP 2/2 window (no change is possible to the displayed data). See Section 4.5 Setting in OPTION SETUP 2/2 Window (Option 5 of SETUP Menu (F6)) for the details of the settings themselves.

- 126 -

QT108300

10.7 Display in SHOW PROGRAM VERSION Window (Option 7 of DIAGNOSTIC Menu (F7))
In this window, you can check the current program version (no change is possible to the displayed data).

10.8 Display in READ REGISTER Window (Option 8 of DIAGNOSTIC Menu (F7))


In this window, you can check the current values in the CP4s internal registers. Although no change to these values is possible, you can switch them between decimal and hexadecimal notations.

Explanation of screen operation

DECIMAL/ HEXADECIMAL display

Current page/total pages

Operation in this window: Press the TAB key to advance the page by one. Press both ALT and TAB keys at the same time to reverse the page by one. Press both SHIFT and TAB keys at the same time to advance the page by five. Press the ALT, SHIFT and TAB keys at the same time to reverse the page by five. The display switches between decimal and hexadecimal notations each time you press the DELETE key.

- 127 -

QT108300

10.9 Display in READ BIT Window (Option 9 of DIAGNOSTIC Menu (F7))


In this window, you can check the states of the bit devices (digital input/output devices and internal relays) in CP4 (no change is possible to the displayed data). 0 indicates OFF and 1 indicates ON in each bit place.

Explanation of screen operation

Current page/total pages

Operation in this window: Press the TAB key to advance the page by one. Press both ALT and TAB keys at the same time to reverse the page by one.

10.10 Display in READ TIMER/COUNTER Window (Option 0 in DIAGNOSTIC Menu (F7))


In this window, you can check the current values and ON/OFF states of the CP4s internal timers and counters. Although no change is possible to the displayed data in this window, you can switch them between decimal and hexadecimal notations.

Explanation of screen operation

DECIMAL/ HEXADECIMAL display

Current page/total pages

Operation in this window: Press the TAB key to advance the page by one. Press both ALT and TAB keys at the same time to reverse the page by one. The display is switched between decimal and hexadecimal notations each time the DELETE key is pressed. - 128 -

QT108300

Chapter 11 Troubleshooting
This chapter contains several conditions that may suggest failures or other problems with CP4 and the actions we recommend you to take when these conditions occur. (1) Nothing is displayed on the front panel screen. CP4 has the function of automatically turning off the backlight to prevent LCD from burning and increase its life. By default, the backlight is automatically turned off if no operation is performed on the front panel for 10 minutes. Press any key on the front panel to turn on the backlight again. (2) Check that the flat cable from the LI board is connected to J3 on the PR01 board. Check that 12 V DC power is supplied to J3 on the LI board (namely, that the fuse is not blown).

Display remains dark (backlight is not lit) CP4 has the function of automatically turning off the backlight to prevent LCD from burning and increase its life. By default, the backlight is automatically turned off if no operation is performed on the front panel for 10 minutes. Press any key on the front panel to turn on the backlight again. Check that the backlight power is supplied from J4 on the LI board (namely, that the fuse is not blown). Check whether the backlights life (30,000 to 50,000 hours) has expired.

(3)

The CPU light (an LED regularly blinking to indicate normal state) does not blink. Check that the UV-EPROM is installed in the correct direction and position. Check that 5 V DC power is supplied to J1 on the PR01 board (namely, that the fuse is not blown). Check the wiring to the circuit breaker and noise filter has no defects and the power voltage is correct.

(4)

The displayed actual measurements of the pressure sensors differ from the actual pressure values (pressure gauge readings etc.) Check that the pressure sensor and its wiring have no defects. Check that the scaling for displaying the measurement is set correctly. (The scaling is set in the ANALOG INPUT SCALING window (Option 2 of SETUP menu (F6).) If the displayed measurements noticeably deviate from the actual values, you can enter an appropriate offset value to make the displayed values close to the actual pressure values.

(5)

The displayed actual measurements of the temperature sensors differ from the actual temperature values (thermometer readings etc.) Check that the temperature sensors and their wiring have no defects. Check that the scaling for displaying the measurements is set correctly. (The scaling is set in the ANALOG INPUT SCALING Window (Option 2 of SETUP Menu (F6).) If the displayed measurements noticeably deviate from the actual values, you can enter an appropriate offset value to make the displayed values closer to the actual temperature values.

(6)

The displayed actual measurements of the current sensor differ from the actual current values. Check that the jumper pins of the CT sensor are in the correct (removed) state. Check that the CT sensor winding is correct in number of turns (twice). Check that the scaling for displaying the measurement is set correctly. (The scaling is set in the ANALOG INPUT SCALING Window (Option 2 of SETUP Menu (F6).) If the displayed measurements noticeably deviate from the actual values, you can enter an appropriate offset value to make the displayed values closer to the actual current values. (Use the ANALOG INPUT ADJUSTMENT window (Option 4 of the ADJUSTMENT menu (F5)).)

- 129 -

QT108300

(7)

Measurements respond to changes too slowly or too fast To make the response faster, decrease the FILTER COEFFICIENT value. (Use the ANALOG INPUT ADJUSTMENT window (Option 4 of the ADJUSTMENT menu (F5)).) NOTE: Making the response time too short increases effects of noise. To make the response slower, increase the FILTER COEFFICIENT value. (Use the ANALOG INPUT ADJUSTMENT window (Option 4 of the ADJUSTMENT menu (F5)).) NOTE: Making the response time too long results in too slow reactions.

(8)

Settings cannot be changed. Entry of a password of the required level is needed to change settings. Make sure you have entered the required password correctly. Some items of setting have limitations. Enter only values within the permitted range. To complete a change to any setting, you have to press the SAVE key to store entries in memory. Pressing the ENTER key alone does not complete the setting.

(9)

The compressor does not run. Check the operation control mode you have selected in the OPERATION MODE Window (Option 1 of the SETPOINTS menu (F1)). The way to give operation commands to the compressor varies depending on the selected operation control mode. The compressor does not start running until the operation start delay time elapses after the compressor operation conditions (operation command etc.) are satisfied. Check that the compressor start command has turned ON at DO-01(Y00). Check that YES is selected for D/O TEST OPERATION in the OPERATION MODE window (Option 1 of SETPOINTS menu (F1)). If you make a selection to enable an item that requires installation of an optional extension board in the SYSTEM SETUP (Option 1), OPTION SETUP 1/2 (Option 4), or OPTION SETUP 1/2 (Option 4) window of the SETUP menu (F6) without actually installing that board, CP4 issues, for the sake of safety, an EMERGENCY STOP FAILURE alarm that cannot be cancelled with the CLEAR ALARM key and disables operation of the compressor. In this case do either of the following: Install the optional extension board. Disable the item that requires installation of the optional extension board.

The compressor has been stopped by pressing the STOP key. If the compressor has been stopped by pressing the STOP key, different action should be taken according to the operation control mode selected at that time to recover operation of the compressor. When the STOP key has been pressed while the operation command is ON with a mode other than the AUTO STAGE selected for the OPERATION item in the OPERATION MODE window (Option 1 of SETPOINTS menu (F1)), the operation control mode automatically changes to LOCAL. In this case, you must reselect the desired operation control mode for the OPERATION item and then turn ON the operation command. When the STOP key has been pressed with AUTO STAGE selected for OPERATION and ENABLE selected for the CONTROL item, ENABLE automatically changes to DISABLE. To resume the automatic staging control (AUTO STAGE), you must reselect ENABLE for the CONTROL item in the AUTO STAGE window (Option 7 of SETPOINTS menu (F1)) and then turn ON the operation command.

The CPU is reset by such action as turning power ON while BATTERY ALARM is displayed on the top of the Status Display Screen. If a run-down memory backup battery is detected when the CPU is reset during power-up operation or the like, CP4 performs special booting for safetys sake, which prevents the compressor from operating. See Section 2.2.2 Replacement of Memory Backup Battery on CPU Board to replace the battery. In the case of battery replacement, you may need to initialize all settings.

- 130 -

QT108300

(10) Capacity control does not take place. MANUAL is selected for OPERATION of the capacity controller (or WARNING! is displayed at the top of the screen). Selection made for OPERATION of the capacity controller is not AUTO but any of the following: MANUAL (capacity increase/decrease commands are given through key operations on front panel); REMOTE DIGITAL (capacity increase/decrease commands are given by digital inputs from an external device); REMOTE ANALOG (capacity increase/decrease commands are given by external analog inputs); COMM (capacity is determined according to commands from remote master station through communications) The capacity control limiter function is working. While the limiter function is active, LIMIT or UNLOAD is displayed in white characters for each of the limiter operation indications MA, DP, SP, and IP in the CAPACITY CONTROL window on the Main Status Screen. (While the function is not working, these indications are displayed in gray.) Settings in the SLIDE VALVE SETUP window are incorrect. If the settings made in the SLIDE VALVE SETUP window (Option 1 of ADJUSTMENT Menu (F5)) are incorrect, the unloader slide valve position cannot be detected correctly. See Section 5.1 Settings in SLIDE VALVE SETUP Window (Option 1 of ADJUSTMENT Menu (F5)) to make settings correctly. (11) The compressor fails to stop. Check the mode set for OPERATION in the OPERATION MODE window (Option 1 of SETPOINTS menu (F1)). The compressor stopping method varies depending on the selected operation control mode. Check that the compressor operation command sent through communications from the remote device is not ON.

(12) BATTERY ALARM is displayed at the top of the status display screen. The memory backup battery is low. See Section 2.2.2 Replacement of Memory Backup Battery on CPU Board to replace the battery. Even if this alarm is not displayed, replace the battery every three years. If a run-down memory backup battery is detected when the CPU is reset during power-up operation or the like, CP4 performs special booting for safetys sake, which prevents the compressor from operating. (If a power failure occurs while this alarm is displayed, the settings in memory may not be backed up.) (13) D/O TEST OPERATION cannot be enabled. Check that YES is selected for D/O TEST OPERATION in the OPERATION MODE window (Option 1 of SETPOINTS menu (F1)). To make YES selectable for D/O TEST OPERATION, check the following in the OPERATION MODE window: OPERATION MODE - LOCAL AUTO START/STOP - NO Operation confirmation input (MSRB) at DI-12 (X0B) - OFF (14) OPERATION changes to LOCAL unintentionally. STOP key has been pressed. If the STOP key is pressed when the operation mode is other than AUTO STAGE, the operation mode changes to the LOCAL mode automatically. In this case, reselect the desired mode for the OPERATION item in the OPERATION MODE window (Option 1 of SETPOINTS menu (F1)). Change to LOCAL MODE is selected for the OPERATION MODE ON FAILURE item in the SYSTEM SETUP window (Option 1 of SETUP menu (F6)). If FAILURE (critical alarm) occurs, CP4 automatically switches the operation mode to LOCAL. Change to LOCAL STOP is selected for the OPERATION MODE RESTORE ON POWER UP item in the SYSTEM SETUP window (Option 1 of SETUP menu (F6)). When the CPU is reset during power-up operation or by other causes, CP4 automatically put itself in a stopped state in the LOCAL mode.

- 131 -

QT108300

(15) Even when emergency stop input at DI11 (X0A) is ON, pressing the CLEAR ALARM key cannot clear EMERGENCY STOP FAILURE alarm. An item which requires installing an optional extension board is enabled in the OPTION SETUP 1/2 or OPTION SETUP 2/2 Window (Option 4 or 5 in SETUP Menu (F6)) without actually installing the board. Depending on the setting item, CP4 may, for safetys sake, issue an EMERGENCY STOP FAILURE alarm to disable operation. In this case, take either of the following actions. Install the optional extension board. Disable the item that requires installing an optional extension board. (16) In the SLIDE VALVE SETUP window (Option 1 of ADJUSTMENT menu (F5)), display does not advance and entry for adjusting the unloader slide valve position cannot be completed. The requirement for the large-small relationship of the analog inputs (showing unloader slide valve positions) are not satisfied for the correction processing. No signal change occurs even when the unloader slide valve moves unless the switches for selecting the signal source for slide valve position detection (potentiometers, 4 to 20 mA DC, or 1 to 5 V DC) on the CP4s CPU board and analog input board are not correctly set. In this case, the switches must be set correctly according to Section 2.4.2 Input Type Selection for Channels 15 and 16 of Analog Input Boards. The 0 %-position analog input becomes larger than the 100 %-position analog input (the inputs reverse) if the connections of terminals 1 and 3 are reversed on the potentiometer for detecting the unloader slide valve position or the potentiometer is installed at a wrong angle. In this case, the potentiometer terminals must be reconnected correctly and the installation angle of the potentiometer must be corrected. The difference between the 0 %-position and 100 %-position analog inputs may become extremely small if the potentiometer for detecting the unloader slide valve position is installed improperly or at a wrong angle, or if it is connected to the analog input terminals improperly. In this case, replace the potentiometer if it is defective, correct its installation and correct potentiometers connection to the analog input terminals.

- 132 -

QT108300

Chapter 12 Specifications
Absolute Maximum Rating Power supply voltage Working temperature Storage temperature Ambient humidity Ambient vibration Endurance to noise 85 to 264 VAC 0 to 55 C -10 to 70 C 85 % RH or less (no condensation is permitted) 1.0G in X-, Y-, and Z-axes Power line I/O line Communication Line Noise voltage: 1,500 V, noise width: 100 ns 1s for 5 minutes Noise voltage: 1,000 V, noise width: 100 ns 1s for 5 minutes Noise voltage: 500 V, noise width: 50 ns for 5 minutes

Withstand voltage Insulation resistance

1,000 VAC for 1 minute (between power terminal and connection terminal) 500 VAC for 1 minute (between input/output terminal and connection terminal) 500 VDC 500 VDC 20 M or more (between power terminal and connection terminal) 20 M or more (between input/output terminal and connection terminal)

If voltages exceeding the absolute maximum rating are applied, the equipment may suffer permanent damage. If the equipment is left under the absolute maximum rating conditions for a long time, its reliability may be deteriorated.

Recommended Operating Conditions Power supply voltage Frequency Working temperature Ambient humidity Ambient atmosphere 100/200 VAC 50/60 Hz 5 to 50 C 70 % RH or less (no condensation is tolerated) Free from corrosive gas and heavy dust

Inputs/Outputs Input sensor Analog inputs Potentiometer inputs (analog/digital at channels 15 and 16) Pressure *1 Measurement range 4 to 20 mA DC (input impedance: 250 ) or, 1 to 5 VDC (input impedance: 100 k) (Switching by a switch is possible) 1 k potentiometer input Standard: 16 points Maximum: 32 points Maximum: 2 points

Temperature *1

Current Capacity Measurement accuracy Sensor power supply Switch output Contacts Switch input Sampling frequency (Option) analog output

*2 Display unit: MPa 2 *2 Display unit: kgf/cm *2 Display unit: bar *2 Display unit: PSI *2 Display unit: C *2 Display unit: F *2 Display unit: K *2 Display unit: A Display unit: % 0 to 100% 0.5 % / full-scale (sensor errors not included) 24 VDC (supplied from external 24 VDC power supply to analog input board) Mechanical relay (load 250 V and 5 A AC, or 30 V Standard: 10 points and 5 A DC) or, solid state relay (load 100 to 240 Maximum: 24 points VAC, 1.2 A) No-voltage contact connection (internally supplied Standard: 6 points 12 V at Max. 25 mA DC) Maximum: 8 points 250 msec 4 to 20mA DC (at load resistance of 500 or less) 4 points

*1 Display units can be selected in the SYSTEM SETUP window (Option 1 of SETUP menu (F6)). *2 Ranges can freely scaled in the ANALOG INPUT SCALING window (Option 3 of SETUP menu (F6)).

- 133 -

QT108300

Communications Interface Communication system COM0 COM1 to COM3 COM0 Small round 8-pin connector (signal level conforming to RS-232C.) Conforms to RS-485 (COM2 and COM3 are optional ports.) Half-duplex 4-wire half-duplex (2-wire system is also usable for communications.) Asynchronous communication method 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 bps (The total bit rates of all communication ports must be less than 192,000 bps.) Fixed to 1 bit 7 or 8 bits (COM0 is fixed to 8 bits.) N (none), O (odd), or E (even) (COM0 is fixed to N.) 1 or 2 bits (COM0 is fixed to 1 bit) Parity check: Yes (odd/even) or No (COM0 is fixed to No.) CRC-16: Fixed to Yes (in only RTU mode of MODBUS protocol) LRC: Fixed to Yes (in only ASCII mode of MODBUS protocol) Up to 150 m in total (COM0 only) 1k X-Modem protocol (BINARY code) MODBUS protocol RTU mode (BINARY code) MODBUS protocol ASCII mode (ASCII code)

COM1 to COM3 Synchronization method

Communication speed (bit/sec) Start bit Character bit Parity bit Stop bit Signal transmission error detection Transmission distance Communication protocol (Communication code)

Character format

Display, Keys, and Switches 10.4 liquid crystal display Resolution: 640 x 480 pixels Number of colors: 256 Service life of LCD backlight: 30,000 to 50,000 hours (depending on the ambient temperature) F1 to F7 keys Display function menus. ESC key Closes a menu window. SHIFT key Used in combination with another key (not used independently). ALT key Used in combination with another key (not used independently). DELETE key Deletes data for setting corrections. Arrow keys Used to move from item to item. TAB key Used to move from an item in one window to an item in another. ENTER key Confirming data entered in an item. SAVE key Saves data in internal memory. Numeral keys Used to select an item or enter a number. START key Starts compressor operation. STOP key Stops compressor operation. CLEAR ALARM key Clears an alarm. Currently not used

Display method

Keys

DIP switch (SW1 on CPU board)

Others Protective component Between contact output electrodes Circuit protector: Thermal tripping system, rated current 1 A Backed up by battery (CR2032). (Recommended battery replacement interval: 3 years) 270VA Max. (Max. 0.25 A @200 V AC 3 + Max. 0.60 A @200 V AC 1) 420mm (H) 380mm (W) 100mm (D) 66mm (H) 200mm (W) 35mm (D) 66mm (H) 200mm (W) 35mm (D) 107mm (H) 348mm (W) 35mm (D)

Storage of set points Power consumption CP4 panel A/I board (REF-CX100-AI01) Outside A/I board dimensions (REF-CX100-AI11) DI/O board (REF-MCS200-OIA0)

- 134 -

QT108300

Others (continued) CP4 panel A/I board (REF-CX100-AI01) Weight A/I board (REF-CX100-AI11) DI/O board (REF-MCS200-OIA0) Approx. 5.3 kg Approx. 0.2 kg Approx. 0.2 kg Approx. 0.2 kg

- 135 -

QT108300

Device List

- 136 -

QT108300

About MODBUS Protocol of CPIV Status of CPIV can be monitored by MODBUS (ASCII or RTU) reading protocol. Also control of CPIV can be changed by MODBUS (ASCII or RTU) writing protocol. CPIV has one RS-485 compatible, Half-Duplex Four-wire serial communication port with MODBUS protocol. (Optional plus two ports) It is named as COM1. (Optional ports are named as COM2 and COM3.) The setting of each communication port can be input on F5: ADJUSTMENT>8.COMMUNICATION SETUP(LEVEL-1 Password required) Name COMMUNICATION ADDRSS RATE FORMAT PROTOCOL RESPONSE Selection STOP or RUN Zero to 99 300 to 115200 bps C7/8,PN/E/O,S1/2 MODBUS ASCII or RTU Zero to 100 X 10 msec Note Control of Communication. The following can be input when it is STOP. Communication address (ADDRESS zero stops communication.) Communication speed Character format C(haracter Bit), P(arity Bit), S(top Bit) Communication protocol Response time of each communication. 100 means one second delay.

CP has two kinds of devices on MODBUS protocol, one is Holding Registers and another is Coils. Holding Registers number 40001 to 42200 Number 40001 to 40256 40257 to 40272 40273 to 40308 40309 to 40320 40321 to 40400 40401 to 40656 40657 to 40912 40667 to 40668 40683 to 40684 40827 to 40828 40843 to 40844 40913 to 42000 41001 41002 41262 41295 41401 Description for Sequence Control Control by Communication DI/O Status Calculated Data A/I PID Controllers PID Controllers Capacity MVL%/MVH% Set Capacity MVL%/MVH% Set VFD Compressor MVL%/MVH% Set VFD Compressor MVL%/MVH% Set Setup Settings Compressor Operation Mode Set Auto Start/Stop Enable Capacity Control Mode Set VFD Compressor Capacity Mode Set MVL%/MVH% Write Enable Attribute Read Only Read Write Read Only Read Only Read Only Read Only Read Only Read Write Read Write Read Write Read Write Read Only Read Write Read Write Read Write Read Write Read Write Note

<-Except following eight registers Suction Pressure Chiller LB Temperature Suction Pressure Chiller LB Temperature <-Except following 12 registers F1:1.OPERATION MODE>OPERATION MODE F1:1.OPERATION MODE>AUTO START/STOP F2:1.CAPACITY CONTROL>MONITOR>OPERATION F2:2.VFD COMPRESSOR CONTROL>MONITOR>OPERATION F2:1.CAPACITY CONTROL>MVL%/MVH% BY COMM or F2:2.VFD COMPRESOOR CONTROL>MVL%/MVH% BY COMM F5:2.SET TIME>WEEK F5:2.SET TIME>MONTH F5:2.SET TIME>DAY F5:2.SET TIME>YEAAR F5:2.SET TIME>HOUR F5:2.SET TIME>MINUTE F5:2.SET TIME>SECOND

41972 41973 41974 41975 41976 41977 41978 42001 to 42100 42101 to 42200

WEEK Set MONTH Set DAY Set YEAR Set HOUR Set MINUTE Set SECOND Set for Status Monitor for AUTO STAGE Calculation

Read Write Read Write Read Write Read Write Read Write Read Write Read Write Read Only Read Only

- 137 -

QT108300

Holding Registers number 40001 to 42200 can be read using MODBUS Function Code 03h (Read Holding Register). Read Write Holding Registers can be written using MODBUS Function Code 06h (Preset Single Register) or 10h (Preset Multiple Registers). Coil number 00001 to 02624 Number 00001 to 00128 00129 to 00256 00257 to 00384 00385 to 00448 00449 to 00512 00513 to 00576 00577 to 01600 01601 to 02624 Description Real DI/O Pseudo D/O Pseudo D/O Pseudo D/I Pseudo D/I Control by Communication Pseudo Relay Latched Pseudo Relay Attribute Read Only Read Only Read Only Read Only Read Only Read Write Read Only Read Only Note ALARM FAILURE MODE CONFIGURATION Control & Monitor Control

Coils number 00001 to 02624 can be read using MODBUS Function Code 01h (Read Coil Status). Coils number 00513 to 00576 can be written using MODBUS Function Code 05h (Force Single Coil) or 0Fh (Force Multiple Coils).

- 138 -

QT108300

Holding Registers number 40001 to 42560 can be read using MODBUS Function Code 03h (Read Holding Register). Read Write Holding Registers can be written using MODBUS Function Code 06h (Preset Single Register) or 10h (Preset Multiple Registers). Holding Registers number 40001 to 40128 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024 40025 40026 40027 40028 40029 40030 40031 40032 40033 40034 40035 40036 40037 40038 40039 40040 40041 40042 40043 40044 40045 40046 40047 40048 40049 40050 40051 40052 40053 40054 40055 40056 40057 40058 40059 40060 40061 40062 40063 40064 40065 40066 40067 40068 40069 40070 40071 40072 40073 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0000 D0001 D0002 D0003 D0004 D0005 D0006 D0007 D0008 D0009 D0010 D0011 D0012 D0013 D0014 D0015 D0016 D0017 D0018 D0019 D0020 D0021 D0022 D0023 D0024 D0025 D0026 D0027 D0028 D0029 D0030 D0031 D0032 D0033 D0034 D0035 D0036 D0037 D0038 D0039 D0040 D0041 D0042 D0043 D0044 D0045 D0046 D0047 D0048 D0049 D0050 D0051 D0052 D0053 D0054 D0055 D0056 D0057 D0058 D0059 D0060 D0061 D0062 D0063 D0064 D0065 D0066 D0067 D0068 D0069 D0070 D0071 D0072 Name None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control Sub Category Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Note

- 139 -

QT108300

(continued)
Register Number 40074 40075 40076 40077 40078 40079 40080 40081 40082 40083 40084 40085 40086 40087 40088 40089 40090 40091 40092 40093 40094 40095 40096 40097 40098 40099 40100 40101 40102 40103 40104 40105 40106 40107 40108 40109 40110 40111 40112 40113 40114 40115 40116 40117 40118 40119 40120 40121 40122 40123 40124 40125 40126 40127 40128 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0073 D0074 D0075 D0076 D0077 D0078 D0079 D0080 D0081 D0082 D0083 D0084 D0085 D0086 D0087 D0088 D0089 D0090 D0091 D0092 D0093 D0094 D0095 D0096 D0097 D0098 D0099 D0100 D0101 D0102 D0103 D0104 D0105 D0106 D0107 D0108 D0109 D0110 D0111 D0112 D0113 D0114 D0115 D0116 D0117 D0118 D0119 D0120 D0121 D0122 D0123 D0124 D0125 D0126 D0127 Name None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control Sub Category Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Unlatched Note

- 140 -

QT108300

Holding Registers number 40129 to 40256 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 40129 40130 Attribute Read Only Read Only Internal Word Device D0128 D0129 Name Current CUT-IN Set Point Current PRESSURE CONTROL Set Point Current TEMPERATURE CONTROL Set Point Current CUT-OUT Set Point None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None Range Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category for Sequence Control for Sequence Control Sub Category Latched Latched Note Set Point displayed on STATUS screen Set Point displayed on STATUS screen Set Point displayed on STATUS screen Set Point displayed on STATUS screen

40131

Read Only

D0130

for Sequence Control

Latched

40132 40133 40134 40135 40136 40137 40138 40139 40140 40141 40142 40143 40144 40145 40146 40147 40148 40149 40150 40151 40152 40153 40154 40155 40156 40157 40158 40159 40160 40161 40162 40163 40164 40165 40166 40167 40168 40169 40170 40171 40172 40173 40174 40175 40176 40177 40178 40179 40180 40181 40182 40183 40184 40185 40186 40187 40188 40189 40190 40191 40192 40193 40194 40195 40196 40197 40198 40199 40200

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0131 D0132 D0133 D0134 D0135 D0136 D0137 D0138 D0139 D0140 D0141 D0142 D0143 D0144 D0145 D0146 D0147 D0148 D0149 D0150 D0151 D0152 D0153 D0154 D0155 D0156 D0157 D0158 D0159 D0160 D0161 D0162 D0163 D0164 D0165 D0166 D0167 D0168 D0169 D0170 D0171 D0172 D0173 D0174 D0175 D0176 D0177 D0178 D0179 D0180 D0181 D0182 D0183 D0184 D0185 D0186 D0187 D0188 D0189 D0190 D0191 D0192 D0193 D0194 D0195 D0196 D0197 D0198 D0199

for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control

Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched

- 141 -

QT108300

(continued)
Register Number 40201 40202 40203 40204 40205 40206 40207 40208 40209 40210 40211 40212 40213 40214 40215 40216 40217 40218 40219 40220 40221 40222 40223 40224 40225 40226 40227 40228 40229 40230 40231 40232 40233 40234 40235 40236 40237 40238 40239 40240 40241 40242 40243 40244 40245 40246 40247 40248 40249 40250 40251 40252 40253 40254 40255 40256 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0200 D0201 D0202 D0203 D0204 D0205 D0206 D0207 D0208 D0209 D0210 D0211 D0212 D0213 D0214 D0215 D0216 D0217 D0218 D0219 D0220 D0221 D0222 D0223 D0224 D0225 D0226 D0227 D0228 D0229 D0230 D0231 D0232 D0233 D0234 D0235 D0236 D0237 D0238 D0239 D0240 D0241 D0242 D0243 D0244 D0245 D0246 D0247 D0248 D0249 D0250 D0251 D0252 D0253 D0254 D0255 Name None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None None Week Month Day Year Hour Minute Second Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 0 (SUN.) to Six (SAT.) 1 to 12 1 to 31 A.D. Four digits. 0 to 23 0 to 59 0 to 59 Category for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control for Sequence Control Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

Real Time Clock displayed on screen Real Time Clock displayed on screen Real Time Clock displayed on screen Real Time Clock displayed on screen Real Time Clock displayed on screen Real Time Clock displayed on screen Real Time Clock displayed on screen

- 142 -

QT108300

Holding Registers number 40257 to 40384 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.) The data written to Holding Registers number 40257 to 40261 should be industrial unit X 10~n. (^ means power and n is the number of decimal place that is displayed on screen.) If the target data is displayed 12.345, n is three, so the written data should be 1000 times. The data of Internal Word Device D0256 to D0260 are converted Range Low to 0 and Range High to 4095. The relation of data read from Holding Registers number 40321 to 40400 between Internal Word Device D0320 to D0399 are similar as above.
Register Number 40257 Internal Word Device D0256 Sub Category

Attribute Read Write

Name CUT IN Set Point (Pressure(n=3) or Temperature(n=1) )

Range Industrial Unit X 10^n Control

Category

Note Required F1:4.SCHEDULER >CUT IN/OUT:COMM Written result can be confirmed F1:3.SET POINTS>SET POINTS>COMM Required F1:4.SCHEDULER >CUT IN/OUT:COMM Written result can be confirmed F1:3.SET POINTS>SET POINTS>COMM Required F1:4.SCHEDULER >CONTROL TARGET:COMM Written result can be confirmed F1:3.SET POINTS>SET POINTS>COMM Required F1:4.SCHEDULER >CONTROL TARGET:COMM Written result can be confirmed F1:3.SET POINTS>SET POINTS>COMM Required F2:1.CAPACITY CONTROL>OPER ATION:COMM or F2:2.VFD COMPRESSOR> OPERATION:COM M. Or write 4 to Holding Register number 41262 or 41295(VFD Compressor). for Master of AUTO STAGE Control Required F1:7.AUTO STAGE>AUTOST AGE>LEAD LISTING:COMM for Master of AUTO STAGE Control Required F1:7.AUTO STAGE>AUTOST AGE>LEAD LISTING:COMM for Master of AUTO STAGE Control Required F1:7.AUTO STAGE>AUTOST AGE>LEAD LISTING:COMM

40258

Read Write

D0257

CUT OUT Set Point (Pressure(n=3) or Temperature(n=1) )

Industrial Unit X 10^n

Control

40259

Read Write

D0258

(Low Stage) Capacity Control Pressure Set Point(n=3)

Industrial Unit X 10^n

Control

40260

Read Write

D0259

(Low Stage) Capacity Control Temperature Set Point(n=1)

Industrial Unit X 10^n

Control

40261

Read Write

D0260

Capacity Set Point(n=1)

Industrial Unit X 10^n 0 to 1000

Control

40262

Read Write

D0261

LEAD LIST 1 ADDRESS

0 to 99

Control

40263

Read Write

D0262

LEAD LIST 2 ADDRESS

0 to 99

Control

40264

Read Write

D0263

LEAD LIST 3 ADDRESS

0 to 99

Control

- 143 -

QT108300

(continued)
Register Number 40265 Attribute Read Write Internal Word Device D0264 Name LEAD LIST 4 ADDRESS 0 to 99 Range Control Category Sub Category Note for Master of AUTO STAGE Control Required F1:7.AUTO STAGE>AUTOST AGE>LEAD LISTING:COMM for Master of AUTO STAGE Control Required F1:7.AUTO STAGE>AUTOST AGE>LEAD LISTING:COMM for Master of AUTO STAGE Control Required F1:7.AUTO STAGE>AUTOST AGE>LEAD LISTING:COMM for Master of AUTO STAGE Control Required F1:7.AUTO STAGE>AUTOST AGE>LEAD LISTING:COMM for Master of AUTO STAGE Control Required F1:7.AUTO STAGE>AUTOST AGE>LEAD LISTING:COMM

40266

Read Write

D0265

LEAD LIST 5 ADDRESS

0 to 99

Control

40267

Read Write

D0266

LEAD LIST 6 ADDRESS

0 to 99

Control

40268

Read Write

D0267

LEAD LIST 7 ADDRESS

0 to 99

Control

40269

Read Write

D0268

LEAD LIST 8 ADDRESS

0 to 99

Control

40270 40271 40272 40273 40274 40275 40276 40277 40278 40279 40280 40281 40282 40283 40284 40285 40286 40287 40288 40289

Read Write Read Write Read Write Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0269 D0270 D0271 D0272 D0273 D0274 D0275 D0276 D0277 D0278 D0279 D0280 D0281 D0282 D0283 D0284 D0285 D0286 D0287 D0288

Undefined Undefined Undefined MSB:b15:X/Y000 FhLSB:b0:X/Y0 000h MSB:b15:X/Y001 FhLSB:b0:X/Y0 010h MSB:b15:X/Y002 FhLSB:b0:X/Y0 020h MSB:b15:X/Y003 FhLSB:b0:X/Y0 030h MSB:b15:X/Y004 FhLSB:b0:X/Y0 040h MSB:b15:X/Y005 FhLSB:b0:X/Y0 050h MSB:b15:X/Y006 FhLSB:b0:X/Y0 060h MSB:b15:X/Y007 FhLSB:b0:X/Y0 070h MSB:b15:Y008Fh LSB:b0:Y0080h MSB:b15:Y009Fh LSB:b0:Y0090h MSB:b15:Y00AFh LSB:b0:Y00A0 h MSB:b15:Y00BFh LSB:b0:Y00B0 h MSB:b15:Y00CFh LSB:b0:Y00C0 h MSB:b15:Y00DFh LSB:b0:Y00D0 h MSB:b15:Y00EFh LSB:b0:Y00E0 h MSB:b15:Y00FFh LSB:b0:Y00F0h MSB:b15:Y010Fh LSB:b0:Y0100h

-32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767

Control Control Control Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor

Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O ALARM Refer Coils number 00129 to 00256

FAILURE

- 144 -

QT108300

(continued)
Register Number 40290 40291 40292 40293 40294 40295 40296 40297 40298 40299 40300 40301 40302 40303 40304 40305 40306 40307 40308 40309 40310 40311 40312 40313 40314 40315 40316 40317 40318 40319 40320 40321 40322 40323 40324 40325 40326 40327 40328 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0289 D0290 D0291 D0292 D0293 D0294 D0295 D0296 D0297 D0298 D0299 D0300 D0301 D0302 D0303 D0304 D0305 D0306 D0307 D0308 D0309 D0310 D0311 D0312 D0313 D0314 D0315 D0316 D0317 D0318 D0319 D0320 D0321 D0322 D0323 D0324 D0325 D0326 D0327 Name MSB:b15:Y011Fh LSB:b0:Y0110h MSB:b15:Y012Fh LSB:b0:Y0120h MSB:b15:Y013Fh LSB:b0:Y0130h MSB:b15:Y014Fh LSB:b0:Y0140h MSB:b15:Y015Fh LSB:b0:Y0150h MSB:b15:Y016Fh LSB:b0:Y0160h MSB:b15:Y017Fh LSB:b0:Y0170h MSB:b15:X00CFh LSB:b0:X00C0 h MSB:b15:X00DFh LSB:b0:X00D0 h MSB:b15:X00EFh LSB:b0:X00E0 h MSB:b15:X00FFh LSB:b0:X00F0h MSB:b15:X010Fh LSB:b0:X0100h MSB:b15:X011Fh LSB:b0:X0110h MSB:b15:X012Fh LSB:b0:X0120h MSB:b15:X013Fh LSB:b0:X0130h MSB:b15:X014Fh LSB:b0:X0140h MSB:b15:X015Fh LSB:b0:X0150h MSB:b15:X016Fh LSB:b0:X0160h MSB:b15:X017Fh LSB:b0:X0170h Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined RUN TIME (Low Word) RUN TIME (High Word) Suction Pressure(n=3) Discharge Pressure(n=2) Oil Supply Pressure(n=2) After Filter Pressure(n=2) Suction Temperature(n=1) Discharge Temperature(n=1) Oil Supply Temperature(n=1) PLATFORM: US, Oil Separator Temperature(n=1) PLATFORM: EU, After Fine Filter Pressure(n=2) PLATFORM:AS, OPTION ANALOG INPUT1 to 4 PLATFORM: AS, Undefined Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Hour X 65536 Hours Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Monitor Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Category Sub Category Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Calculated Calculated Calculated Calculated Calculated Calculated Calculated Calculated Calculated Calculated Calculated Calculated 1/64 2/64 3/64 4/64 5/64 6/64 7/64 8/64 SP DP OP AFP ST DT OT OS AFFP OPT1 to OPT4 COMMUNICATIO N Refer Coils number 00513 to 576 CONFIGURATION Refer Coils number 00449 to 512 Note Refer Coils number 00257 to 00384

MODE Refer Coils number 00385 to 448

RUN TIME = 65536 X (40320) + (40319) HOURS

N.C.

- 145 -

QT108300

(continued)
Register Number 40329 Attribute Read Only Internal Word Device D0328 Name Intermediate Pressure(n=2) OPTION ANALOG INPUT1 to 4 Undefined Intermediate Temperature(n=1) OPTION ANALOG INPUT1 to 4 Undefined System Discharge Pressure(n=2) OPTION ANALOG INPUT1 to 4 Undefined Compressor Motor Electric Current(n=0 to 1) Chiller Entering Brine Temperature(n=1) OPTION ANALOG INPUT1 to 4 Undefined Chiller Leaving Brine Temperature(n=1) OPTION ANALOG INPUT1 to 4 Undefined (Low Stage) Slide Valve Position(n=1) High Stage Slide Valve Position(n=1) Vi Port Slide Valve Position(n=1) System Suction Pressure(n=3) OPTION ANALOG INPUT1 to 4 Undefined Chiller Suction Pressure1(n=3) Undefined Chiller Gas Temperature1(n= 1) Undefined System Suction Pressure(n=3) Undefined Remote Analog Capacity Input Undefined OPTION ANALOG INPUT1 to 4 Undefined OPTION ANALOG INPUT1 to 4 Undefined OPTION ANALOG INPUT1 to 4 Undefined OPTION ANALOG INPUT1 to 4 Undefined Chiller Suction Pressure1(n=3) Undefined Range Industrial Unit X 10^n Real AI Category Sub Category 9/64 IP OPT1 to OPT4 N.C. IT OPT1 to OPT4 N.C. SDP OPT1 to OPT4 N.C. MA EBT OPT1 to OPT4 N.C. LBT OPT1 to OPT4 N.C. LSV (on VFD COMPRESSOR, capacity is number 40394.) HSV PSV SSP OPT1 to OPT4 N.C. SP1 N.C. GT1 N.C. SSP N.C. RLD N.C. OPT1 to OPT4 N.C. OPT1 to OPT4 N.C. OPT1 to OPT4 N.C. OPT1 to OPT4 N.C. SP2 N.C. Note

40330

Read Only

D0329

Industrial Unit X 10^n

Real AI

10/64

40331

Read Only

D0330

Industrial Unit X 10^n

Real AI

11/64

40332 40333

Read Only Read Only

D0331 D0332

Industrial Unit X 10^n Industrial Unit X 10^n

Real AI Real AI

12/64 13/64

40334

Read Only

D0333

Industrial Unit X 10^n

Real AI

14/64

40335

Read Only

D0334

Industrial Unit X 10^n

Real AI

15/64

40336

Read Only

D0335

Industrial Unit X 10^n

Real AI

16/64

40337 40338

Read Only Read Only

D0336 D0337

Industrial Unit X 10^n Industrial Unit X 10^n

Real AI Real AI

17/64 18/64

40339 40340 40341

Read Only Read Only Read Only

D0338 D0339 D0340

Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n

Real AI Real AI Real AI

19/64 20/64 21/64

40342

Read Only

D0341

Industrial Unit X 10^n

Real AI

22/64

40343

Read Only

D0342

Industrial Unit X 10^n

Real AI

23/64

40344

Read Only

D0343

Industrial Unit X 10^n

Real AI

24/64

40345

Read Only

D0344

Industrial Unit X 10^n

Real AI

25/64

- 146 -

QT108300

(continued)
Register Number 40346 Attribute Read Only Internal Word Device D0345 Name Chiller Gas Temperature1(n= 1) Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Range Industrial Unit X 10^n Real AI Category Sub Category 26/64 GT2 N.C. Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI Real AI 27/64 28/64 29/64 30/64 31/64 32/64 33/64 34/64 35/64 36/64 37/64 38/64 39/64 40/64 41/64 42/64 43/64 44/64 45/64 46/64 47/64 48/64 49/64 50/64 51/64 52/64 53/64 54/64 55/64 56/64 57/64 58/64 59/64 60/64 61/64 62/64 63/64 64/64 Note

40347 40348 40349 40350 40351 40352 40353 40354 40355 40356 40357 40358 40359 40360 40361 40362 40363 40364 40365 40366 40367 40368 40369 40370 40371 40372 40373 40374 40375 40376 40377 40378 40379 40380 40381 40382 40383 40384

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0346 D0347 D0348 D0349 D0350 D0351 D0352 D0353 D0354 D0355 D0356 D0357 D0358 D0359 D0360 D0361 D0362 D0363 D0364 D0365 D0366 D0367 D0368 D0369 D0370 D0371 D0372 D0373 D0374 D0375 D0376 D0377 D0378 D0379 D0380 D0381 D0382 D0383

- 147 -

QT108300

Holding Registers number 40385 to 40512 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 40385 40386 40387 Attribute Read Only Read Only Read Only Internal Word Device D0384 D0385 D0386 Name Oil Differential Pressure(DP OP) (n=2) Filter Differential Pressure(DP AFP) (n=2) Differential Pressure (n=2) Single(AFP SP),Compound(A FP - IP) Suction Superheat(n=1) Intermediate Superheat(n=1) Discharge Superheat(n=1) Ratio: DPSP(n=2) Calculated Vi(n=2) Current Vi 2.63/3.65/5.80, 2.50/3.50/5.00(n= 2) Capacity/VFD Output(n=1) (Low Stage)Slide Valve Percent(n=1) AUTO STAGE Target-Pressure( n=3) Oil Differential Pressure2(OP2-D P)(n=2) Suction Superheat2(n=1) Fine Filter Differential Pressure(DP AFFP) (n=2) AUTO STAGE Target-Temperatu re(n=1) PV: Process Value/SP(n=3) SV: Set Value(n=3) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/SP(n=3) SV: Set Value(n=3) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) Range Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Category Pseudo AI Pseudo AI Pseudo AI Sub Category 1/16 2/16 3/16 OP FP P Note

40388 40389 40390 40391 40392 40393

Read Only Read Only Read Only Read Only Read Only Read Only

D0387 D0388 D0389 D0390 D0391 D0392

Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n

Pseudo AI Pseudo AI Pseudo AI Pseudo AI Pseudo AI Pseudo AI

4/16 5/16 6/16 7/16 8/16 9/16

SSH ISH DSH D/S Vi CRVi

40394 40395 40396 40397 40398 40399

Read Only Read Only Read Only Read Only Read Only Read Only

D0393 D0394 D0395 D0396 D0397 D0398

Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n

Pseudo AI Pseudo AI Pseudo AI Pseudo AI Pseudo AI Pseudo AI

10/16 11/16 12/16 13/16 14/16 15/16

CAP SVP F1:7.AUTO STAGE>CONTRO L SET POINT OP2 SH2 FFP

40400 40401 40402 40403 40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40419 40420 40421

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0399 D0400 D0401 D0402 D0403 D0404 D0405 D0406 D0407 D0408 D0409 D0410 D0411 D0412 D0413 D0414 D0415 D0416 D0417 D0418 D0419 D0420

Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

Pseudo AI Capacity Control Suction Pressure

16/16 PID 1/16 Read Area

F1:7.AUTO STAGE>CONTRO L SET POINT

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000

Capacity Control Chiller LB Temperature

PID 2/16 Read Area

- 148 -

QT108300

(continued)
Register Number 40422 40423 40424 40425 40426 40427 40428 40429 40430 40431 40432 40433 40434 40435 40436 40437 40438 40439 40440 40441 40442 40443 40444 40445 40446 40447 40448 40449 40450 40451 40452 40453 40454 40455 40456 40457 40458 40459 40460 40461 40462 40463 40464 40465 40466 40467 40468 40469 40470 40471 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0421 D0422 D0423 D0424 D0425 D0426 D0427 D0428 D0429 D0430 D0431 D0432 D0433 D0434 D0435 D0436 D0437 D0438 D0439 D0440 D0441 D0442 D0443 D0444 D0445 D0446 D0447 D0448 D0449 D0450 D0451 D0452 D0453 D0454 D0455 D0456 D0457 D0458 D0459 D0460 D0461 D0462 D0463 D0464 D0465 D0466 D0467 D0468 D0469 D0470 Name INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/SP(n=3) SV: Set Value(n=3) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/SP(n=3) SV: Set Value(n=3) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/SP(n=3) SV: Set Value(n=3) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) Range 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n Category Sub Category Note

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

Suction Superheat Limitation by Suction Pressure

PID 3/16 Read Area

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

Suction Superheat Limitation by Chiller LB Temperature

PID 3/16 Read Area

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600

Suction Superheat Limitation by Chiller LB Temperature

PID 5/16 Read Area

- 149 -

QT108300

(continued)
Register Number 40472 40473 40474 40475 40476 40477 40478 40479 40480 40481 40482 40483 40484 40485 40486 40487 40488 40489 40490 40491 40492 40493 40494 40495 40496 40497 40498 40499 40500 40501 40502 40503 40504 40505 40506 40507 40508 40509 40510 40511 40512 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0471 D0472 D0473 D0474 D0475 D0476 D0477 D0478 D0479 D0480 D0481 D0482 D0483 D0484 D0485 D0486 D0487 D0488 D0489 D0490 D0491 D0492 D0493 D0494 D0495 D0496 D0497 D0498 D0499 D0500 D0501 D0502 D0503 D0504 D0505 D0506 D0507 D0508 D0509 D0510 D0511 Name MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/SP(n=2) SV: Set Value(n=2) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/DT(n=1) or DSH(n=1) SV: Set Value(n=1) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANAUL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved Range 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n Category Sub Category Note

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

Intercooler Control Intermediate Superheat

PID 6/16 Read Area

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

Liquid Injection YOSAKU Discharge Temperature or Discharge Superheat

PID 7/16 Read Area

- 150 -

QT108300

Holding Registers number 40513 to 40640 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 40513 40514 40515 40516 40517 40518 40519 40520 40521 40522 40523 40524 40525 40526 40527 40528 40529 40530 40531 40532 40533 40534 40535 40536 40537 40538 40539 40540 40541 40542 40543 40544 40545 40546 40547 40548 40549 40550 40551 40552 40553 40554 40555 40556 40557 40558 40559 40560 40561 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0512 D0513 D0514 D0515 D0516 D0517 D0518 D0519 D0520 D0521 D0522 D0523 D0524 D0525 D0526 D0527 D0528 D0529 D0530 D0531 D0532 D0533 D0534 D0535 D0536 D0537 D0538 D0539 D0540 D0541 D0542 D0543 D0544 D0545 D0546 D0547 D0548 D0549 D0550 D0551 D0552 D0553 D0554 D0555 D0556 D0557 D0558 D0559 D0560 Name PV: Process Value/SP(n=1) SV: Set Value(n=1) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/DP(n=2) SV: Set Value(n=2) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/IP(n=2) SV: Set Value(n=2) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANAUL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/SP(n=3) Range Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n Category Chiller Flow Control Chiller LB Temperature Sub Category PID 8/16 Read Area Note

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

VFD Condenser Fan Control Discharge Pressure

PID 9/16 Read Area

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

High Stage Capacity Control Intermediate Pressure

PID10/16 Read Area

Industrial Unit X 10^n

VFD Capacity Control

PID11/16

- 151 -

QT108300

(continued)
Register Number 40562 40563 40564 40565 40566 40567 40568 40569 40570 40571 40572 40573 40574 40575 40576 40577 40578 40579 40580 40581 40582 40583 40584 40585 40586 40587 40588 40589 40590 40591 40592 40593 40594 40595 40596 40597 40598 40599 40600 40601 40602 40603 40604 40605 40606 40607 40608 40609 40610 40611 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0561 D0562 D0563 D0564 D0565 D0566 D0567 D0568 D0569 D0570 D0571 D0572 D0573 D0574 D0575 D0576 D0577 D0578 D0579 D0580 D0581 D0582 D0583 D0584 D0585 D0586 D0587 D0588 D0589 D0590 D0591 D0592 D0593 D0594 D0595 D0596 D0597 D0598 D0599 D0600 D0601 D0602 D0603 D0604 D0605 D0606 D0607 D0608 D0609 D0610 Name SV: Set Value(n=3) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/LBT(n=1) SV: Set Value(n=1) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/SH2(n=1) SV: Set Value(n=1) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/SP2(n=3) SV: Set Value(n=3) Reserved Range Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n Category Suction Pressure Sub Category Read Area Note

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

VFD Capacity Control Chller LB Temperature

PID12/16 Read Area

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

Suction Superheat2

PID13/16 Read Area

Industrial Unit X 10^n Industrial Unit X 10^n

Suction Superheat2 Limitation by Suction Pressure2

PID14/16 Read Area

- 152 -

QT108300

(continued)
Register Number 40612 40613 40614 40615 40616 40617 40618 40619 40620 40621 40622 40623 40624 40625 40626 40627 40628 40629 40630 40631 40632 40633 40634 40635 40636 40637 40638 40639 40640 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0611 D0612 D0613 D0614 D0615 D0616 D0617 D0618 D0619 D0620 D0621 D0622 D0623 D0624 D0625 D0626 D0627 D0628 D0629 D0630 D0631 D0632 D0633 D0634 D0635 D0636 D0637 D0638 D0639 Name MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved PV: Process Value/LVL%(n=1) SV: Set Value%(n=1) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved Range 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n Category Sub Category Note

Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n

Level Control Chiller Liquid Level

PID15/16 Read Area

- 153 -

QT108300

Holding Registers number 40641 to 40768 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 40641 40642 40643 40644 40645 40646 40647 40648 40649 40650 40651 40652 40653 40654 40655 40656 40657 40658 40659 40660 40661 40662 40663 40664 40665 40666 40667 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Write Internal Word Device D0640 D0641 D0642 D0643 D0644 D0645 D0646 D0647 D0648 D0649 D0650 D0651 D0652 D0653 D0654 D0655 D0656 D0657 D0658 D0659 D0660 D0661 D0662 D0663 D0664 D0665 D0666 Name PV: Process Value/undefined SV: Set Value(n=?) Reserved MV:PID OUT%(n=1) PROPORTIONAL BAND%(n=1) INTEGRAL TIME Sec(n=0) DERIVATIVE TIME Sec(n=0) MANUAL RESET%(n=1) Reserved MV LIMIT%/Sec(n=1) MVL%(n=1) MVH%(n=1) Slow Open Sec(n=0) DEAD BAND/SP(n=3) Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved MVL%(n=1) Range Industrial Unit X 10^n Industrial Unit X 10^n 0 to 1000 10 to 2000 0 to 1800 0 to 600 0 to 1000 1 to 1000 0 to MVH% MVL% to 1000 -600 to 600 Industrial Unit X 10^n Category Undefined Sub Category PID16/16 Read Area Note

Capacity Control Suction Pressure

PID 1/16 Write Area

0 to MVH% X 10

40668

Read Write

D0667

MVH%(n=1)

MVL% X 10 to 1000

Required F2:1.CAPACITY CONTROL>MVL% /MVH% BY COMM:ENABLE Required F2:1.CAPACITY CONTROL>MVL% /MVH% BY COMM:ENABLE

40669 40670 40671 40672 40673 40674 40675 40676 40677 40678 40679 40680 40681 40682 40683

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Write

D0668 D0669 D0670 D0671 D0672 D0673 D0674 D0675 D0676 D0677 D0678 D0679 D0680 D0681 D0682

Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved MVL%(n=1)

Capacity Control Chiller LB Temperature

PID 2/16 Write Area

0 to MVH% X 10

40684

Read Write

D0683

MVH%(n=1)

MVL% X 10 to 1000

Required F2:1.CAPACITY CONTROL>MVL% /MVH% BY COMM:ENABLE Required F2:1.CAPACITY CONTROL>MVL% /MVH% BY COMM:ENABLE

40685 40686 40687 40688 40689 40690 40691 40692 40693 40694

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0684 D0685 D0686 D0687 D0688 D0689 D0690 D0691 D0692 D0693

Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved

Suction Superheat Limitation by Suction Pressure

PID 3/16 Write Area

- 154 -

QT108300

(continued)
Register Number 40695 40696 40697 40698 40699 40700 40701 40702 40703 40704 40705 40706 40707 40708 40709 40710 40711 40712 40713 40714 40715 40716 40717 40718 40719 40720 40721 40722 40723 40724 40725 40726 40727 40728 40729 40730 40731 40732 40733 40734 40735 40736 40737 40738 40739 40740 40741 40742 40743 40744 40745 40746 40747 40748 40749 40750 40751 40752 40753 40754 40755 40756 40757 40758 40759 40760 40761 40762 40763 40764 40765 40766 40767 40768 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0694 D0695 D0696 D0697 D0698 D0699 D0700 D0701 D0702 D0703 D0704 D0705 D0706 D0707 D0708 D0709 D0710 D0711 D0712 D0713 D0714 D0715 D0716 D0717 D0718 D0719 D0720 D0721 D0722 D0723 D0724 D0725 D0726 D0727 D0728 D0729 D0730 D0731 D0732 D0733 D0734 D0735 D0736 D0737 D0738 D0739 D0740 D0741 D0742 D0743 D0744 D0745 D0746 D0747 D0748 D0749 D0750 D0751 D0752 D0753 D0754 D0755 D0756 D0757 D0758 D0759 D0760 D0761 D0762 D0763 D0764 D0765 D0766 D0767 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Range Category Sub Category Note

Suction Superheat Limitation by Chiller LB Temperature

PID 3/16 Write Area

Suction Superheat Limitation by Chiller LB Temperature

PID 5/16 Write Area

Intercooler Control Intermediate Superheat

PID 6/16 Write Area

Liquid Injection YOSAKU Discharge Temperature or Discharge Superheat

PID 7/16 Write Area

- 155 -

QT108300

Holding Registers number 40769 to 40896 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 40769 40770 40771 40772 40773 40774 40775 40776 40777 40778 40779 40780 40781 40782 40783 40784 40785 40786 40787 40788 40789 40790 40791 40792 40793 40794 40795 40796 40797 40798 40799 40800 40801 40802 40803 40804 40805 40806 40807 40808 40809 40810 40811 40812 40813 40814 40815 40816 40817 40818 40819 40820 40821 40822 40823 40824 40825 40826 40827 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Write Internal Word Device D0768 D0769 D0770 D0771 D0772 D0773 D0774 D0775 D0776 D0777 D0778 D0779 D0780 D0781 D0782 D0783 D0784 D0785 D0786 D0787 D0788 D0789 D0790 D0791 D0792 D0793 D0794 D0795 D0796 D0797 D0798 D0799 D0800 D0801 D0802 D0803 D0804 D0805 D0806 D0807 D0808 D0809 D0810 D0811 D0812 D0813 D0814 D0815 D0816 D0817 D0818 D0819 D0820 D0821 D0822 D0823 D0824 D0825 D0826 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved MVL%(n=1) Range Category Chiller Flow Control Chiller LB Temperature Sub Category PID 8/16 Write Area Note

VFD Condenser Fan Control Discharge Pressure

PID 9/16 Write Area

High Stage Capacity Control Intermediate Pressure

PID10/16 Write Area

VFD Capacity Control Suction Pressure

PID11/16 Write Area

0 to MVH% X 10

40828

Read Write

D0827

MVH%(n=1)

MVL% X 10 to 1000

Required F2:2.VFD COMPRESSOR> MVL%/MVH% BY COMM:ENABLE Required F2:2.VFD COMPRESSOR> MVL%/MVH% BY COMM:ENABLE

40829 40830 40831 40832 40833 40834 40835 40836 40837 40838

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0828 D0829 D0830 D0831 D0832 D0833 D0834 D0835 D0836 D0837

Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved

VFD Capacity Control Chiller LB Temperature

PID12/16 Write Area

- 156 -

QT108300

(continued)
Register Number 40839 40840 40841 40842 40843 Attribute Read Only Read Only Read Only Read Only Read Write Internal Word Device D0838 D0839 D0840 D0841 D0842 Name Reserved Reserved Reserved Reserved MVL%(n=1) Range Category Sub Category Note

0 to MVH% X 10

40844

Read Write

D0843

MVH%(n=1)

MVL% X 10 to 1000

Required F2:2.VFD COMPRESSOR> MVL%/MVH% BY COMM:ENABLE Required F2:2.VFD COMPRESSOR> MVL%/MVH% BY COMM:ENABLE

40845 40846 40847 40848 40849 40850 40851 40852 40853 40854 40855 40856 40857 40858 40859 40860 40861 40862 40863 40864 40865 40866 40867 40868 40869 40870 40871 40872 40873 40874 40875 40876 40877 40878 40879 40880 40881 40882 40883 40884 40885 40886 40887 40888 40889 40890 40891 40892 40893 40894 40895 40896

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0844 D0845 D0846 D0847 D0848 D0849 D0850 D0851 D0852 D0853 D0854 D0855 D0856 D0857 D0858 D0859 D0860 D0861 D0862 D0863 D0864 D0865 D0866 D0867 D0868 D0869 D0870 D0871 D0872 D0873 D0874 D0875 D0876 D0877 D0878 D0879 D0880 D0881 D0882 D0883 D0884 D0885 D0886 D0887 D0888 D0889 D0890 D0891 D0892 D0893 D0894 D0895

Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved

Suction Superheat2

PID13/16 Write Area

Suction Superheat2 Limitation by Suction Pressure2

PID14/16 Write Area

Level Control Chiller Liquid Level

PID15/16 Write Area

- 157 -

QT108300

Holding Registers number 40897 to 40960 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 40897 40898 40899 40900 40901 40902 40903 40904 40905 40906 40907 40908 40909 40910 40911 40912 40913 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D0896 D0897 D0898 D0899 D0900 D0901 D0902 D0903 D0904 D0905 D0906 D0907 D0908 D0909 D0910 D0911 D0912 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved REMOTE CAPACITY DIGITAL CONTROL OPTION OPTION ANALOG INPUT CONDENSER VFD CONTROL OPTION CONDENSER 3-STEP CONTROL OPTION CONDENSER 6-STEP CONTROL OPTION CHILLER CONTROL OPTION AUTO-STAGEIN G OPTION COMMUNICATIO NS OPTION VFD COMPRESSOR OPTION HIGH STAGE CAPACITY CONTROL OPTION AUTO-Vi CONTROL OPTION LIQUID INJECTION OIL COOLING CONTROL OPTION TIME PROPORTIONAL CONTROL for NO SLIDE POT. OPTION HOT GAS BYPASS CONTROL OPTION STARTING BYPASS CONTROL OPTION ECONOMIZER/IN TER COOLER EXPANSION VALVE CONTROL OPTION COMPRESSOR OIL SEAL CONTROL OPTION Range (Figure in ( ) is default value.) Category Undefined Sub Category PID16/16 Write Area Note

(0):DISABLE,1:ENABLE

Settings

40914 40915

Read Only Read Only

D0913 D0914

(0):DISABLE,1:ENABLE (0):DISABLE ,1:VFD ONLY ,2:VFD + 2STEPS ,3:VFD + 3STEPS ,4:VFD + 5STEPS (0):DISABLE,1:ENABLE

40916

Read Only

D0915

40917

Read Only

D0916

(0):DISABLE,1:ENABLE

40918 40919 40920 40921 40922

Read Only Read Only Read Only Read Only Read Only

D0917 D0918 D0919 D0920 D0921

(0):DISABLE,1:ENABLE (0):DISABLE,1:ENABLE (0):DISABLE,1:ENABLE (0):DISABLE,1:ENABLE (0):DISABLE,1:ENABLE

40923 40924

Read Only Read Only

D0922 D0923

(0):DISABLE,1:ENABLE (0):DISABLE,1:ENABLE

40925

Read Only

D0924

(0):DISABLE,1:ENABLE

40926

Read Only

D0925

(0):DISABLE,1:ENABLE

40927

Read Only

D0926

(0):DISABLE,1:ENABLE

40928

Read Only

D0927

(0):DISABLE,1:ENABLE

40929

Read Only

D0928

(0):DISABLE,1:ENABLE

- 158 -

QT108300

(continued)
Register Number 40930 Attribute Read Only Internal Word Device D0929 Name 400 SERIES COMPRESSOR CONTROL OPTION LEVEL CONTROL SETUP Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved REMOTE CAPACITY CONTROL SETUP CONDENSER CONTROL SETUP CONDENSER CONTROL/CONT ROL TARGET Range (Figure in ( ) is default value.) (0):DISABLE,1:ENABLE Category Sub Category Note

40931 40932 40933 40934 40935 40936 40937 40938 40939 40940 40941

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0930 D0931 D0932 D0933 D0934 D0935 D0936 D0937 D0938 D0939 D0940

(0):DISABLE,1:ENABLE -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 (0):None ,1:DIGITAL ,2:ANALOG (0):NOT USE,1:USE (0):LOACAL DISCHARGE PRESSURE ,1:SYSTEM DISCHARGE PRESSURE (0):ON-OFF SINGLE SET,1:ON-OFF MULTI SET (0):NOT USE,1:USE (0):1SV,1:2SV,2:3SV 0:None/THERMAL EXPANSION ,1:YOSAKU 1-VALVE ,2:YOSAKU 2-VALVES ,3:YOSAKU 3-VALVES ,(4):1-MOTORIZED CONTROL VALVE ,5:2-MOTORIZED CONTROL VALVE (0):NO,1:YES

40942 40943

Read Only Read Only

D0941 D0942

40944 40945 40946 40947

Read Only Read Only Read Only Read Only

D0943 D0944 D0945 D0946

CONDENSER CONTROL/CONT ROL METHOD CHILLER CONTROL SETUP CHILLER CONTROL/LIQUI D SUPPLY SV CHILLER CONTROL/EXPA NSION VALVE

40948

Read Only

D0947

40949

Read Only

D0948

40950

Read Only

D0949

40951

Read Only

D0950

40952 40953 40954

Read Only Read Only Read Only

D0951 D0952 D0953

CHILLER CONTROL/CHILL ER GAS TEMP. SENOR CHILLER CONTROL/CHILL ER ENTERING TEMP. SENSOR CHILLER CONTROL/CHILL ER LEAVING TEMP. SENSOR CHILLER CONTROL/CHILL ER LEAVING TEMP. CONTROL CHILLER CONTROL/CHILL ER PUMP MODE AUTO STAGER SETUP>STAGED COMPRESSORS EXPANSION VALVE CONTROL VFD COMPRESSOR SETUP HIGH STAGE CAPACITY CONTROL SETUP

(0):NO,1:YES

(0):NO,1:YES

(0):NOT USE,1:USE

0:CONTINUOUS ,(1):AUTO START/STOP (0) to 8UNITS (0):SH ONLY,1SH W/ SP LIMIT,2SH W/ LB LIMIT,3:SH W/ SP & LB LIMIT (0):NOT USE,1:USE (0):NOT USE,1:USE

40955 40956

Read Only Read Only

D0954 D0955

- 159 -

QT108300

(continued)
Register Number 40957 Attribute Read Only Internal Word Device D0956 Name AUTO-Vi CONTROL SETUP Range (Figure in ( ) is default value.) (0):NOT USE ,1:USE DO10,11,12,16,17(UDV) ,2:USE DO19,1A,1B,1C,1D(UDV) .3.USE(J1) (0):NOT USE,1:USE Category Sub Category Note

40958

Read Only

D0957

40959

Read Only

D0958

LIQUID INJECTION OIL COOLING CONTROL SETUP LIQUID INJECTION OIL COOLING CONTROL/INJEC TION VALVES LIQUID INJECTION OIL COOLING CONTROL/CONT ROL TARGET

40960

Read Only

D0959

0:None/THERMAL EXPANSION ,(1):YOSAKU 1-VALVE ,2:YOSAKU 2-VALVES ,3:MOTORIZED CONTROL VALVE (0):DISCHARGE TEMPERATURE 1:DISCHARGE SUPERHAET

- 160 -

QT108300

Holding Registers number 40961 to 41024 (Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 40961 40962 Attribute Read Only Read Only Internal Word Device D0960 D0961 Name LEVEL CONTROL SETUP HOT GAS BYPASS CONTROL SETUP STARTING BYPASS CONTROL SETUP ECONOMIZER/IN TER COOLER EXPANSION VALVE CONTROL SETUP ECONOMIZER/IN TER COOLER EXPANSION VALVE CONTROL/EXPA NSION VALVES COMPRESSOR OIL SEAL CONTROL SETUP CONTROL TARGET(CUT-IN/ OUT) SETUP Range (Figure in ( ) is default value.) (0):NOT USE,1:USE (0):NOT USE,1:USE Category Sub Category Note

40963

Read Only

D0962

(0):NOT USE,1:USE

40964

Read Only

D0963

(0):NOT USE,1:USE

40965

Read Only

D0964

0:None/THERMAL EXPANSION ,(1):YOSAKU ,2:MOTORIZED CONTROL VALVE (0):NOT USE,1:USE

40966

Read Only

D0965

40967

Read Only

D0966

40968

Read Only

D0967

CONTROL TARGET(CAPAC ITY CONTROL) SETUP

40969

Read Only

D0968

40970 40971

Read Only Read Only

D0969 D0970

40972 40973 40974 40975 40976 40977 40978 40979 40980 40981 40982

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0971 D0972 D0973 D0974 D0975 D0976 D0977 D0978 D0979 D0980 D0981

CHILLER CONTROL/CHILL ER GAS PRESS. SENOR OPTION SETUP VFD OUTPUT LIMIT ECONOMIZER INTERCOOLER LIQUID SUPPLY CONTROL Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved I/O PLATFORM APPLICATION TYPE(Reserved)

(0):LOACAL SUCTION PRESSURE ,1:SYSTEM SUCTION PRESSURE ,2:CHILLER ENTERING TEMPERATURE ,3:CHILLER LEAVING TEMPERATURE (0):LOACAL SUCTION PRESSURE ,1:SYSTEM SUCTION PRESSURE ,2:CHILLER LEAVING TEMPERATURE ,3:COMBINED LB/LOCAL SP ,4:COMBINED LB/SYSTEM SP ,5:DISCHARGE PRESSURE (0):NO,1:YES

(0):NOT USE,1:USE 0:LSV&SP,(1):HSV&IP

-32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 (0):NORTH AMERICA,1:EUROPE,2 :ASIA -32768 to 32767

- 161 -

QT108300

(continued)
Register Number 40983 Attribute Read Only Internal Word Device D0982 Name COMPRESSOR Range (Figure in ( ) is default value.) (0):SINGLE ,1:ECONOMIZER W/O SENSOR ,2:ECONOMIZER W/ SENSOR ,3:COMPOUND-1(1610 & 1612) ,4:COMPOUND-2(2016 & HIGHER) ,5:SINGLE UD-V(VARIABLE Vi) ,6:400 SERIES .7:SINGLE J ,8.SINGLE J ECONOMIZER W/O SENSOR ,9.SINGLE J ECONOMIZER W/ SENSOR .10:FM160 ,11.FM160 ECONOMIZER W/O SENSOR ,12.FM160 ECONOMIZER W/ SENSOR (0):FULL LUBE ,1:PRE LUB,2:PARTIAL LUBE 0:CHANGE TO LOCAL MODE (1):KEEP CURRENT MODE 0:CHANGE TO LOCAL MODE (1):KEEP CURRENT MODE (0):AUTO RESET ,1:KEYPAD 0:NO,(1):YES 0:W/O OIL PUMP ,(1):W/ 1-OIL PUMP ,2:W/ 2-OIL PUMPS (0):LEAD Y01/LAG Y14 ,1:LEAD Y14/LAG Y01 (0):NORMAL OPEN,1:NORMAL CLOSE 0:NO,(1):YES (0):NO,1:YES -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 (0):DP-AFP,1:BFP-OP,2 :DP-OP (0):OBVERSE,1:REVER SE (0):NO,1:YES Category Sub Category Note

40984 40985

Read Only Read Only

D0983 D0984

OIL FEED TYPE OPERATION MODE ON FAILURE OPERATION MODE RESTORE ON POWER UP ALARM RESET ALARM OUTPUT OIL PUMP OIL PUMP LAEAD/LAG ALARM/FAILURE OUTPUT TYPE OIL SEPARATOR TEMP. SENSOR AFTER FINE FILTER PRESS. SENSOR Reserved Reserved Reserved Reserved DFP CALCULATION LOAD INDICATOR LOCATION OPERATION MODE>D/O TEST OPERATION OPERATION MODE>OPERATI ON OPERATION MODE>COMPRE SSOR AUTO START/STOP SET POINTS>SYSTE M START>SYSTEM START DELAY SET POINTS>MISCEL LANEOUS>CUT-I N DELAY

40986

Read Only

D0985

40987 40988 40989 40990 40991 40992 40993 40994 40995 40996 40997 40998 40999 41000

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D0986 D0987 D0988 D0989 D0990 D0991 D0992 D0993 D0994 D0995 D0996 D0997 D0998 D0999

41001

Read Write

D1000

41002

Read Write

D1001

(0):LOCAL ,1:REMOTE ,2:COMM ,3AUTO STAGE 0:NO,(1):YES

41003

Read Only

D1002

0 to 600(10)Sec X 10

41004

Read Only

D1003

0 to 600(10)Sec X 10

- 162 -

QT108300

(continued)
Register Number 41005 Attribute Read Only Internal Word Device D1004 Name SET POINTS>MISCEL LANEOUS>CUTOUT DELAY SET POINTS>MISCEL LANEOUS>CUTOUT LSV% SET POINTS>MISCEL LANEOUS>OIL P. START DELAY SET POINTS>MISCEL LANEOUS>COM P. START DELAY SET POINTS>MISCEL LANEOUS>COM P. RE-START DELAY SET POINTS>MISCEL LANEOUS>OIL FEED OFF DELAY SET POINTS>PUMP OUT>CAPACITY 0% STOP SET POINTS>PUMP OUT>MINIMUM DELAY SET POINTS>PUMP OUT>MAXIMUM DELAY SET POINTS>PUMP OUT>PUMP OUT PRESS. SET POINTS>PUMP OUT>PUMP OUT LSV% SET POINTS>PUMP OUT>STOP LSV% SET POINTS>SCHED ULER>CUT IN/CUT OUT SET POINTS>SCHED ULER>CONTRO L TARGET SCHEDULED CUT-IN SET POINT SCHEDULED PRESSURE CONTROL SET POINT SCHEDULED TEMPERATURE CONTROL SET POINT SCHEDULED CUT-OUT SET POINT CUT-IN SET POINT #1 PRESSURE CONTROL SET POINT #1 Range (Figure in ( ) is default value.) 0 to 600(10)Sec X 10 Category Sub Category Note

41006

Read Only

D1005

0 to 100%(0):0 to 4095

41007

Read Only

D1006

0 to 600(10)Sec X 10

41008

Read Only

D1007

0 to 600(10)Sec X 10

41009

Read Only

D1008

0 to 600(10)Sec X 10

41010

Read Only

D1009

0 to 600(10)Sec X 10

41011

Read Only

D1010

0:NO,(1):YES

41012

Read Only

D1011

0 to 600(10)Sec X 10

41013

Read Only

D1012

0 to 600(30)Sec X 10

41014

Read Only

D1013

Range Low to High:0 to 4095 0.0 to 100.0(100.0)%:0 to 4095 0.0 to 100.0(0.0)%:0 to 4095 (0):SETPOINT #1 ,1:SETPOINT #2 ,2:SETPOINT #3 ,3:SETPOINT #4 ,4:SCHEDULER ,5:COMM (0):SETPOINT #1 ,1:SETPOINT #2 ,2:SETPOINT #3 ,3:SETPOINT #4 ,4:SCHEDULER ,5:COMM Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High :0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095

41015

Read Only

D1014

41016

Read Only

D1015

41017

Read Write

D1016

41018

Read Write

D1017

41019 41020

Read Only Read Only

D1018 D1019

41021

Read Only

D1020

41022 41023 41024

Read Only Read Only Read Only

D1021 D1022 D1023

- 163 -

QT108300

Holding Registers number 41025 to 41152(Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 41025 41026 41027 41028 41029 41030 41031 41032 41033 41034 41035 41036 41037 41038 41039 41040 41041 41042 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1024 D1025 D1026 D1027 D1028 D1029 D1030 D1031 D1032 D1033 D1034 D1035 D1036 D1037 D1038 D1039 D1040 D1041 Name TEMPERATURE CONTROL SET POINT #1 CUT-OUT SET POINT #1 CUT-IN SET POINT #2 PRESSURE CONTROL SET POINT #2 TEMPERATURE CONTROL SET POINT #2 CUT-OUT SET POINT #2 CUT-IN SET POINT #3 PRESSURE CONTROL SET POINT #3 TEMPERATURE CONTROL SET POINT #3 CUT-OUT SET POINT #3 CUT-IN SET POINT #4 PRESSURE CONTROL SET POINT #4 TEMPERATURE CONTROL SET POINT #4 CUT-OUT SET POINT #4 SCHEDULER>AS SIGN DAYS>SUNDAY SCHEDULER>AS SIGN DAYS>MONDAY SCHEDULER>AS SIGN DAYS>TUESDAY SCHEDULER>AS SIGN DAYS>WEDNES DAY SCHEDULER>AS SIGN DAYS>THURSD AY SCHEDULER>AS SIGN DAYS>FRIDAY SCHEDULER>AS SIGN DAYS>SATURDA Y SCHEDULER>S CHEDULER SCHEDULER>S CHEDULE #1(1/8)>SET # SCHEDULER>S CHEDULE #1(1/8)>START> HOUR SCHEDULER>S CHEDULE #1(1/8)>START> MINUTE SCHEDULER>S CHEDULE #1(2/8)>SET # SCHEDULER>S CHEDULE #1(2/8)>START> HOUR Range (Figure in ( ) is default value.) Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High :0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 #1 to #4(#1):0 to 3 #1 to #4(#1):0 to 3 #1 to #4(#1):0 to 3 #1 to #4(#1):0 to 3 Category Sub Category Note

41043

Read Only

D1042

#1 to #4(#1):0 to 3

41044 41045

Read Only Read Only

D1043 D1044

#1 to #4(#1):0 to 3 #1 to #4(#1):0 to 3

41046 41047 41048

Read Only Read Only Read Only

D1045 D1046 D1047

(0):DISABLE,1:ENABLE #1 to #4(#1):0 to 3 0 to 23 Hour:(0)

41049

Read Only

D1048

(0) to 59 Min

41050 41051

Read Only Read Only

D1049 D1050

#1 to #4(#1):0 to 3 0 to 23 Hour:(3)

- 164 -

QT108300

(continued)
Register Number 41052 Attribute Read Only Internal Word Device D1051 Name SCHEDULER>S CHEDULE #1(2/8)>START> MINUTE SCHEDULER>S CHEDULE #1(3/8)>SET # SCHEDULER>S CHEDULE #1(3/8)>START> HOUR SCHEDULER>S CHEDULE #1(3/8)>START> MINUTE SCHEDULER>S CHEDULE #1(4/8)>SET # SCHEDULER>S CHEDULE #1(4/8)>START> HOUR SCHEDULER>S CHEDULE #1(4/8)>START> MINUTE SCHEDULER>S CHEDULE #1(5/8)>SET # SCHEDULER>S CHEDULE #1(5/8)>START> HOUR SCHEDULER>S CHEDULE #1(5/8)>START> MINUTE SCHEDULER>S CHEDULE #1(6/8)>SET # SCHEDULER>S CHEDULE #1(6/8)>START> HOUR SCHEDULER>S CHEDULE #1(6/8)>START> MINUTE SCHEDULER>S CHEDULE #1(7/8)>SET # SCHEDULER>S CHEDULE #1(7/8)>START> HOUR SCHEDULER>S CHEDULE #1(7/8)>START> MINUTE SCHEDULER>S CHEDULE #1(8/8)>SET # SCHEDULER>S CHEDULE #1(8/8)>START> HOUR SCHEDULER>S CHEDULE #1(8/8)>START> MINUTE SCHEDULER>S CHEDULE #2(1/8)>SET # SCHEDULER>S CHEDULE #2(1/8)>START> HOUR SCHEDULER>S CHEDULE #2(1/8)>START> MINUTE SCHEDULER>S CHEDULE #2(2/8)>SET # Range (Figure in ( ) is default value.) (0) to 59 Min Category Sub Category Note

41053 41054

Read Only Read Only

D1052 D1053

#1 to #4(#1):0 to 3 0 to 23 Hour:(6)

41055

Read Only

D1054

(0) to 59 Min

41056 41057

Read Only Read Only

D1055 D1056

#1 to #4(#1):0 to 3 0 to 23 Hour:(9)

41058

Read Only

D1057

(0) to 59 Min

41059 41060

Read Only Read Only

D1058 D1059

#1 to #4(#1):0 to 3 0 to 23 Hour:(12)

41061

Read Only

D1060

(0) to 59 Min

41062 41063

Read Only Read Only

D1061 D1062

#1 to #4(#1):0 to 3 0 to 23 Hour:(15)

41064

Read Only

D1063

(0) to 59 Min

41065 41066

Read Only Read Only

D1064 D1065

#1 to #4(#1):0 to 3 0 to 23 Hour: (18)

41067

Read Only

D1066

(0) to 59 Min

41068 41069

Read Only Read Only

D1067 D1068

#1 to #4(#1):0 to 3 0 to 23 Hour: (21)

41070

Read Only

D1069

(0) to 59 Min

41071 41072

Read Only Read Only

D1070 D1071

#1 to #4(#1):0 to 3 0 to 23 Hour:(0)

41073

Read Only

D1072

(0) to 59 Min

41074

Read Only

D1073

#1 to #4(#1):0 to 3

- 165 -

QT108300

(continued)
Register Number 41075 Attribute Read Only Internal Word Device D1074 Name SCHEDULER>S CHEDULE #2(2/8)>START> HOUR SCHEDULER>S CHEDULE #2(2/8)>START> MINUTE SCHEDULER>S CHEDULE #2(3/8)>SET # SCHEDULER>S CHEDULE #2(3/8)>START> HOUR SCHEDULER>S CHEDULE #2(3/8)>START> MINUTE SCHEDULER>S CHEDULE #2(4/8)>SET # SCHEDULER>S CHEDULE #2(4/8)>START> HOUR SCHEDULER>S CHEDULE #2(4/8)>START> MINUTE SCHEDULER>S CHEDULE #2(5/8)>SET # SCHEDULER>S CHEDULE #2(5/8)>START> HOUR SCHEDULER>S CHEDULE #2(5/8)>START> MINUTE SCHEDULER>S CHEDULE #2(6/8)>SET # SCHEDULER>S CHEDULE #2(6/8)>START> HOUR SCHEDULER>S CHEDULE #2(6/8)>START> MINUTE SCHEDULER>S CHEDULE #2(7/8)>SET # SCHEDULER>S CHEDULE #2(7/8)>START> HOUR SCHEDULER>S CHEDULE #2(7/8)>START> MINUTE SCHEDULER>S CHEDULE #2(8/8)>SET # SCHEDULER>S CHEDULE #2(8/8)>START> HOUR SCHEDULER>S CHEDULE #2(8/8)>START> MINUTE SCHEDULER>S CHEDULE #3(1/8)>SET # SCHEDULER>S CHEDULE #3(1/8)>START> HOUR SCHEDULER>S CHEDULE #3(1/8)>START> MINUTE Range (Figure in ( ) is default value.) 0 to 23 Hour:(3) Category Sub Category Note

41076

Read Only

D1075

(0) to 59 Min

41077 41078

Read Only Read Only

D1076 D1077

#1 to #4(#1):0 to 3 0 to 23 Hour:(6)

41079

Read Only

D1078

(0) to 59 Min

41080 41081

Read Only Read Only

D1079 D1080

#1 to #4(#1):0 to 3 0 to 23 Hour:(9)

41082

Read Only

D1081

(0) to 59 Min

41083 41084

Read Only Read Only

D1082 D1083

#1 to #4(#1):0 to 3 0 to 23 Hour:(12)

41085

Read Only

D1084

(0) to 59Min

41086 41087

Read Only Read Only

D1085 D1086

#1 to #4(#1):0 to 3 0 to 23 Hour:(15)

41088

Read Only

D1087

(0) to 59Min

41089 41090

Read Only Read Only

D1088 D1089

#1 to #4(#1):0 to 3 0 to 23 Hour:(18)

41091

Read Only

D1090

(0) to 59 Min

41092 41093

Read Only Read Only

D1091 D1092

#1 to #4(#1):0 to 3 0 to 23 Hour:(21)

41094

Read Only

D1093

(0) to 59 Min

41095 41096

Read Only Read Only

D1094 D1095

#1 to #4(#1):0 to 3 0 to 23 Hour:(0)

41097

Read Only

D1096

(0) to 59 Min

- 166 -

QT108300

(continued)
Register Number 41098 41099 Attribute Read Only Read Only Internal Word Device D1097 D1098 Name SCHEDULER>S CHEDULE #3(2/8)>SET # SCHEDULER>S CHEDULE #3(2/8)>START> HOUR SCHEDULER>S CHEDULE #3(2/8)>START> MINUTE SCHEDULER>S CHEDULE #3(3/8)>SET # SCHEDULER>S CHEDULE #3(3/8)>START> HOUR SCHEDULER>S CHEDULE #3(3/8)>START> MINUTE SCHEDULER>S CHEDULE #3(4/8)>SET # SCHEDULER>S CHEDULE #3(4/8)>START> HOUR SCHEDULER>S CHEDULE #3(4/8)>START> MINUTE SCHEDULER>S CHEDULE #3(5/8)>SET # SCHEDULER>S CHEDULE #3(5/8)>START> HOUR SCHEDULER>S CHEDULE #3(5/8)>START> MINUTE SCHEDULER>S CHEDULE #3(6/8)>SET # SCHEDULER>S CHEDULE #3(6/8)>START> HOUR SCHEDULER>S CHEDULE #3(6/8)>START> MINUTE SCHEDULER>S CHEDULE #3(7/8)>SET # SCHEDULER>S CHEDULE #3(7/8)>START> HOUR SCHEDULER>S CHEDULE #3(7/8)>START> MINUTE SCHEDULER>S CHEDULE #3(8/8)>SET # SCHEDULER>S CHEDULE #3(8/8)>START> HOUR SCHEDULER>S CHEDULE #3(8/8)>START> MINUTE SCHEDULER>S CHEDULE #4(1/8)>SET # SCHEDULER>S CHEDULE #4(1/8)>START> HOUR Range (Figure in ( ) is default value.) #1 to #4(#1):0 to 3 0 to 23 Hour:(3) Category Sub Category Note

41100

Read Only

D1099

(0) to 59Min

41101 41102

Read Only Read Only

D1100 D1101

#1 to #4(#1):0 to 3 0 to 23 Hour:(6)

41103

Read Only

D1102

(0) to 59 Min

41104 41105

Read Only Read Only

D1103 D1104

#1 to #4(#1):0 to 3 0 to 23 Hour:(9)

41106

Read Only

D1105

(0) to 59 Min

41107 41108

Read Only Read Only

D1106 D1107

#1 to #4(#1):0 to 3 0 to 23 Hour:(12)

41109

Read Only

D1108

(0) to 59 Min

41110 41111

Read Only Read Only

D1109 D1110

#1 to #4(#1):0 to 3 0 to 23 Hour:(15)

41112

Read Only

D1111

(0) to 59 Min

41113 41114

Read Only Read Only

D1112 D1113

#1 to #4(#1):0 to 3 0 to 23 Hour:(18)

41115

Read Only

D1114

(0) to 59 Min

41116 41117

Read Only Read Only

D1115 D1116

#1 to #4(#1):0 to 3 0 to 23 Hour:(21)

41118

Read Only

D1117

(0) to 59 Min

41119 41120

Read Only Read Only

D1118 D1119

#1 to #4(#1):0 to 3 0 to 23 Hour:(0)

- 167 -

QT108300

(continued)
Register Number 41121 Attribute Read Only Internal Word Device D1120 Name SCHEDULER>S CHEDULE #4(1/8)>START> MINUTE SCHEDULER>S CHEDULE #4(2/8)>SET # SCHEDULER>S CHEDULE #4(2/8)>START> HOUR SCHEDULER>S CHEDULE #4(2/8)>START> MINUTE SCHEDULER>S CHEDULE #4(3/8)>SET # SCHEDULER>S CHEDULE #4(3/8)>START> HOUR SCHEDULER>S CHEDULE #4(3/8)>START> MINUTE SCHEDULER>S CHEDULE #4(4/8)>SET # SCHEDULER>S CHEDULE #4(4/8)>START> HOUR SCHEDULER>S CHEDULE #4(4/8)>START> MINUTE SCHEDULER>S CHEDULE #4(5/8)>SET # SCHEDULER>S CHEDULE #4(5/8)>START> HOUR SCHEDULER>S CHEDULE #4(5/8)>START> MINUTE SCHEDULER>S CHEDULE #4(6/8)>SET # SCHEDULER>S CHEDULE #4(6/8)>START> HOUR SCHEDULER>S CHEDULE #4(6/8)>START> MINUTE SCHEDULER>S CHEDULE #4(7/8)>SET # SCHEDULER>S CHEDULE #4(7/8)>START> HOUR SCHEDULER>S CHEDULE #4(7/8)>START> MINUTE SCHEDULER>S CHEDULE #4(8/8)>SET # SCHEDULER>S CHEDULE #4(8/8)>START> HOUR SCHEDULER>S CHEDULE #4(8/8)>START> MINUTE SCHEDULER>S CHEDULE #1(1/8)>SET # Range (Figure in ( ) is default value.) (0) to 59 Min Category Sub Category Note

41122 41123

Read Only Read Only

D1121 D1122

#1 to #4(#1):0 to 3 0 to 23 Hour:(3)

41124

Read Only

D1123

(0) to 59 Min

41125 41126

Read Only Read Only

D1124 D1125

#1 to #4(#1):0 to 3 0 to 23 Hour:(6)

41127

Read Only

D1126

(0) to 59 Min

41128 41129

Read Only Read Only

D1127 D1128

#1 to #4(#1):0 to 3 0 to 23 Hour:(9)

41130

Read Only

D1129

(0) to 59 Min

41131 41132

Read Only Read Only

D1130 D1131

#1 to #4(#1):0 to 3 0 to 23 Hour:(12)

41133

Read Only

D1132

(0) to 59 Min

41134 41135

Read Only Read Only

D1133 D1134

#1 to #4(#1):0 to 3 0 to 23 Hour:(15)

41136

Read Only

D1135

(0) to 59 Min

41137 41138

Read Only Read Only

D1136 D1137

#1 to #4(#1):0 to 3 0 to 23 Hour:(18)

41139

Read Only

D1138

(0) to 59 Min

41140 41141

Read Only Read Only

D1139 D1140

#1 to #4(#1):0 to 3 0 to 23 Hour:(21)

41142

Read Only

D1141

(0) to 59 Min

41143

Read Only

D1142

#1 to #4(#1):0 to 3

- 168 -

QT108300

(continued)
Register Number 41144 Attribute Read Only Internal Word Device D1143 Name SCHEDULER>S CHEDULE #5(1/8)>START> HOUR SCHEDULER>S CHEDULE #5(1/8)>START> MINUTE SCHEDULER>S CHEDULE #5(2/8)>SET # SCHEDULER>S CHEDULE #5(2/8)>START> HOUR SCHEDULER>S CHEDULE #5(2/8)>START> MINUTE SCHEDULER>S CHEDULE #5(3/8)>SET # SCHEDULER>S CHEDULE #5(3/8)>START> HOUR SCHEDULER>S CHEDULE #5(3/8)>START> MINUTE SCHEDULER>S CHEDULE #5(4/8)>SET # Range (Figure in ( ) is default value.) 0 to 23 Hour:(0) Category Sub Category Note

41145

Read Only

D1144

(0) to 59 Min

41146 41147

Read Only Read Only

D1145 D1146

#1 to #4(#1):0 to 3 0 to 23 Hour:(3)

41148

Read Only

D1147

(0) to 59 Min

41149 41150

Read Only Read Only

D1148 D1149

#1 to #4(#1):0 to 3 0 to 23 Hour:(6)

41151

Read Only

D1150

(0) to 59 Min

41152

Read Only

D1151

#1 to #4(#1):0 to 3

- 169 -

QT108300

Holding Registers number 41453 to 41280(Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 41153 Attribute Read Only Internal Word Device D1152 Name SCHEDULER>S CHEDULE #5(4/8)>START> HOUR SCHEDULER>S CHEDULE #5(4/8)>START> MINUTE SCHEDULER>S CHEDULE #5(5/8)>SET # SCHEDULER>S CHEDULE #5(5/8)>START> HOUR SCHEDULER>S CHEDULE #5(5/8)>START> MINUTE SCHEDULER>S CHEDULE #5(6/8)>SET # SCHEDULER>S CHEDULE #5(6/8)>START> HOUR SCHEDULER>S CHEDULE #5(6/8)>START> MINUTE SCHEDULER>S CHEDULE #5(7/8)>SET # SCHEDULER>S CHEDULE #5(7/8)>START> HOUR SCHEDULER>S CHEDULE #5(7/8)>START> MINUTE SCHEDULER>S CHEDULE #5(8/8)>SET # SCHEDULER>S CHEDULE #5(8/8)>START> HOUR SCHEDULER>S CHEDULE #5(8/8)>START> MINUTE SCHEDULER>S CHEDULE #6(1/8)>SET # SCHEDULER>S CHEDULE #6(1/8)>START> HOUR SCHEDULER>S CHEDULE #6(1/8)>START> MINUTE SCHEDULER>S CHEDULE #6(2/8)>SET # SCHEDULER>S CHEDULE #6(2/8)>START> HOUR SCHEDULER>S CHEDULE #6(2/8)>START> MINUTE SCHEDULER>S CHEDULE #6(3/8)>SET # SCHEDULER>S CHEDULE #6(3/8)>START> HOUR Range (Figure in ( ) is default value.) 0 to 23 Hour:(9) Category Sub Category Note

41154

Read Only

D1153

(0) to 59 Min

41155 41156

Read Only Read Only

D1154 D1155

#1 to #4(#1):0 to 3 0 to 23 Hour:(12)

41157

Read Only

D1156

(0) to 59 Min

41158 41159

Read Only Read Only

D1157 D1158

#1 to #4(#1):0 to 3 0 to 23 Hour:(15)

41160

Read Only

D1159

(0) to 59 Min

41161 41162

Read Only Read Only

D1160 D1161

#1 to #4(#1):0 to 3 0 to 23 Hour:(18)

41163

Read Only

D1162

(0) to 59 Min

41164 41165

Read Only Read Only

D1163 D1164

#1 to #4(#1):0 to 3 0 to 23 Hour:(21)

41166

Read Only

D1165

(0) to 59 Min

41167 41168

Read Only Read Only

D1166 D1167

#1 to #4(#1):0 to 3 0 to 23 Hour:(0)

41169

Read Only

D1168

(0) to 59 Min

41170 41171

Read Only Read Only

D1169 D1170

#1 to #4(#1):0 to 3 0 to 23 Hour:(3)

41172

Read Only

D1171

(0) to 59 Min

41173 41174

Read Only Read Only

D1172 D1173

#1 to #4(#1):0 to 3 0 to 23 Hour:(6)

- 170 -

QT108300

(continued)
Register Number 41175 Attribute Read Only Internal Word Device D1174 Name SCHEDULER>S CHEDULE #6(3/8)>START> MINUTE SCHEDULER>S CHEDULE #6(4/8)>SET # SCHEDULER>S CHEDULE #6(4/8)>START> HOUR SCHEDULER>S CHEDULE #6(4/8)>START> MINUTE SCHEDULER>S CHEDULE #6(5/8)>SET # SCHEDULER>S CHEDULE #6(5/8)>START> HOUR SCHEDULER>S CHEDULE #6(5/8)>START> MINUTE SCHEDULER>S CHEDULE #6(6/8)>SET # SCHEDULER>S CHEDULE #6(6/8)>START> HOUR SCHEDULER>S CHEDULE #6(6/8)>START> MINUTE SCHEDULER>S CHEDULE #6(7/8)>SET # SCHEDULER>S CHEDULE #6(7/8)>START> HOUR SCHEDULER>S CHEDULE #6(7/8)>START> MINUTE SCHEDULER>S CHEDULE #6(8/8)>SET # SCHEDULER>S CHEDULE #6(8/8)>START> HOUR SCHEDULER>S CHEDULE #6(8/8)>START> MINUTE SCHEDULER>S CHEDULE #7(1/8)>SET # SCHEDULER>S CHEDULE #7(1/8)>START> HOUR SCHEDULER>S CHEDULE #7(1/8)>START> MINUTE SCHEDULER>S CHEDULE #7(2/8)>SET # SCHEDULER>S CHEDULE #7(2/8)>START> HOUR SCHEDULER>S CHEDULE #7(2/8)>START> MINUTE SCHEDULER>S CHEDULE #7(3/8)>SET # Range (Figure in ( ) is default value.) (0) to 59 Min Category Sub Category Note

41176 41177

Read Only Read Only

D1175 D1176

#1 to #4(#1):0 to 3 0 to 23 Hour:(9)

41178

Read Only

D1177

(0) to 59 Min

41179 41180

Read Only Read Only

D1178 D1179

#1 to #4(#1):0 to 3 0 to 23 Hour:(12)

41181

Read Only

D1180

(0) to 59 Min

41182 41183

Read Only Read Only

D1181 D1182

#1 to #4(#1):0 to 3 0 to 23 Hour:(15)

41184

Read Only

D1183

(0) to 59 Min

41185 41186

Read Only Read Only

D1184 D1185

#1 to #4(#1):0 to 3 0 to 23 Hour:(18)

41187

Read Only

D1186

(0) to 59 Min

41188 41189

Read Only Read Only

D1187 D1188

#1 to #4(#1):0 to 3 0 to 23 Hour:(21)

41190

Read Only

D1189

(0) to 59 Min

41191 41192

Read Only Read Only

D1190 D1191

#1 to #4(#1):0 to 3 0 to 23 Hour:(0)

41193

Read Only

D1192

(0) to 59 Min

41194 41195

Read Only Read Only

D1193 D1194

#1 to #4(#1):0 to 3 0 to 23 Hour:(3)

41196

Read Only

D1195

(0) to 59 Min

41197

Read Only

D1196

#1 to #4(#1):0 to 3

- 171 -

QT108300

(continued)
Register Number 41198 Attribute Read Only Internal Word Device D1197 Name SCHEDULER>S CHEDULE #7(3/8)>START> HOUR SCHEDULER>S CHEDULE #7(3/8)>START> MINUTE SCHEDULER>S CHEDULE #7(4/8)>SET # SCHEDULER>S CHEDULE #7(4/8)>START> HOUR SCHEDULER>S CHEDULE #7(4/8)>START> MINUTE SCHEDULER>S CHEDULE #7(5/8)>SET # SCHEDULER>S CHEDULE #7(5/8)>START> HOUR SCHEDULER>S CHEDULE #7(5/8)>START> MINUTE SCHEDULER>S CHEDULE #7(6/8)>SET # SCHEDULER>S CHEDULE #7(6/8)>START> HOUR SCHEDULER>S CHEDULE #7(6/8)>START> MINUTE SCHEDULER>S CHEDULE #7(7/8)>SET # SCHEDULER>S CHEDULE #7(7/8)>START> HOUR SCHEDULER>S CHEDULE #7(7/8)>START> MINUTE SCHEDULER>S CHEDULE #7(8/8)>SET # SCHEDULER>S CHEDULE #7(8/8)>START> HOUR SCHEDULER>S CHEDULE #7(8/8)>START> MINUTE OTHER SETPOINTS>AN TI CYCLE>ANTI-CY CLE TIME OTHER SETPOINTS>AN TI CYCLE>INTERV AL TIME OTHER SETPOINTS>EC ONOMIZER INTER COOLER SV>SV ON LSV% OTHER SETPOINTS>EC ONOMIZER INTER COOLER SV>SV OFF LSV% Range (Figure in ( ) is default value.) 0 to 23 Hour:(6) Category Sub Category Note

41199

Read Only

D1198

(0) to 59 Min

41200 41201

Read Only Read Only

D1199 D1200

#1 to #4(#1):0 to 3 0 to 23 Hour:(9)

41202

Read Only

D1201

(0) to 59 Min

41203 41204

Read Only Read Only

D1202 D1203

#1 to #4(#1):0 to 3 0 to 23 Hour:(12)

41205

Read Only

D1204

(0) to 59 Min

41206 41207

Read Only Read Only

D1205 D1206

#1 to #4(#1):0 to 3 0 to 23 Hour:(15)

41208

Read Only

D1207

(0) to 59 Min

41209 41210

Read Only Read Only

D1208 D1209

#1 to #4(#1):0 to 3 0 to 23 Hour:(18)

41211

Read Only

D1210

(0) to 59 Min

41212 41213

Read Only Read Only

D1211 D1212

#1 to #4(#1):0 to 3 0 to 23 Hour:(21)

41214

Read Only

D1213

(0) to 59 Min

41215

Read Only

D1214

0 to 54(5)Min X 600

41216

Read Only

D1215

0 to 54(15)Min X 600

41217

Read Only

D1216

0.0 to 100.0(50.0)%:0 to 4095

41218

Read Only

D1217

0.0 to 100.0(40.0)%:0 to 4095

- 172 -

QT108300

(continued)
Register Number 41219 Attribute Read Only Internal Word Device D1218 Name OTHER SETPOINTS>EC ONOMIZER INTER COOLER SV>SV ON SP OTHER SETPOINTS>EC ONOMIZER INTER COOLER SV>SV OFF SP OTHER SETPOINTS>SE AL PROTECTION>I NTERVAL OTHER SETPOINTS>SE AL PROTECTION>A UTO ONLY/ALL OTHER SETPOINTS>OIL SEAL CONTROL>STA RT PERIOD OTHER SETPOINTS>OIL SEAL CONTROL>OIL PUMP RUN OTHER SETPOINTS>OIL SEAL CONTROL>COM P. STOP OTHER SETPOINTS>OIL SEAL CONTROL>OIL PUMP DELAY OIL RETURN SV>SV ON DELAY OTHER SETPOINTS>OIL HEATER>HEATE R ON OS OTHER SETPOINTS>OIL HEATER>HEATE R OFF OS OTHER SETPOINTS>ST ARTING BYPASS SV>SV OFF DELAY OTHER SETPOINTS>HO T GAS BYPASS SV>SV ON LSV% OTHER SETPOINTS>HO T GAS BYPASS SV>SV OFF LSV% OTHER SETPOINTS>HO T GAS BYPASS SV>SV ON DELAY OTHER SETPOINTS>HO T GAS BYPASS SV>SV ON SP OTHER SETPOINTS>HO T GAS BYPASS SV>SV ON DELAY AUTO-Vi CONTROL>SETP OINTS>INITIAL Vi Range (Figure in ( ) is default value.) Range Low to High: 0 to 4095 Category Sub Category Note

41220

Read Only

D1219

Range Low to High: 0 to 4095

41221

Read Only

D1220

(0)DISABLE,1ENABLE

41222

Read Only

D1221

0:ALL,(1):AUTO ONLY

41223

Read Only

D1222

0 to 999(100) X 1

41224

Read Only

D1223

0 to 54(1)Min X 600

41225

Read Only

D1224

(0)DISABLE,1ENABLE

41226

Read Only

D1225

0 to 600(10)Sec X 10

41227 41228

Read Only Read Only

D1226 D1227

0 to 600(10)Sec X 10 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 0 to 600(10)Sec X 10

41229

Read Only

D1228

41230

Read Only

D1229

41231

Read Only

D1230

0.0 to 100.0(50.0)%:0 to 4095 0.0 to 100.0(50.0)%:0 to 4095

41232

Read Only

D1231

41233

Read Only

D1232

0 to 600(10)Sec X 10

41234

Read Only

D1233

Range Low to High: 0 to 4095 0 to 600(10)Sec X 10

41235

Read Only

D1234

41236

Read Only

D1235

(0):2.63,1:3.65,2:5.80

- 173 -

QT108300

(continued)
Register Number 41237 Attribute Read Only Internal Word Device D1236 Name AUTO-Vi CONTROL>SETP OINTS>SAMPLE DELAY AUTO-Vi CONTROL>SETP OINTS>SAMPLE QUANTITY Reserved AUTO-Vi CONTROL>SETP OINTS>MOVE DELAY Reserved Reserved AUTO STAGER>ADDR ESS AUTO STAGER>CONT ROL AUTO STAGER>LISTIN G AUTO STAGER>LEAD LIST #1 AUTO STAGER>LEAD LIST #2 AUTO STAGER>LEAD LIST #3 AUTO STAGER>LEAD LIST #4 AUTO STAGER>LEAD LIST #5 AUTO STAGER>LEAD LIST #6 AUTO STAGER>LEAD LIST #7 AUTO STAGER>LEAD LIST #8 AUTO STAGER>CUT-IN SETPOINT AUTO STAGER>CUT-IN DELAY AUTO STAGER>CONT ROL SETPOINT AUTO STAGER>CUT-O UT SETPOINT AUTO STAGER>CUT-O UT DELAY AUTO STAGER>SV START NEXT AUTO STAGER>SV HOLD PREVIOUS AUTO STAGER>SV STOP TRIM CAPACITY CONTROL>MONI TOR>OPERATIO N CAPACITY CONTROL>SETP OINTS>CONTRO L START DELAY Range (Figure in ( ) is default value.) 1 to 3240(30)Sec X 10 Category Sub Category Note

41238

Read Only

D1237

1 to 99(5)

41239 41240

Read Only Read Only

D1238 D1239

-32768 to 32767 30 to 3240(30)Sec X 10

41241 41242 41243 41244 41245 41246 41247 41248 41249 41250 41251 41252 41253 41254 41255 41256 41257 41258 41259 41260

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D1240 D1241 D1242 D1243 D1244 D1245 D1246 D1247 D1248 D1249 D1250 D1251 D1252 D1253 D1254 D1255 D1256 D1257 D1258 D1259

-32768 to 32767 -32768 to 32767 (0) to 99 (0):DISABLE,1:ENABLE (0):MANUAL,1:AUTO (VFD LAG),2:AUTO (VFD LEAD) (0) to 99 (0) to 99 (0) to 99 (0) to 99 (0) to 99 (0) to 99 (0) to 99 (0) to 99 Range Low to High: 0 to 4095 0 to 600(10)Sec X 10 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 0 to 600(10)Sec X 10 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 (0):MANUAL ,1:AUTO ,2:REMOTE DIGITAL ,3:REMOTE ANALOG ,4:COMM 0 to 600(10)Sec X 10

41261 41262

Read Only Read Write

D1260 D1261

41263

Read Only

D1262

- 174 -

QT108300

(continued)
Register Number 41264 Attribute Read Only Internal Word Device D1263 Name CAPACITY CONTROL>SETP OINTS>FORCE FULL LOAD CAPACITY CONTROL(VFD) >SETPOINTS>F ORCE FULL LOAD #2 CAPACITY CONTROL>SETP OINTS>RAMP CONTROL>REM OTE MVH CAPACITY CONTROL(VFD) >SETPOINTS>V FD START DELAY CAPACITY CONTROL(VFD) >SETPOINTS>V FD STOP DELAY EXPANSION VALVE (SH) CONTROL>2ND LIQUID SUPPLY OFF MV% EXPANSION VALVE (SH) CONTROL>2ND LIQUID SUPPLY ON MV% EXPANSION VALVE (SH) CONTROL>3RD LIQUID SUPPLY OFF MV% EXPANSION VALVE (SH) CONTROL>3RD LIQUID SUPPLY ON MV% LIQUID INJECTION OIL COOLING CONTROL>2ND YOSAKU START MV% LIQUID INJECTION OIL COOLING CONTROL>2ND YOSAKU STOP MV% LIQUID INJECTION OIL COOLING CONTROL>CON TROL START OT LIQUID INJECTION OIL COOLING CONTROL>CON TROL STOP OT CHILLER LEAVING TEMPERATURE CONTROL>100% CAPACITY ON MV% CHILLER LEAVING TEMPERATURE CONTROL>100% CAPACITY OFF MV% CONDENSER CONTROL (SINGLE SET)>START CONDENSER CONTROL (SINGLE SET)>STOP Range (Figure in ( ) is default value.) 0.0 to 100.0(2.0)%/SEC:0 to 4095 0.0 to 100.0(2.0)%/SEC:0 to 4095 0.0 to 100.0(100.0)%:0 to 4095 Category Sub Category Note

41265

Read Only

D1264

41266

Read Only

D1265

41267

Read Only

D1266

0 to 600(10)Sec X 10

41268

Read Only

D1267

0 to 600(10)Sec X 10

41269

Read Only

D1268

0.0 to 100.0(40.0)%:0 to 4095

41270

Read Only

D1269

0.0 to 100.0(50.0)%:0 to 4095

41271

Read Only

D1270

0.0 to 100.0(80.0)%:0 to 4095

41272

Read Only

D1271

0.0 to 100.0(90.0)%:0 to 4095

41273

Read Only

D1272

0.0 to 100.0(50.0)%:0 to 4095

41274

Read Only

D1273

0.0 to 100.0(40.0)%:0 to 4095

41275

Read Only

D1274

Range Low to High:0 to 4095

41276

Read Only

D1275

Range Low to High:0 to 4095

41277

Read Only

D1276

Range Low to High:0 to 4095

41278

Read Only

D1277

Range Low to High:0 to 4095

41279

Read Only

D1278

Range Low to High:0 to 4095 Range Low to High:0 to 4095

41280

Read Only

D1279

- 175 -

QT108300

Holding Registers number 41281 to 41408(Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 41281 Attribute Read Only Internal Word Device D1280 Name CONDENSER CONTROL (SINGLE SET)>CYCLE TIME CONDENSER CONTROL (MULTI SET)>START #1 CONDENSER CONTROL (MULTI SET)>STOP #1 CONDENSER CONTROL (MULTI SET)>START #2 CONDENSER CONTROL (MULTI SET)>STOP #2 CONDENSER CONTROL (MULTI SET)>START #3 CONDENSER CONTROL (MULTI SET)>STOP #3 CONDENSER CONTROL (MULTI SET)>START #4 CONDENSER CONTROL (MULTI SET)>STOP #4 CONDENSER CONTROL (MULTI SET)>START #5 CONDENSER CONTROL (MULTI SET)>STOP #5 CONDENSER CONTROL (MULTI SET)>START #6 CONDENSER CONTROL (MULTI SET)>STOP #6 VFD COMPRESSOR FORCE UNLOAD %/SEC VFD COMPRESSOR CONTROL>MONI TOR>OPERATIO N HIGH STAGE CAPACITY CONTROL>MONI TOR>OPERATIO N CONDENSER CONTROL>RUN MINIMUM CONDENSER VFD CONTROL MODE AUTO STAGE>CUT IN/OUT AUTO STAGE>CONTR OL ALARM>LOW SP Range (Figure in ( ) is default value.) 0 to 600(10)Sec X 10 Category Sub Category Note

41282

Read Only

D1281

Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 Range Low to High:0 to 4095 Range Low to High: 0 to 4095 Range Low to High: 0 to 4095 0.0 to 100.0(2.0)%/SEC:0 to 4095 (0):MANUAL ,1:AUTO ,2:REMOTE DIGITAL ,3:REMOTE ANALOG ,4:COMM (0):MANUAL,1:AUTO

41283

Read Only

D1282

41284

Read Only

D1283

41285

Read Only

D1284

41286

Read Only

D1285

41287

Read Only

D1286

41288

Read Only

D1287

41289

Read Only

D1288

41290

Read Only

D1289

41291

Read Only

D1290

41292

Read Only

D1291

41293

Read Only

D1292

41294

Read Only

D1293

41295

Read Write

D1294

41296

Read Only

D1295

41297 41298 41299 41300 41301

Read Only Read Only Read Only Read Only Read Only

D1296 D1297 D1298 D1299 D1300

0 to 1 (0):#1 LAG,1:#1 LEAD (0):PRESSURE,1:TEMP ERATURE (0):PRESSURE,1:TEMP ERATURE Range Low to High:0 to 4095

- 176 -

QT108300

(continued)
Register Number 41302 41303 41304 41305 41306 41307 41308 41309 41310 41311 41312 41313 41314 41315 41316 41317 41318 41319 41320 41321 41322 41323 41324 41325 41326 41327 41328 41329 41330 41331 41332 41333 41334 41335 41336 41337 41338 41339 41340 41341 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1301 D1302 D1303 D1304 D1305 D1306 D1307 D1308 D1309 D1310 D1311 D1312 D1313 D1314 D1315 D1316 D1317 D1318 D1319 D1320 D1321 D1322 D1323 D1324 D1325 D1326 D1327 D1328 D1329 D1330 D1331 D1332 D1333 D1334 D1335 D1336 D1337 D1338 D1339 D1340 Name ALARM>LOW SP>ALARM DELAY ALARM>LOW SSH>CANCEL ALARM>HIGH DP ALARM>LOW OP ALARM>HIGH OF ALARM>HIGH OF>ALARM DELAY ALARM>HIGH MA ALARM>HIGH DT ALARM>HIGH OT ALARM>LOW SSH ALARM>RE-STA RT/TIMEOUT ALARM>HIGH IP ALARM>LOW P ALARM>LOW SH2>CANCEL ALARM>LOW ISH ALARM>LOW EB ALARM>LOW LB ALARM>LOW OS ALARM>LOW OP2 ALARM>LOW SSH2 ALARM>HIGH FF ALARM>HIGH FF>DELAY ALARM>LOW DSH ALARM>LOW DSH>DELAY ALARM>LOW DSH>MASK ALARM>HIGH SP ALARM>HIGH SP>DELAY ALARM>HIGH ST ALARM>LOW OP(PRE LUBE) FAILURE>LOW SP FAILURE>LOW SP>ALARM DELAY FAILURE>LOW SP>MASK TIME FAILURE>HIGH DP FAILURE>LOW OP FAILURE>HIGH OF FAILURE>LOW SH2>DELAY FAILURE>HIGH MA FAILURE>HIGH DT FAILURE>HIGH OT FAILURE>LOW SSH Range (Figure in ( ) is default value.) 0 to 600(10)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(10)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(10)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(600)Sec X 10 Range Low to High:0 to 4095 0 to 300(30)Sec X 10 0 to 54(30)Min X 600 Range Low to High:0 to 4095 0 to 300(30)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 1 to 300(30)Sec X 10 0 to 54(1)Min X 600 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(30)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Category Sub Category Note

- 177 -

QT108300

(continued)
Register Number 41342 41343 41344 41345 41346 41347 41348 41349 41350 41351 41352 41353 41354 41355 41356 41357 41358 41359 41360 41361 41362 41363 41364 41365 41366 41367 41368 41369 41370 41371 41372 41373 41374 41375 41376 41377 41378 41379 41380 41381 41382 41383 41384 41385 41386 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1341 D1342 D1343 D1344 D1345 D1346 D1347 D1348 D1349 D1350 D1351 D1352 D1353 D1354 D1355 D1356 D1357 D1358 D1359 D1360 D1361 D1362 D1363 D1364 D1365 D1366 D1367 D1368 D1369 D1370 D1371 D1372 D1373 D1374 D1375 D1376 D1377 D1378 D1379 D1380 D1381 D1382 D1383 D1384 D1385 Name FAILURE>LOW SSH>DELAY FAILURE>HIGH IP FAILURE>LOW P FAILURE>LOW P>MASK TIME ALARM>HIGH ST>MASK ALARM>HIGH ST>DELAY FAILURE>LOW LB Reserved Reserved FAILURE>LOW SH2 FAILURE>HIGH FF Reserved ALARM>LOW LEVEL ALARM>LOW LEVEL>DELAY ALARM>LOW LEVEL>MASK FAILURE>HIGH SP FAILURE>HIGH SP>DELAY FAILURE>HIGH ST FAILURE>LOW OP(PRE LUBE) OEM LIMITS>LOW SP OEM LIMITS>HIGH DP OEM LIMITS>LOW OP OEM LIMITS>HIGH OF OEM LIMITS>HIGH MA OEM LIMITS>HIGH DT OEM LIMITS>HIGH OT OEM LIMITS>LOW SSH OEM LIMITS>HIGH IP OEM LIMITS>LOW P OEM LIMITS>LOW ISH OEM LIMITS>LOW EB OEM LIMITS>LOW LB OEM LIMITS>LOW OS OEM LIMITS>LOW OP2 OEM LIMITS>LOW SSH2 Reserved Reserved Reserved Reserved Reserved OEM LIMITS>HIGH FF Reserved OEM LIMITS>LOW DSH Reserved Reserved Range (Figure in ( ) is default value.) 0 to 600(30)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 1 to 600(600)Sec X 10 0 to 54(10)Min X 600 1 to 300(60)Sec X 10 Range Low to High:0 to 4095 -32768 to 32767 -32768 to 32767 Range Low to High:0 to 4095 Range Low to High:0 to 4095 -32768 to 32767 Range Low to High:0 to 4095 0 to 300(30)Sec X 10 0 to 54(10)Min X 600 Range Low to High:0 to 4095 0 to 300(60)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Range Low to High:0 to 4095 -32768 to 32767 Range Low to High:0 to 4095 -32768 to 32767 -32768 to 32767 Category Sub Category Note

- 178 -

QT108300

(continued)
Register Number 41387 41388 41389 41390 41391 Attribute Read Only Read Only Read Only Read Only Read Only Internal Word Device D1386 D1387 D1388 D1389 D1390 Name OEM LIMITS>HIGH SP OEM LIMITS>LOW LEVEL OEM LIMITS>HIGH ST OEM LIMITS>LOW OP(PRE LUBE) AUXILIARY INPUT TIMER>COMP. MSRB(Starting) AUXILIARY INPUT TIMER>COMP. MSRB(Running) AUXILIARY INPUT TIMER>COMP. MSRB(Stopped) AUXILIARY INPUT TIMER>INTERLO CK-1 AUXILIARY INPUT TIMER>INTERLO CK-2 AUXILIARY INPUT TIMER>INTERLO CK-3 263,250 365,350 580,500 Range (Figure in ( ) is default value.) Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 1 to 60(60)Sec X 10 Category Sub Category Note

41392

Read Only

D1391

1 to 60(2)Sec X 10

41393

Read Only

D1392

1 to 60(60)Sec X 10

41394

Read Only

D1393

1 to 180(20)Sec X 10

41395

Read Only

D1394

1 to 180(20)Sec X 10

41396

Read Only

D1395

1 to 180(20)Sec X 10

41397 41398 41399 41400 41401

Read Only Read Only Read Only Read Only Read Write

D1396 D1397 D1398 D1399 D1400

41402

Read Only

D1401

41403

Read Only

D1402

41404

Read Only

D1403

41405

Read Only

D1404

41406

Read Only

D1405

41407

Read Only

D1406

41408

Read Only

D1407

CAPACITY CONTROL>MVL %/MVH% BY COMM VFD COMPRESOOR CONTROL>MVL %/MVH% BY COMM RANGE OVER>PRESSU RE SENSOR MASK TIME RANGE OVER>TEMPER ATURE SENSOR MASK TIME RANGE OVER>SUCTION PRESSURE OVER DELAY RANGE OVER>DISCHAR GE PRESSURE UNDER DELAY RANGE OVER>OIL SUPPLY PRESSURE OVER DELAY RANGE OVER>AFTER FILTER PRESSURE OVER DELAY RANGE OVER>SUCTION TEMPERATURE OVER DELAY

LVi X 100 MVi X 100 HVi X 100 M100%:0 to 4095 (0):DISABLE,1:ENABLE

0 to 3240(180)Sec X 10

0 to 3240(600)Sec X 10

0 to 3240(10)Sec X 10

0 to 3240(10)Sec X 10

0 to 3240(10)Sec X 10

0 to 3240(10)Sec X 10

0 to 3240(15)Sec X 10

- 179 -

QT108300

Holding Registers number 41409 to 41536(Internal Word (16Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 41409 Attribute Read Only Internal Word Device D1408 Name RANGE OVER>SUCTION TEMPERATURE UNDER DELAY RANGE OVER>DISCHAR GE TEMPERATURE UNDER DELAY RANGE OVER>OIL SUPPLY TEMPERATURE UNDER DELAY RANGE OVER>INTERME DIATE PRESSURE UNDER DELAY RANGE OVER>INTERME DIATE TEMPERATURE OVER DELAY RANGE OVER>INTERME DIATE TEMPERATURE UNDER DELAY RANGE OVER>COMPRE SSOR MOTOR CURRENT UNDER DELAY RANGE OVER>LEAVING BRINE TEMPERATURE OVER DELAY RANGE OVER>LOW STAGE SLIDE VALVE POSITION OVER DELAY RANGE OVER>LOW STAGE SLIDE VALVE POSITION UNDER DELAY RANGE OVER>HIGH STAGE SLIDE VALVE POSITION OVER DELAY RANGE OVER>HIGH STAGE SLIDE VALVE POSITION UNDER DELAY RANGE OVER>CHILLER GAS TEMPERATURE OVER DELAY RANGE OVER>CHILLER GAS TEMPERATURE UNDER DELAY RANGE OVER>SUCTOP N PRESSURE1 OVER DELAY RANGE OVER>SUCTOP N PRESSURE1 UNDER DELAY Reserved Range (Figure in ( ) is default value.) 0 to 3240(15)Sec X 10 Category Sub Category Note

41410

Read Only

D1409

0 to 3240(15)Sec X 10

41411

Read Only

D1410

0 to 3240(10)Sec X 10

41412

Read Only

D1411

0 to 3240(10)Sec X 10

41413

Read Only

D1412

0 to 3240(15)Sec X 10

41414

Read Only

D1413

0 to 3240(15)Sec X 10

41415

Read Only

D1414

0 to 3240(30)Sec X 10

41416

Read Only

D1415

0 to 3240(15)Sec X 10

41417

Read Only

D1416

0 to 3240(60)Sec X 10

41418

Read Only

D1417

0 to 3240(60)Sec X 10

41419

Read Only

D1418

0 to 3240(60)Sec X 10

41420

Read Only

D1419

0 to 3240(60)Sec X 10

41421

Read Only

D1420

0 to 3240(15)Sec X 10

41422

Read Only

D1421

0 to 3240(15)Sec X 10

41423

Read Only

D1422

0 to 3240(10)Sec X 10

41424

Read Only

D1423

0 to 3240(10)Sec X 10

41425

Read Only

D1424

-32768 to 32767

- 180 -

QT108300

(continued)
Register Number 41426 41427 41428 41429 41430 41431 41432 41433 41434 41435 41436 41437 41438 41439 41440 41441 41442 41443 41444 41445 41446 41447 41448 41449 41450 41451 41452 41453 41454 41455 41456 41457 41458 41459 41460 41461 41462 41463 41464 41465 41466 41467 41468 41469 41470 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1425 D1426 D1427 D1428 D1429 D1430 D1431 D1432 D1433 D1434 D1435 D1436 D1437 D1438 D1439 D1440 D1441 D1442 D1443 D1444 D1445 D1446 D1447 D1448 D1449 D1450 D1451 D1452 D1453 D1454 D1455 D1456 D1457 D1458 D1459 D1460 D1461 D1462 D1463 D1464 D1465 D1466 D1467 D1468 D1469 Name Reserved Reserved Reserved Reserved Reserved LAG OIL P. START OP LAG OIL P. STOP DELAY VFD OUT LIMIT ZONE1 LOW VFD OUT LIMIT ZONE1 HIGH VFD OUT LIMIT ZONE2 LOW VFD OUT LIMIT ZONE2 HIGH VFD OUT LIMIT ZONE3 LOW VFD OUT LIMIT ZONE3 HIGH VFD OUT LIMIT DEAD BAND Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved AUTO STAGE>APPRO ACH T CONDENSER CONTROL (SINGLE SET)>START CONDENSER CONTROL (SINGLE SET)>STOP CONDENSER CONTROL (SINGLE SET)>CYCLE TIME CONDENSER CONTROL (MULTI SET)>START #1 CONDENSER CONTROL (MULTI SET)>STOP #1 CONDENSER CONTROL (MULTI SET)>START #2 Range (Figure in ( ) is default value.) -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Range Low to High:0 to 4095 10 to 600(60)Sec X 10 0.0 to 100.0(0.0)%:0 to 4095 0.0 to 100.0(0.0)%:0 to 4095 0.0 to 100.0(0.0)%:0 to 4095 0.0 to 100.0(0.0)%:0 to 4095 0.0 to 100.0(0.0)%:0 to 4095 0.0 to 100.0(0.0)%:0 to 4095 0.0 to 100.0(0.5)%:0 to 4095 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(10)Sec X 10 Category Sub Category Note

41471

Read Only

D1470

41472

Read Only

D1471

41473

Read Only

D1472

41474

Read Only

D1473

Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095

41475

Read Only

D1474

41476

Read Only

D1475

- 181 -

QT108300

(continued)
Register Number 41477 Attribute Read Only Internal Word Device D1476 Name CONDENSER CONTROL (MULTI SET)>STOP #2 CONDENSER CONTROL (MULTI SET)>START #3 CONDENSER CONTROL (MULTI SET)>STOP #3 CONDENSER CONTROL (MULTI SET)>START #4 CONDENSER CONTROL (MULTI SET)>STOP #4 CONDENSER CONTROL (MULTI SET)>START #5 CONDENSER CONTROL (MULTI SET)>STOP #5 CONDENSER CONTROL (MULTI SET)>START #6 CONDENSER CONTROL (MULTI SET)>STOP #6 OPERATION MODE>ALARM/F AILURE OPTION ANALOG INPUT>OPT1>AL ARM OPTION ANALOG INPUT>OPT2>AL ARM OPTION ANALOG INPUT>OPT3>AL ARM OPTION ANALOG INPUT>OPT4>AL ARM Reserved Reserved Reserved Reserved OPTION ANALOG INPUT>OPT1>FA ILURE OPTION ANALOG INPUT>OPT2>FA ILURE OPTION ANALOG INPUT>OPT3>FA ILURE OPTION ANALOG INPUT>OPT4>FA ILURE Reserved Reserved Reserved Reserved ALARM>OPT1 ALARM ALARM>OPT2 ALARM ALARM>OPT3 ALARM Range (Figure in ( ) is default value.) Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 (0):SET POINT#1,1:SET POINT#2 (0):NOT USE,1:LOW ALARM,2:HIGH ALARM (0):NOT USE,1:LOW ALARM,2:HIGH ALARM (0):NOT USE,1:LOW ALARM,2:HIGH ALARM (0):NOT USE,1:LOW ALARM,2:HIGH ALARM -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 (0):NOT USE,1:LOW FAILURE,2:HIGH FAILURE (0):NOT USE,1:LOW FAILURE,2:HIGH FAILURE (0):NOT USE,1:LOW FAILURE,2:HIGH FAILURE (0):NOT USE,1:LOW FAILURE,2:HIGH FAILURE -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Category Sub Category Note

41478

Read Only

D1477

41479

Read Only

D1478

41480

Read Only

D1479

41481

Read Only

D1480

41482

Read Only

D1481

41483

Read Only

D1482

41484

Read Only

D1483

41485

Read Only

D1484

41486 41487

Read Write Read Only

D1485 D1486

41488

Read Only

D1487

41489

Read Only

D1488

41490

Read Only

D1489

41491 41492 41493 41494 41495

Read Only Read Only Read Only Read Only Read Only

D1490 D1491 D1492 D1493 D1494

41496

Read Only

D1495

41497

Read Only

D1496

41498

Read Only

D1497

41499 41500 41501 41502 41503 41504 41505

Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D1498 D1499 D1500 D1501 D1502 D1503 D1504

- 182 -

QT108300

(continued)
Register Number 41506 41507 41508 41509 41510 41511 41512 41513 41514 41515 41516 41517 41518 41519 41520 41521 41522 41523 41524 41525 41526 41527 41528 41529 41530 41531 41532 41533 41534 41535 41536 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1505 D1506 D1507 D1508 D1509 D1510 D1511 D1512 D1513 D1514 D1515 D1516 D1517 D1518 D1519 D1520 D1521 D1522 D1523 D1524 D1525 D1526 D1527 D1528 D1529 D1530 D1531 D1532 D1533 D1534 D1535 Name ALARM>OPT4 ALARM Reserved Reserved Reserved Reserved FAILURE>OPT1 FAILURE FAILURE>OPT2 FAILURE FAILURE>OPT3 FAILURE FAILURE>OPT4 FAILURE Reserved Reserved Reserved Reserved ALARM>OPT1 ALARM>MASK ALARM>OPT2 ALARM>MASK ALARM>OPT3 ALARM>MASK ALARM>OPT4 ALARM>MASK Reserved Reserved Reserved Reserved ALARM>OPT1 ALARM>DELAY ALARM>OPT2 ALARM>DELAY ALARM>OPT3 ALARM>DELAY ALARM>OPT4 ALARM>DELAY Reserved Reserved Reserved Reserved FAILURE>OPT1 FAILURE>DELAY FAILURE>OPT2 FAILURE>DELAY Range (Figure in ( ) is default value.) Range Low to High:0 to 4095 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 0 to 54(0)Min X 600 0 to 54(0)Min X 600 0 to 54(0)Min X 600 0 to 54(0)Min X 600 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 0 to 600(0)Sec X 10 0 to 600(0)Sec X 10 0 to 600(0)Sec X 10 0 to 600(0)Sec X 10 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 0 to 600(0)Sec X 10 0 to 600(0)Sec X 10 Category Sub Category Note

- 183 -

QT108300

Holding Registers number 41537 to 41664(Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 41537 41538 41539 41540 41541 41542 41543 41544 41545 41546 41547 41548 41549 41550 41551 41552 41553 41554 41555 41556 41557 41558 41559 41560 41561 41562 41563 41564 41565 41566 41567 41568 41569 41570 41571 41572 41573 41574 41575 41576 41577 41578 41579 41580 41581 41582 41583 41584 41585 41586 41587 41588 41589 41590 41591 41592 41593 41594 41595 41596 41597 41598 41599 41600 41601 41602 41603 41604 41605 41606 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1536 D1537 D1538 D1539 D1540 D1541 D1542 D1543 D1544 D1545 D1546 D1547 D1548 D1549 D1550 D1551 D1552 D1553 D1554 D1555 D1556 D1557 D1558 D1559 D1560 D1561 D1562 D1563 D1564 D1565 D1566 D1567 D1568 D1569 D1570 D1571 D1572 D1573 D1574 D1575 D1576 D1577 D1578 D1579 D1580 D1581 D1582 D1583 D1584 D1585 D1586 D1587 D1588 D1589 D1590 D1591 D1592 D1593 D1594 D1595 D1596 D1597 D1598 D1599 D1600 D1601 D1602 D1603 D1604 D1605 Name FAILURE>OPT3 FAILURE>DELAY FAILURE>OPT4 FAILURE>DELAY Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved ALARM>LOW SP #2 FAILURE>LOW SP #2 ALARM>LOW SP #2>DELAY FAILURE>LOW SP #2>DELAY ALARM>LOW SP #2>MASK ALARM>HIGH SP #2 Range (Figure in ( ) is default value.) 0 to 600(0)Sec X 10 0 to 600(0)Sec X 10 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Range Low to High:0 to 4095 Range Low to High:0 to 4095 1 to 300(30)Sec X 10 1 to 300(30)Sec X 10 0 to 54(1)Min X 600 Range Low to High:0 to 4095 Category Sub Category Note

- 184 -

QT108300

(continued)
Register Number 41607 41608 41609 41610 41611 41612 41613 41614 41615 41616 41617 41618 41619 41620 41621 41622 41623 41624 41625 41626 41627 41628 41629 41630 41631 41632 41633 41634 41635 41636 41637 41638 41639 41640 41641 41642 41643 41644 41645 41646 41647 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1606 D1607 D1608 D1609 D1610 D1611 D1612 D1613 D1614 D1615 D1616 D1617 D1618 D1619 D1620 D1621 D1622 D1623 D1624 D1625 D1626 D1627 D1628 D1629 D1630 D1631 D1632 D1633 D1634 D1635 D1636 D1637 D1638 D1639 D1640 D1641 D1642 D1643 D1644 D1645 D1646 Name FAILURE>HIGH SP #2 ALARM>HIGH SP #2>DELAY FAILURE>HIGH SP #2>DELAY ALARM>HIGH DP #2 FAILURE>HIGH DP #2 ALARM>LOW OP #2 FAILURE>LOW OP #2 ALARM>LOW OP #2(PRE LUBE) FAILURE>LOW OP #2(PRE LUBE) ALARM>HIGH OF #2 FAILURE>HIGH OF #2 ALARM>HIGH OF #2>DELAY ALARM>HIGH MA #2 FAILURE>HIGH MA #2 ALARM>HIGH DT #2 FAILURE HIGH DT #2 ALARM>HIGH OT #2 FAILURE>HIGH OT #2 ALARM>LOW DSH #2 ALARM>LOW DSH #2>DELAY ALARM>LOW DSH #2>MASK ALARM>LOW SSH #2 FAILURE>LOW SSH #2 ALARM>LOW SSH #2>CANCEL ALARM>LOW SSH #2>DELAY ALARM>LOW SH2 #2 FAILURE>LOW SH2 #2 FAILUER>LOW SH2 #2>CANCEL ALARM>LOW SH2 #2>DELAY ALARM>RE-STA RT/TIMEOUT #2 ALARM>LOW OP2 #2 ALARM>HIGH IP #2 FAILURE>HIGH IP #2 ALARM>LOW P #2 FAILURE>LOW P #2 ALARM>LOW P #2>MASK ALARM>LOW ISH #2 ALARM>LOW EB #2 ALARM>LOW LB #2 FAILURE>LOW LB #2 ALARM>LOW OS #2 Range (Figure in ( ) is default value.) Range Low to High:0 to 4095 0 to 300(30)Sec X 10 0 to 300(60)Sec X 10 Range 4095 Range 4095 Range 4095 Range 4095 Range 4095 Range 4095 Low to High:0 to Low to High:0 to Low to High:0 to Low to High:0 to Low to High:0 to Low to High:0 to Category Sub Category Note

Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(600)Sec X 10 Range Low to High:0 4095 Range Low to High:0 4095 Range Low to High:0 4095 Range Low to High:0 4095 Range Low to High:0 4095 Range Low to High:0 4095 Range Low to High:0 4095 0 to 300(30)Sec X 10 0 to 54(30)Min X 600 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(30)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(30)Sec X 10 0 to 300(30)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 Range Low to High:0 to 4095 1 to 600(600)Sec X 10 Range 4095 Range 4095 Range 4095 Range 4095 Range 4095 Low to High:0 to Low to High:0 to Low to High:0 to Low to High:0 to Low to High:0 to to to to to to to to

- 185 -

QT108300

(continued)
Register Number 41648 41649 41650 41651 41652 41653 41654 41655 41656 41657 41658 41659 41660 41661 41662 41663 41664 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1647 D1648 D1649 D1650 D1651 D1652 D1653 D1654 D1655 D1656 D1657 D1658 D1659 D1660 D1661 D1662 D1663 Name ALARM>HIGH FF #2 FAILURE HIGH FF #2 ALARM>HIGH FF #2>DELAY ALARM>HIGH ST #2 FAILURE>HIGH ST #2 ALARM>HIGH ST #2>DELAY ALARM>HIGH ST #2>MASK ALARM>LOW LEVEL #2 FAILURE>LOW LEVEL #2 ALARM>LOW LEVEL #2>DELAY ALARM>LOW LEVEL #2>MASK Reserved Reserved Reserved Reserved Reserved Reserved Range (Figure in ( ) is default value.) Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 600(600)Sec X 10 Range Low to High:0 to 4095 Range Low to High:0 to 4095 1 to 300(60)Sec X 10 0 to 54(10)Min X 600 Range Low to High:0 to 4095 Range Low to High:0 to 4095 0 to 300(30)Sec X 10 0 to 54(10)Min X 600 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category Sub Category Note

- 186 -

QT108300

Holding Registers number 41665 to 41792 (Internal Word (16Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 41665 41666 41667 41668 41669 41670 41671 41672 41673 41674 41675 41676 41677 41678 41679 41680 41681 41682 41683 41684 41685 41686 41687 41688 41689 41690 41691 41692 41693 41694 41695 41696 41697 41698 41699 41700 41701 41702 41703 41704 41705 41706 41707 41708 41709 41710 41711 41712 41713 41714 41715 41716 41717 41718 41719 41720 41721 41722 41723 41724 41725 41726 41727 41728 41729 41730 41731 41732 41733 41734 41735 41736 41737 41738 41739 41740 41741 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1664 D1665 D1666 D1667 D1668 D1669 D1670 D1671 D1672 D1673 D1674 D1675 D1676 D1677 D1678 D1679 D1680 D1681 D1682 D1683 D1684 D1685 D1686 D1687 D1688 D1689 D1690 D1691 D1692 D1693 D1694 D1695 D1696 D1697 D1698 D1699 D1700 D1701 D1702 D1703 D1704 D1705 D1706 D1707 D1708 D1709 D1710 D1711 D1712 D1713 D1714 D1715 D1716 D1717 D1718 D1719 D1720 D1721 D1722 D1723 D1724 D1725 D1726 D1727 D1728 D1729 D1730 D1731 D1732 D1733 D1734 D1735 D1736 D1737 D1738 D1739 D1740 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category Sub Category Note

- 187 -

QT108300

(continued)
Register Number 41742 41743 41744 41745 41746 41747 41748 41749 41750 41751 41752 41753 41754 41755 41756 41757 41758 41759 41760 41761 41762 41763 41764 41765 41766 41767 41768 41769 41770 41771 41772 41773 41774 41775 41776 41777 41778 41779 41780 41781 41782 41783 41784 41785 41786 41787 41788 41789 41790 41791 41792 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1741 D1742 D1743 D1744 D1745 D1746 D1747 D1748 D1749 D1750 D1751 D1752 D1753 D1754 D1755 D1756 D1757 D1758 D1759 D1760 D1761 D1762 D1763 D1764 D1765 D1766 D1767 D1768 D1769 D1770 D1771 D1772 D1773 D1774 D1775 D1776 D1777 D1778 D1779 D1780 D1781 D1782 D1783 D1784 D1785 D1786 D1787 D1788 D1789 D1790 D1791 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category Sub Category Note

- 188 -

QT108300

Holding Registers number 41793 to 41920 (Internal Word (16Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 41793 41794 41795 41796 41797 41798 41799 41800 41801 41802 41803 41804 41805 41806 41807 41808 41809 41810 41811 41812 41813 41814 41815 41816 41817 41818 41819 41820 41821 41822 41823 41824 41825 41826 41827 41828 41829 41830 41831 41832 41833 41834 41835 41836 41837 41838 41839 41840 41841 41842 41843 41844 41845 41846 41847 41848 41849 41850 41851 41852 41853 41854 41855 41856 41857 41858 41859 41860 41861 41862 41863 41864 41865 41866 41867 41868 41869 41870 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1792 D1793 D1794 D1795 D1796 D1797 D1798 D1799 D1800 D1801 D1802 D1803 D1804 D1805 D1806 D1807 D1808 D1809 D1810 D1811 D1812 D1813 D1814 D1815 D1816 D1817 D1818 D1819 D1820 D1821 D1822 D1823 D1824 D1825 D1826 D1827 D1828 D1829 D1830 D1831 D1832 D1833 D1834 D1835 D1836 D1837 D1838 D1839 D1840 D1841 D1842 D1843 D1844 D1845 D1846 D1847 D1848 D1849 D1850 D1851 D1852 D1853 D1854 D1855 D1856 D1857 D1858 D1859 D1860 D1861 D1862 D1863 D1864 D1865 D1866 D1867 D1868 D1869 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category Sub Category Note

- 189 -

QT108300

(continued)
Register Number 41871 41872 41873 41874 41875 41876 41877 41878 41879 41880 41881 41882 41883 41884 41885 41886 41887 41888 41889 41890 41891 41892 41893 41894 41895 41896 41897 41898 41899 41900 41901 41902 41903 41904 41905 41906 41907 41908 41909 41910 41911 41912 41913 41914 41915 41916 41917 41918 41919 41920 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1870 D1871 D1872 D1873 D1874 D1875 D1876 D1877 D1878 D1879 D1880 D1881 D1882 D1883 D1884 D1885 D1886 D1887 D1888 D1889 D1890 D1891 D1892 D1893 D1894 D1895 D1896 D1897 D1898 D1899 D1900 D1901 D1902 D1903 D1904 D1905 D1906 D1907 D1908 D1909 D1910 D1911 D1912 D1913 D1914 D1915 D1916 D1917 D1918 D1919 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Vi Ratio LM(n=2) Vi Ratio MH(n=2) Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Industrial Unit X 10^n Industrial Unit X 10^n -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category Sub Category Note

- 190 -

QT108300

Holding Registers number 41921 to 42048(Internal Word (16Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 41921 41922 41923 41924 41925 41926 41927 41928 41929 41930 41931 41932 41933 41934 41935 41936 41937 41938 41939 41940 41941 41942 41943 41944 41945 41946 41947 41948 41949 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1920 D1921 D1922 D1923 D1924 D1925 D1926 D1927 D1928 D1929 D1930 D1931 D1932 D1933 D1934 D1935 D1936 D1937 D1938 D1939 D1940 D1941 D1942 D1943 D1944 D1945 D1946 D1947 D1948 Name Reserved Reserved Reserved Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 Category Sub Category Note

- 191 -

QT108300

(continued)
Register Number 41950 41951 41952 41953 41954 41955 41956 41957 41958 41959 41960 41961 41962 41963 41964 41965 41966 41967 41968 41969 41970 41971 41972 41973 41974 41975 41976 41977 41978 41979 41980 41981 41982 41983 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Write Read Write Read Write Read Write Read Write Read Write Read Write Read Only Read Only Read Only Read Only Read Only Internal Word Device D1949 D1950 D1951 D1952 D1953 D1954 D1955 D1956 D1957 D1958 D1959 D1960 D1961 D1962 D1963 D1964 D1965 D1966 D1967 D1968 D1969 D1970 D1971 D1972 D1973 D1974 D1975 D1976 D1977 D1978 D1979 D1980 D1981 D1982 Name Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value Reserved as Buffer of Set Value WEEK Set MONTH Set DAY Set YEAR Set HOUR Set MINUTE Set SECOND Set Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Range -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 0(SUN.) to 6(SAT.) 1 to 12 1 to 31 A.D. 4 Digits(2000 to 2099) 0 to 23 0 to 59 0 to 59 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 Category Sub Category Note

PID 1/16 PID 2/16 PID 3/16 PID 4/16 PID 5/16

- 192 -

QT108300

(continued)
Register Number 41984 41985 41986 41987 41988 41989 41990 41991 41992 41993 41994 41995 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D1983 D1984 D1985 D1986 D1987 D1988 D1989 D1990 D1991 D1992 D1993 D1994 Name Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number Process Value AI channel Number PRESSURE INDICATION Range 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0 to 79 or -1 0:MPa(Absolute) ,1:MPa(Gauge) ,2:kgf/cm2(Absolute) ,3:kgf/cm2(Gauge) ,4:Bar(Absolute) ,5:Bar(Gauge) ,6:PSI(Absoluter) ,(7):PSI(Gauge) 0:KELVIN ,1:CELSIUS ,(2):FAHRENHEIT 0:R22 ,1:R23 ,2:R134a ,3:R404a ,4:R407 ,5:R410 ,6:R502 ,7:R507 ,(8):R717(NH3) ,9:R290(PROPANE) ,10:R744(CO2) ,11:USER DEFINED Always 0 (0):ENGLISH ,1:FRENCH ,2:GERMAN ,3:PORTUGUESE ,4:RUSSIAN ,5:SPANISH (0):NORTH AMERICA ,1:EUROPE ,2:ASIA 3:FACTORY Number X 65536 Numbers Second X 65536 Seconds Second X 65536 Seconds Second X 65536 Seconds Hour X 65536 Hours Hour Category Sub Category PID 6/16 PID 7/16 PID 8/16 PID 9/16 PID10/16 PID11/16 PID12/16 PID13/16 PID14/16 PID15/16 PID16/16 Note

41996 41997

Read Only Read Only

D1995 D1996

TEMPERATURE INDICATION REFRIGERANT

41998 41999

Read Only Read Only

D1997 D1998

Reserved as APPLICATION TYPE LANGUAGE

42000

Read Only

D1999

CONTROL PLATFORM COMPRESSOR START/STOP(Lo w Word) COMPRESSOR START/STOP(Hi gh Word) RUN(Low Word) RUN(High Word) STOP(Low Word) STOP(High Word) TODAY(Low Word) TODAY(High Word) RUN TIME(Low Word) RUN TIME(High Word) TOTAL RUN(Low Word)

42001 42002 42003 42004 42005 42006 42007 42008 42009 42010 42011

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D2000 D2001 D2002 D2003 D2004 D2005 D2006 D2007 D2008 D2009 D2010

STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor

START/STOP = (42001) + 65536 X (42002)

RUN = (42003) + 65536 X (42004) STOP = (42005) + 65536 X (42006) TODAY = (42007) + 65536 X (42008) RUN TIME = (42009) + 65536 X (42010) TOTAL RUN = (42011) + 65536 X (42012)

- 193 -

QT108300

(continued)
Register Number 42012 42013 Attribute Read Only Read Only Internal Word Device D2011 D2012 Name TOTAL RUN(High Word) ALARM Status Range X 65536 Hours (0):NO ALARM-NO FAILURE ,1:ALARM-NO FAILURE 2:NO ALARM-FAILURE ,3:ALARM-FAILURE 0:NO,(1):YES (0):LOCAL-OFF ,1:LOCAL-ON ,2:REMOTE-OFF ,3REMOTE-ON ,4:COMM-OFF ,5:COMM-ON ,6:AUTO STAGE-OFF ,7:AUTO STAGE-ON 0:NO,(1):YES (0):STOP ,1:ANTI CYCLE ,2:AUTO STOP ,3:CUT IN ,4:SYSTEM START 5:OIL PUMP START ,6:PRE START ,7:START ,8:RUN ,9:CUT OUT 10:PUMP OUT Seconds Industrial Unit10^n Industrial Unit10^n 1 to 7 1 to 4 Industrial Unit10^n Category STATUS Monitor STATUS Monitor Sub Category Note

42014 42015

Read Only Read Only

D2013 D2014

D/O TEST MODE COMPRESSOR OPERATION MODE

STATUS Monitor STATUS Monitor

42016 42017

Read Only Read Only

D2015 D2016

COMPRESSOR AUTO START/STOP COMPRESSOR STATUS

STATUS Monitor STATUS Monitor

42018 42019 42020 42021 42022 42023

Read Only Read Only Read Only Read Only Read Only Read Only

D2017 D2018 D2019 D2020 D2021 D2022

42024

Read Only

D2023

42025 42026

Read Only Read Only

D2024 D2025

Delay Timers to Time Up. Current CUT IN Set Point(n=3 or 1) Current CUT OUT Set Point(n=3 or 1) Current SCHEDULE # Current SET POINT # Current(Low Stage)Slide Valve Pressure Set Point Current(Low Stage)Slide Valve Temperature Set Point (Low Stage)Slide Valve Controller PID OUT(MV)% (Low Stage)Positi1r Status

STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor

Industrial Unit10^n

STATUS Monitor

0 to 1000 (0):LOAD-OFF/UNLOA D-OFF 1:LOAD-ON/UNLOADOFF ,2:LOAD-OFF/UNLOAD -ON (0):LIMIT-OFF/UNLOAD -OFF 1:LIMIT-ON/UNLOAD-O FF 2:LIMIT-OFF/UNLOADON (0):LIMIT-OFF/UNLOAD -OFF 1:LIMIT-ON/UNLOAD-O FF 2:LIMIT-OFF/UNLOADON (0):LIMIT-OFF/UNLOAD -OFF 1:LIMIT-ON/UNLOAD-O FF 2:LIMIT-OFF/UNLOADON (0):LIMIT-OFF/UNLOAD -OFF 1:LIMIT-ON/UNLOAD-O FF 2:LIMIT-OFF/UNLOADON Industrial Unit10^n

STATUS Monitor STATUS Monitor

42027

Read Only

D2026

HIGH MA Limiter Status

STATUS Monitor

42028

Read Only

D2027

HIGH DP Limiter Status

STATUS Monitor

42029

Read Only

D2028

LOW SP Limiter Status

STATUS Monitor

42030

Read Only

D2029

HIGH IP Limiter Status

STATUS Monitor

42031

Read Only

D2030

High Stage Slide Valve Controller Set Point(n=2)

STATUS Monitor

- 194 -

QT108300

(continued)
Register Number 42032 42033 Attribute Read Only Read Only Internal Word Device D2031 D2032 Name High Stage Slide Valve Controller PID OUT(MV)% High Stage Positi1r Status Range 0 to 1000 (0):LOAD-OFF/UNLOA D-OFF 1:LOAD-ON/UNLOADOFF ,2:LOAD-OFF/UNLOAD -ON (0):OFF-NEUTRAL ,1:ACTIVE-NEUTRAL ,2:OFF-ERROR ,3:ACTIVE-ERROR (0):OFF-NEUTRAL ,1:ACTIVE-NEUTRAL ,2:OFF-ERROR ,3:ACTIVE-ERROR (0):OFF-NEUTRAL ,1:ACTIVE-NEUTRAL ,2:OFF-ERROR ,3:ACTIVE-ERROR (0):OFF-NEUTRAL ,1:ACTIVE-NEUTRAL ,2:OFF-ERROR ,3:ACTIVE-ERROR RPM RPM Category STATUS Monitor STATUS Monitor Sub Category Note

42034

Read Only

D2033

COMM-1 Status

STATUS Monitor

42035

Read Only

D2034

COMM-2 Status

STATUS Monitor

42036

Read Only

D2035

COMM-3 Status

STATUS Monitor

42037

Read Only

D2036

COMM-0 Status

STATUS Monitor

42038 42039 42040 42041 42042 42043 42044 42045 42046 42047 42048

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

D2037 D2038 D2039 D2040 D2041 D2042 D2043 D2044 D2045 D2046 D2047

VFD COMPRESSOR Revolution VFD CONDENSER Revolution Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined

STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor

- 195 -

QT108300

Holding Registers number 42049 to 42176(Internal Word (16 Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 42049 42050 42051 42052 42053 42054 42055 42056 42057 42058 42059 42060 42061 42062 42063 42064 42065 42066 42067 42068 42069 42070 42071 42072 42073 42074 42075 42076 42077 42078 42079 42080 42081 42082 42083 42084 42085 42086 42087 42088 42089 42090 42091 42092 42093 42094 42095 42096 42097 42098 42099 42100 42101 42102 42103 42104 42105 42106 42107 42108 42109 42110 42111 42112 42113 42114 42115 42116 42117 42118 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D2048 D2049 D2050 D2051 D2052 D2053 D2054 D2055 D2056 D2057 D2058 D2059 D2060 D2061 D2062 D2063 D2064 D2065 D2066 D2067 D2068 D2069 D2070 D2071 D2072 D2073 D2074 D2075 D2076 D2077 D2078 D2079 D2080 D2081 D2082 D2083 D2084 D2085 D2086 D2087 D2088 D2089 D2090 D2091 D2092 D2093 D2094 D2095 D2096 D2097 D2098 D2099 D2100 D2101 D2102 D2103 D2104 D2105 D2106 D2107 D2108 D2109 D2110 D2111 D2112 D2113 D2114 D2115 D2116 D2117 Name Undefined Undefined OPTION ANALOG INPUT1(n=0 to 3) OPTION ANALOG INPUT2(n=0 to 3) OPTION ANALOG INPUT3(n=0 to 3) OPTION ANALOG INPUT4(n=0 to 3) Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Range Category STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor STATUS Monitor for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation Sub Category Note

Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n Industrial Unit X 10^n

- 196 -

QT108300

(continued)
Register Number 42119 42120 42121 42122 42123 42124 42125 42126 42127 42128 42129 42130 42131 42132 42133 42134 42135 42136 42137 42138 42139 42140 42141 42142 42143 42144 42145 42146 42147 42148 42149 42150 42151 42152 42153 42154 42155 42156 42157 42158 42159 42160 42161 42162 42163 42164 42165 42166 42167 42168 42169 42170 42171 42172 42173 42174 42175 42176 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D2118 D2119 D2120 D2121 D2122 D2123 D2124 D2125 D2126 D2127 D2128 D2129 D2130 D2131 D2132 D2133 D2134 D2135 D2136 D2137 D2138 D2139 D2140 D2141 D2142 D2143 D2144 D2145 D2146 D2147 D2148 D2149 D2150 D2151 D2152 D2153 D2154 D2155 D2156 D2157 D2158 D2159 D2160 D2161 D2162 D2163 D2164 D2165 D2166 D2167 D2168 D2169 D2170 D2171 D2172 D2173 D2174 D2175 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Range Category for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation Sub Category Note

- 197 -

QT108300

Holding Registers number 42177 to 42200 (Internal Word (16Bits) Device can be monitored on F7: DIAGNOSTIC>8.READ REGISTER.)
Register Number 42177 42178 42179 42180 42181 42182 42183 42184 42185 42186 42187 42188 42189 42190 42191 42192 42193 42194 42195 42196 42197 42198 42199 42200 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Word Device D2176 D2177 D2178 D2179 D2180 D2181 D2182 D2183 D2184 D2185 D2186 D2187 D2188 D2189 D2190 D2191 D2192 D2193 D2194 D2195 D2196 D2197 D2198 D2199 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Range Category for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation for AUTO STAGE calculation Sub Category Note

- 198 -

QT108300

Coils number 00001 to 02624 can be read using MODBUS Function Code 01h (Read Coil Status). Coils number 00513 to 00576 can be written using MODBUS Function Code 05h (Force Single Coil) or 0Fh (Force Multiple Coils). Coils number 00001 to 00128(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 00001 00002 00003 00004 00005 00006 00007 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device Y0000h Y0001h Y0002h Y0003h Y0004h Y0005h Y0006h Name Compressor Start Oil Pump Start Low Stage Load SV Low Stage Unload SV Liquid Injection Supply SV High Stage Load SV Liquid Injection YOSAKU SV High Stage Unload SV Oil Heater Chiller Supply SV1of3(!NORTH AMERICA) J Economizer/Intercooler supply SV Economizer/Intercooler Supply SV J Vi Increase SV Oil Feed SV Oil Drain SV J Vi Decrease SV FM160 Oil Return SV Alarm/Failure Emergency Stop Input Compressor Motor Starter Read Back Interlock-1 Interlock-2(Cooling Water Flow SW) Interlock-3(Process Flow SW) J or FM160 Oil Level SW Remote Start/Stop Input Chiller Supply SV1of3 UD-V M Drain SV Chiller YOSAKU SV1of3 UD-V M Plug SV Chiller Pump Start UD-V Bypass SV Starting Bypass SV Hot Gas Bypass SV Economizer/Intercooler YOSAKU SV Oil Pump #2 Start Alarm Chiller Supply SV2of3 UD-V LH Increase SV Chiller YOSAKU SV2of3 UD-V LH Decrease SV Condenser Out1of6 Auxiliary Start Condenser Out2of6 UD-V M Drain SV Condenser Out3of6 UD-V M Plug SV Condenser Out4of6 UD-V Bypass SV Liquid Injection YOSAKU SV #2 Condenser Out5of6 UD-V LH Increase SV Chiller Supply SV3of 3 Condenser Out6of6 UD-V LH Decrease SV Chiller YOSAKU SV3of 3 Remote Load Input Remote Unload Input Category Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Sub Category Note

00008 00009

Read Only Read Only

Y0007h Y0008h

Real DI/O Real DI/O

00010 00011 00012 00013 00014 00015 00016 00017 00018 00019 00020 00021 00022 00023 00024 00025 00026 00027 00028

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

Y0009h X000Ah X000Bh X000Ch X000Dh X000Eh X000Fh Y0010h Y0011h Y0012h Y0013h Y0014h Y0015h Y0016h Y0017h Y0018h Y0019h Y001Ah Y001Bh

Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O

00029

Read Only

Y001Ch

Real DI/O

00030

Read Only

Y001Dh

Real DI/O

00031 00032 00033 00034 00035 00036 00037 00038 00039 00040 00041 00042 00043 00044 00045

Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only

X001Eh X001Fh Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined

Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O

- 199 -

QT108300

(continued)
Coil Number 00046 00047 00048 00049 00050 00051 00052 00053 00054 00055 00056 00057 00058 00059 00060 00061 00062 00063 00064 00065 00066 00067 00068 00069 00070 00071 00072 00073 00074 00075 00076 00077 00078 00079 00080 00081 00082 00083 00084 00085 00086 00087 00088 00089 00090 00091 00092 00093 00094 00095 00096 00097 00098 00099 00100 00101 00102 00103 00104 00105 00106 00107 00108 00109 00110 00111 00112 00113 00114 00115 00116 00117 00118 00119 00120 00121 00122 00123 00124 00125 00126 00127 00128 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Name Category Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Real DI/O Sub Category Note

- 200 -

QT108300

Coils number 00129 to 00256(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 00129 00130 00131 00132 00133 00134 00135 00136 00137 00138 00139 00140 00141 00142 00143 00144 00145 00146 00147 00148 00149 00150 00151 00152 00153 00154 00155 00156 00157 00158 00159 00160 00161 00162 00163 00164 00165 00166 00167 00168 00169 00170 00171 00172 00173 00174 00175 00176 00177 00178 00179 00180 00181 00182 00183 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device Y0080h Y0081h Y0082h Y0083h Y0084h Y0085h Y0086h Y0087h Y0088h Y0089h Y008Ah Y008Bh Y008Ch Y008Dh Y008Eh Y008Fh Y0090h Y0091h Y0092h Y0093h Y0094h Y0095h Y0096h Y0097h Y0098h Y0099h Y009Ah Y009Bh Y009Ch Y009Dh Y009Eh Y009Fh Y00A0h Y00A1h Y00A2h Y00A3h Y00A4h Y00A5h Y00A6h Y00A7h Y00A8h Y00A9h Y00AAh Y00ABh Y00ACh Y00ADh Y00AEh Y00AFh Y00B0h Y00B1h Y00B2h Y00B3h Y00B4h Y00B5h Y00B6h Name Undefined OP LOW P LOW DISCHAGE PRESSURE HIGH DISCHAGE TEMPERATURE HIGH OIL TEMPERATURE HIGH COMPRESSOR MOTOR CURRENT HIGH INTERMEDIATE PRESSURE HIGH SUCTION PRESSURE LOW LEAVING BRINE TEMPERATURE LOW CAPACITY NO DOWN SUCTION SUPERHEAT LOW OIL FILTER(FP High) RE-START HIGH STAGE(No Down) INTERMEDIATE SUPERHEAT LOW ENTERING BRINETEMPERATURE LOW SEPARATOR OIL TEMPERATURE LOW OP2 LOW(for 400Series) SUCTION SUPERHEAT2 LOW AUTO VI SLIDE FINE FILTER(Fine Filter Pressure High) DISCHARGE SUPERHEAT LOW SUCTION PRESSURE HIGH SUCTION TEMPERATURE HIGH CHILLER LIQUID LEVEL LOW Undefined Undefined Undefined Undefined Undefined Undefined AUTO STAGE NO REQUEST(SLAVE Only) AUTO STAGE LIST1 NO RESPONSE(MASTER Only) AUTO STAGE LIST2 NO RESPONSE(MASTER Only) AUTO STAGE LIST3 NO RESPONSE(MASTER Only) AUTO STAGE LIST4 NO RESPONSE(MASTER Only) AUTO STAGE LIST5 NO RESPONSE(MASTER Only) AUTO STAGE LIST6 NO RESPONSE(MASTER Only) AUTO STAGE LIST7 NO RESPONSE(MASTER Only) AUTO STAGE LIST8 NO RESPONSE(MASTER Only) OPTION ANALOG INPUT1 LOW OPTION ANALOG INPUT1 HIGH OPTION ANALOG INPUT2 LOW OPTION ANALOG INPUT2 HIGH OPTION ANALOG INPUT3 LOW OPTION ANALOG INPUT3 HIGH OPTION ANALOG INPUT4 LOW OPTION ANALOG INPUT4 HIGH Undefined Undefined Undefined Undefined Undefined Undefined Category Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Sub Category ALARM ALARM ALARM ALARM ALARM 1/128 2/128 3/128 4/128 5/128 Note

ALARM 6/128 ALARM 7/128 ALARM 8/128 ALARM 9/128 ALARM 10/128 ALARM ALARM ALARM ALARM ALARM ALARM 11/128 12/128 13/128 14/128 15/128 16/128

ALARM 17/128 ALARM 18/128 ALARM ALARM ALARM ALARM 19/128 20/128 21/128 22/128

ALARM 23/128 ALARM 24/128 ALARM 25/128 ALARM ALARM ALARM ALARM ALARM ALARM ALARM ALARM 26/128 27/128 28/128 29/128 30/128 31/128 32/128 33/128

ALARM 34/128 ALARM 35/128 ALARM 36/128 ALARM 37/128 ALARM 38/128 ALARM 39/128 ALARM 40/128 ALARM 41/128 ALARM 42/128 ALARM 43/128 ALARM 44/128 ALARM 45/128 ALARM 46/128 ALARM 47/128 ALARM 48/128 ALARM 49/128 ALARM ALARM ALARM ALARM ALARM ALARM 50/128 51/128 52/128 53/128 54/128 55/128

- 201 -

QT108300

(continued)
Coil Number 00184 00185 00186 00187 00188 00189 00190 00191 00192 00193 00194 00195 00196 00197 00198 00199 00200 00201 00202 00203 00204 00205 00206 00207 00208 00209 00210 00211 00212 00213 00214 00215 00216 00217 00218 00219 00220 00221 00222 00223 00224 00225 00226 00227 00228 00229 00230 00231 00232 00233 00234 00235 00236 00237 00238 00239 00240 00241 00242 00243 00244 00245 00246 00247 00248 00249 00250 00251 00252 00253 00254 00255 00256 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device Y00B7h Y00B8h Y00B9h Y00BAh Y00BBh Y00BCh Y00BDh Y00BEh Y00BFh Y00C0h Y00C1h Y00C2h Y00C3h Y00C4h Y00C5h Y00C6h Y00C7h Y00C8h Y00C9h Y00CAh Y00CBh Y00CCh Y00CDh Y00CEh Y00CFh Y00D0h Y00D1h Y00D2h Y00D3h Y00D4h Y00D5h Y00D6h Y00D7h Y00D8h Y00D9h Y00DAh Y00DBh Y00DCh Y00DDh Y00DEh Y00DFh Y00E0h Y00E1h Y00E2h Y00E3h Y00E4h Y00E5h Y00E6h Y00E7h Y00E8h Y00E9h Y00EAh Y00EBh Y00ECh Y00EDh Y00EEh Y00EFh Y00F0h Y00F1h Y00F2h Y00F3h Y00F4h Y00F5h Y00F6h Y00F7h Y00F8h Y00F9h Y00FAh Y00FBh Y00FCh Y00FDh Y00FEh Y00FFh Name Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Category Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Sub Category ALARM 56/128 ALARM 57/128 ALARM 58/128 ALARM 59/128 ALARM 60/128 ALARM 61/128 ALARM 62/128 ALARM 63/128 ALARM 64/128 ALARM 65/128 ALARM 66/128 ALARM 67/128 ALARM 68/128 ALARM 69/128 ALARM 70/128 ALARM 71/128 ALARM 72/128 ALARM 73/128 ALARM 74/128 ALARM 75/128 ALARM 76/128 ALARM 77/128 ALARM 78/128 ALARM 79/128 ALARM 80/128 ALARM 81/128 ALARM 82/128 ALARM 83/128 ALARM 84/128 ALARM 85/128 ALARM 86/128 ALARM 87/128 ALARM 88/128 ALARM 89/128 ALARM 90/128 ALARM 91/128 ALARM 92/128 ALARM 93/128 ALARM 94/128 ALARM 95/128 ALARM 96/128 ALARM 97/128 ALARM 98/128 ALARM 99/128 ALARM 100/128 ALARM 101/128 ALARM 102/128 ALARM 103/128 ALARM 104/128 ALARM 105/128 ALARM 106/128 ALARM 107/128 ALARM 108/128 ALARM 109/128 ALARM 110/128 ALARM 111/128 ALARM 112/128 ALARM 113/128 ALARM 114/128 ALARM 115/128 ALARM 116/128 ALARM 117/128 ALARM 118/128 ALARM 119/128 ALARM 120/128 ALARM 121/128 ALARM 122/128 ALARM 123/128 ALARM 124/128 ALARM 125/128 ALARM 126/128 ALARM 127/128 ALARM 128/128 Note

- 202 -

QT108300

Coils number 00257 to 00384(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 00257 00258 00259 00260 00261 00262 00263 00264 00265 00266 00267 00268 00269 00270 00271 00272 00273 00274 00275 00276 00277 00278 00279 00280 00281 00282 00283 00284 00285 00286 00287 00288 00289 00290 00291 00292 00293 00294 00295 00296 00297 00298 00299 00300 00301 00302 00303 00304 00305 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device Y0100h Y0101h Y0102h Y0103h Y0104h Y0105h Y0106h Y0107h Y0108h Y0109h Y010Ah Y010Bh Y010Ch Y010Dh Y010Eh Y010Fh Y0110h Y0111h Y0112h Y0113h Y0114h Y0115h Y0116h Y0117h Y0118h Y0119h Y011Ah Y011Bh Y011Ch Y011Dh Y011Eh Y011Fh Y0120h Y0121h Y0122h Y0123h Y0124h Y0125h Y0126h Y0127h Y0128h Y0129h Y012Ah Y012Bh Y012Ch Y012Dh Y012Eh Y012Fh Y0130h Name Start Fail OP LOW P LOW DISCHARGE PRESSURE HIGH DISCHARGE TEMPERATURE HIGH OIL TEMPERATURE HIGH COMPRESSOR MOTOR ELECTRIC CURRENT HIGH OIL FILTER(FP High) INTERLOCK-2 EMERGENCY STOP OIL LEVEL LOW FINE FILTER(Fine Filter Pressure High) INTERMEDIATE PRESSURE HIGH INTERLOCK LEAVING BRINE TEMPERATURE LOW INTERLOCK-3 SUCTION PRESSURE LOW SUCTION PRESSURE OVER RANGE DISCHAGE PRESSURE UNDER RANGE OIL SUPPLY PRESSURE OVER RANGE AFTER FILTER PRESSURE OVER RANGE SUCTION TEMPERATURE UNDER/OVER RANGE DISCHARGE TEMPERATURE UNDER RANGE OIL SUPPLY TEMPERATURE UNDER RANGE INTERMEDIATE PRESSURE UNDER RANGE INTERMEDIATE TEMPERATURE UNDER/OVER RANGE COMPRESSOR MOTOR CURRENT UNDER RANGE LEAVING BRINE TEMPERATURE OVER RANGE LOW SLIDE VALVE POSITION UNDER/OVER RANGE HIGH SLIDE VALVE POSITION UNDER/OVER RANGE CHILLER GAS TEMPERATURE1&2 UNDER/OVER RANGE SUCTION PRESSURE1&2 UNDER/OVER RANGE Undefined SUCTION SUPERHEAT LOW SUCTION SUPERHEAT2 LOW SUCTION PRESSURE HIGH SUCTION TEMPERATURE HIGH Undefined Undefined Undefined Undefined OPTION ANALOG INPUT1 LOW OPTION ANALOG INPUT1 HIGH OPTION ANALOG INPUT2 LOW OPTION ANALOG INPUT2 HIGH OPTION ANALOG INPUT3 LOW OPTION ANALOG INPUT3 HIGH OPTION ANALOG INPUT4 LOW OPTION ANALOG INPUT4 HIGH Category Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Sub Category FAILURE FAILURE FAILURE FAILURE 1/128 2/128 3/128 4/128 Note

FAILURE 5/128 FAILURE 6/128 FAILURE 7/128 FAILURE FAILURE FAILURE FAILURE FAILURE 8/128 9/128 10/128 11/128 12/128

FAILURE 13/128 FAILURE 14/128 FAILURE 15/128 FAILURE 16/128 FAILURE 17/128 FAILURE 18/128 FAILURE 19/128 FAILURE 20/128 FAILURE 21/128 FAILURE 22/128 FAILURE 23/128 FAILURE 24/128 FAILURE 25/128 FAILURE 26/128 FAILURE 27/128 FAILURE 28/128 FAILURE 29/128 FAILURE 30/128 FAILURE 31/128 FAILURE 32/128 FAILURE FAILURE FAILURE FAILURE FAILURE FAILURE FAILURE FAILURE FAILURE FAILURE 33/128 34/128 35/128 36/128 37/128 38/128 39/128 40/128 41/128 42/128

FAILURE 43/128 FAILURE 44/128 FAILURE 45/128 FAILURE 46/128 FAILURE 47/128 FAILURE 48/128 FAILURE 49/128

- 203 -

QT108300

(continued)
Coil Number 00306 00307 00308 00309 00310 00311 00312 00313 00314 00315 00316 00317 00318 00319 00320 00321 00322 00323 00324 00325 00326 00327 00328 00329 00330 00331 00332 00333 00334 00335 00336 00337 00338 00339 00340 00341 00342 00343 00344 00345 00346 00347 00348 00349 00350 00351 00352 00353 00354 00355 00356 00357 00358 00359 00360 00361 00362 00363 00364 00365 00366 00367 00368 00369 00370 00371 00372 00373 00374 00375 00376 00377 00378 00379 00380 00381 00382 00383 00384 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device Y0131h Y0132h Y0133h Y0134h Y0135h Y0136h Y0137h Y0138h Y0139h Y013Ah Y013Bh Y013Ch Y013Dh Y013Eh Y013Fh Y0140h Y0141h Y0142h Y0143h Y0144h Y0145h Y0146h Y0147h Y0148h Y0149h Y014Ah Y014Bh Y014Ch Y014Dh Y014Eh Y014Fh Y0150h Y0151h Y0152h Y0153h Y0154h Y0155h Y0156h Y0157h Y0158h Y0159h Y015Ah Y015Bh Y015Ch Y015Dh Y015Eh Y015Fh Y0160h Y0161h Y0162h Y0163h Y0164h Y0165h Y0166h Y0167h Y0168h Y0169h Y016Ah Y016Bh Y016Ch Y016Dh Y016Eh Y016Fh Y0170h Y0171h Y0172h Y0173h Y0174h Y0175h Y0176h Y0177h Y0178h Y0179h Y017Ah Y017Bh Y017Ch Y017Dh Y017Eh Y017Fh Name Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Category Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Pseudo D/O Sub Category FAILURE 50/128 FAILURE 51/128 FAILURE 52/128 FAILURE 53/128 FAILURE 54/128 FAILURE 55/128 FAILURE 56/128 FAILURE 57/128 FAILURE 58/128 FAILURE 59/128 FAILURE 60/128 FAILURE 61/128 FAILURE 62/128 FAILURE 63/128 FAILURE 64/128 FAILURE 65/128 FAILURE 66/128 FAILURE 67/128 FAILURE 68/128 FAILURE 69/128 FAILURE 70/128 FAILURE 71/128 FAILURE 72/128 FAILURE 73/128 FAILURE 74/128 FAILURE 75/128 FAILURE 76/128 FAILURE 77/128 FAILURE 78/128 FAILURE 79/128 FAILURE 80/128 FAILURE 81/128 FAILURE 82/128 FAILURE 83/128 FAILURE 84/128 FAILURE 85/128 FAILURE 86/128 FAILURE 87/128 FAILURE 88/128 FAILURE 89/128 FAILURE 90/128 FAILURE 91/128 FAILURE 92/128 FAILURE 93/128 FAILURE 94/128 FAILURE 95/128 FAILURE 96/128 FAILURE 97/128 FAILURE 98/128 FAILURE 99/128 FAILURE 100/128 FAILURE 101/128 FAILURE 102/128 FAILURE 103/128 FAILURE 104/128 FAILURE 105/128 FAILURE 106/128 FAILURE 107/128 FAILURE 108/128 FAILURE 109/128 FAILURE 110/128 FAILURE 111/128 FAILURE 112/128 FAILURE 113/128 FAILURE 114/128 FAILURE 115/128 FAILURE 116/128 FAILURE 117/128 FAILURE 118/128 FAILURE 119/128 FAILURE 120/128 FAILURE 121/128 FAILURE 122/128 FAILURE 123/128 FAILURE 124/128 FAILURE 125/128 FAILURE 126/128 FAILURE 127/128 FAILURE 128/128 Note

- 204 -

QT108300

Coils number 00385 to 00512(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 00385 00386 00387 00388 00389 00390 00391 00392 00393 00394 00395 00396 00397 00398 00399 00400 00401 00402 00403 00404 00405 00406 00407 00408 00409 00410 00411 00412 00413 00414 00415 00416 00417 00418 00419 00420 00421 00422 00423 00424 00425 00426 00427 00428 00429 00430 00431 00432 00433 00434 00435 00436 00437 00438 00439 00440 00441 00442 00443 00444 00445 00446 00447 00448 00449 00450 00451 00452 00453 00454 00455 00456 00457 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device X00C0h X00C1h X00C2h X00C3h X00C4h X00C5h X00C6h X00C7h X00C8h X00C9h X00CAh X00CBh X00CCh X00CDh X00CEh X00CFh X00D0h X00D1h X00D2h X00D3h X00D4h X00D5h X00D6h X00D7h X00D8h X00D9h X00DAh X00DBh X00DCh X00DDh X00DEh X00DFh X00E0h X00E1h X00E2h X00E3h X00E4h X00E5h X00E6h X00E7h X00E8h X00E9h X00EAh X00EBh X00ECh X00EDh X00EEh X00EFh X00F0h X00F1h X00F2h X00F3h X00F4h X00F5h X00F6h X00F7h X00F8h X00F9h X00FAh X00FBh X00FCh X00FDh X00FEh X00FFh X0100h X0101h X0102h X0103h X0104h X0105h X0106h X0107h X0108h Name Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Category Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Sub Category MODE 1/64 MODE 2/64 MODE 3/64 MODE 4/64 MODE 5/64 MODE 6/64 MODE 7/64 MODE 8/64 MODE 9/64 MODE 10/64 MODE 11/64 MODE 12/64 MODE 13/64 MODE 14/64 MODE 15/64 MODE 16/64 MODE 17/64 MODE 18/64 MODE 19/64 MODE 20/64 MODE 21/64 MODE 22/64 MODE 23/64 MODE 24/64 MODE 25/64 MODE 26/64 MODE 27/64 MODE 28/64 MODE 29/64 MODE 30/64 MODE 31/64 MODE 32/64 MODE 33/64 MODE 34/64 MODE 35/64 MODE 36/64 MODE 37/64 MODE 38/64 MODE 39/64 MODE 40/64 MODE 41/64 MODE 42/64 MODE 43/64 MODE 44/64 MODE 45/64 MODE 46/64 MODE 47/64 MODE 48/64 MODE 49/64 MODE 50/64 MODE 51/64 MODE 52/64 MODE 53/64 MODE 54/64 MODE 55/64 MODE 56/64 MODE 57/64 MODE 58/64 MODE 59/64 MODE 60/64 MODE 61/64 MODE 62/64 MODE 63/64 MODE 64/64 CONFIGURATION 1/64 CONFIGURATION 2/64 CONFIGURATION 3/64 CONFIGURATION 4/64 CONFIGURATION 5/64 CONFIGURATION 6/64 CONFIGURATION 7/64 CONFIGURATION 8/64 CONFIGURATION 9/64 Note

- 205 -

QT108300

(continued)
Coil Number 00458 00459 00460 00461 00462 00463 00464 00465 00466 00467 00468 00469 00470 00471 00472 00473 00474 00475 00476 00477 00478 00479 00480 00481 00482 00483 00484 00485 00486 00487 00488 00489 00490 00491 00492 00493 00494 00495 00496 00497 00498 00499 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device X0109h X010Ah X010Bh X010Ch X010Dh X010Eh X010Fh X0110h X0111h X0112h X0113h X0114h X0115h X0116h X0117h X0118h X0119h X011Ah X011Bh X011Ch X011Dh X011Eh X011Fh X0120h X0121h X0122h X0123h X0124h X0125h X0126h X0127h X0128h X0129h X012Ah X012Bh X012Ch X012Dh X012Eh X012Fh X0130h X0131h X0132h Name Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Category Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Sub Category CONFIGURATION 10/64 CONFIGURATION 11/64 CONFIGURATION 12/64 CONFIGURATION 13/64 CONFIGURATION 14/64 CONFIGURATION 15/64 CONFIGURATION 16/64 CONFIGURATION 17/64 CONFIGURATION 18/64 CONFIGURATION 19/64 CONFIGURATION 20/64 CONFIGURATION 21/64 CONFIGURATION 22/64 CONFIGURATION 23/64 CONFIGURATION 24/64 CONFIGURATION 25/64 CONFIGURATION 26/64 CONFIGURATION 27/64 CONFIGURATION 28/64 CONFIGURATION 29/64 CONFIGURATION 30/64 CONFIGURATION 31/64 CONFIGURATION 32/64 CONFIGURATION 33/64 CONFIGURATION 34/64 CONFIGURATION 35/64 CONFIGURATION 36/64 CONFIGURATION 37/64 CONFIGURATION 38/64 CONFIGURATION 39/64 CONFIGURATION 40/64 CONFIGURATION 41/64 CONFIGURATION 42/64 CONFIGURATION 43/64 CONFIGURATION 44/64 CONFIGURATION 45/64 CONFIGURATION 46/64 CONFIGURATION 47/64 CONFIGURATION 48/64 CONFIGURATION 49/64 CONFIGURATION 50/64 CONFIGURATION 51/64 Note

- 206 -

QT108300

(continued)
Coil Number 00500 00501 00502 00503 00504 00505 00506 00507 00508 00509 00510 00511 00512 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device X0133h X0134h X0135h X0136h X0137h X0138h X0139h X013Ah X013Bh X013Ch X013Dh X013Eh X013Fh Name Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Category Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Sub Category CONFIGURATION 52/64 CONFIGURATION 53/64 CONFIGURATION 54/64 CONFIGURATION 55/64 CONFIGURATION 56/64 CONFIGURATION 57/64 CONFIGURATION 58/64 CONFIGURATION 59/64 CONFIGURATION 60/64 CONFIGURATION 61/64 CONFIGURATION 62/64 CONFIGURATION 63/64 CONFIGURATION 64/64 Note

- 207 -

QT108300

Coils number 00513 to 00640(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 00513 Attribute Read/Write Internal Bit Device X0140h Name Communication Compressor Start Input Communication Compressor Immediate Stop Input Communication Compressor Full Load Input Communication Compressor Load Limit input Category Pseudo D/I Sub Category COMMUNICATION 1/64 COMMUNICATION 2/64 COMMUNICATION 3/64 COMMUNICATION 4/64 Note Required OPERATION MODE: COMM or Write 2 to Holding Register number 41001. Forcibly Finishes PUMP OUT Process Capacity MVH% is limited to "REMOTE MVH%" on F2:1.CAPACITY CONTROL or 2.VFD COMPRESSOR

00514 00515 00516

Read/Write Read/Write Read/Write

X0141h X0142h X0143h

Pseudo D/I Pseudo D/I Pseudo D/I

00517 00518 00519 00520 00521 00522 00523 00524 00525 00526 00527 00528 00529 00530 00531 00532 00533 00534 00535 00536 00537 00538 00539 00540 00541 00542 00543 00544 00545 00546 00547 00548 00549 00550

Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write

X0144h X0145h X0146h X0147h X0148h X0149h X014Ah X014Bh X014Ch X014Dh X014Eh X014Fh X0150h X0151h X0152h X0153h X0154h X0155h X0156h X0157h X0158h X0159h X015Ah X015Bh X015Ch X015Dh X015Eh X015Fh X0160h X0161h X0162h X0163h X0164h X0165h

Undefined Communication Chiller LBT Controller 100% Input Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined

Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I

COMMUNICATION 5/64 COMMUNICATION 6/64 COMMUNICATION 7/64 COMMUNICATION 8/64 COMMUNICATION 9/64 COMMUNICATION 10/64 COMMUNICATION 11/64 COMMUNICATION 12/64 COMMUNICATION 13/64 COMMUNICATION 14/64 COMMUNICATION 15/64 COMMUNICATION 16/64 COMMUNICATION 17/64 COMMUNICATION 18/64 COMMUNICATION 19/64 COMMUNICATION 20/64 COMMUNICATION 21/64 COMMUNICATION 22/64 COMMUNICATION 23/64 COMMUNICATION 24/64 COMMUNICATION 25/64 COMMUNICATION 26/64 COMMUNICATION 27/64 COMMUNICATION 28/64 COMMUNICATION 29/64 COMMUNICATION 30/64 COMMUNICATION 31/64 COMMUNICATION 32/64 COMMUNICATION 33/64 COMMUNICATION 34/64 COMMUNICATION 35/64 COMMUNICATION 36/64 COMMUNICATION 37/64 COMMUNICATION 38/64

- 208 -

QT108300

(continued)
Coil Number 00551 00552 00553 00554 00555 00556 00557 00558 00559 00560 00561 00562 00563 00564 00565 00566 00567 00568 00569 00570 00571 00572 00573 00574 00575 00576 00577 00578 00579 00580 00581 00582 00583 00584 00585 00586 00587 00588 00589 00590 00591 00592 00593 00594 00595 00596 00597 00598 00599 00600 00601 00602 00603 00604 00605 00606 00607 00608 Attribute Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read/Write Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device X0166h X0167h X0168h X0169h X016Ah X016Bh X016Ch X016Dh X016Eh X016Fh X0170h X0171h X0172h X0173h X0174h X0175h X0176h X0177h X0178h X0179h X017Ah X017Bh X017Ch X017Dh X017Eh X017Fh M0000 M0001 M0002 M0003 M0004 M0005 M0006 M0007 M0008 M0009 M0010 M0011 M0012 M0013 M0014 M0015 M0016 M0017 M0018 M0019 M0020 M0021 M0022 M0023 M0024 M0025 M0026 M0027 M0028 M0029 M0030 M0031 Name Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Undefined Communication Clear Alarm input Category Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo D/I Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category COMMUNICATION 39/64 COMMUNICATION 40/64 COMMUNICATION 41/64 COMMUNICATION 42/64 COMMUNICATION 43/64 COMMUNICATION 44/64 COMMUNICATION 45/64 COMMUNICATION 46/64 COMMUNICATION 47/64 COMMUNICATION 48/64 COMMUNICATION 49/64 COMMUNICATION 50/64 COMMUNICATION 51/64 COMMUNICATION 52/64 COMMUNICATION 53/64 COMMUNICATION 54/64 COMMUNICATION 55/64 COMMUNICATION 56/64 COMMUNICATION 57/64 COMMUNICATION 58/64 COMMUNICATION 59/64 COMMUNICATION 60/64 COMMUNICATION 61/64 COMMUNICATION 62/64 COMMUNICATION 63/64 COMMUNICATION 64/64 Note

Effective Only in the moment of OFF to ON

LOCAL/REMOTE/COMM ON

PUMP OUT

- 209 -

QT108300

(continued)
Coil Number 00609 00610 00611 00612 00613 00614 00615 00616 00617 00618 00619 00620 00621 00622 00623 00624 00625 00626 00627 00628 00629 00630 00631 00632 00633 00634 00635 00636 00637 00638 00639 00640 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0032 M0033 M0034 M0035 M0036 M0037 M0038 M0039 M0040 M0041 M0042 M0043 M0044 M0045 M0046 M0047 M0048 M0049 M0050 M0051 M0052 M0053 M0054 M0055 M0056 M0057 M0058 M0059 M0060 M0061 M0062 M0063 Name Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

FAILURE

H PORT SELECT

- 210 -

QT108300

Coils number 00641 to 00768(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 00641 00642 00643 00644 00645 00646 00647 00648 00649 00650 00651 00652 00653 00654 00655 00656 00657 00658 00659 00660 00661 00662 00663 00664 00665 00666 00667 00668 00669 00670 00671 00672 00673 00674 00675 00676 00677 00678 00679 00680 00681 00682 00683 00684 00685 00686 00687 00688 00689 00690 00691 00692 00693 00694 00695 00696 00697 00698 00699 00700 00701 00702 00703 00704 00705 00706 00707 00708 00709 00710 00711 00712 00713 00714 00715 00716 00717 00718 00719 00720 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0064 M0065 M0066 M0067 M0068 M0069 M0070 M0071 M0072 M0073 M0074 M0075 M0076 M0077 M0078 M0079 M0080 M0081 M0082 M0083 M0084 M0085 M0086 M0087 M0088 M0089 M0090 M0091 M0092 M0093 M0094 M0095 M0096 M0097 M0098 M0099 M0100 M0101 M0102 M0103 M0104 M0105 M0106 M0107 M0108 M0109 M0110 M0111 M0112 M0113 M0114 M0115 M0116 M0117 M0118 M0119 M0120 M0121 M0122 M0123 M0124 M0125 M0126 M0127 M0128 M0129 M0130 M0131 M0132 M0133 M0134 M0135 M0136 M0137 M0138 M0139 M0140 M0141 M0142 M0143 Name M PORT SELECT Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

ALARM

VFD COMPRESSOR CONTROL

SETUP H PORT SETTING SETUP M PORT SETTING SETUP L PORT SETTING

- 211 -

QT108300

(continued)
Coil Number 00721 00722 00723 00724 00725 00726 00727 00728 00729 00730 00731 00732 00733 00734 00735 00736 00737 00738 00739 00740 00741 00742 00743 00744 00745 00746 00747 00748 00749 00750 00751 00752 00753 00754 00755 00756 00757 00758 00759 00760 00761 00762 00763 00764 00765 00766 00767 00768 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0144 M0145 M0146 M0147 M0148 M0149 M0150 M0151 M0152 M0153 M0154 M0155 M0156 M0157 M0158 M0159 M0160 M0161 M0162 M0163 M0164 M0165 M0166 M0167 M0168 M0169 M0170 M0171 M0172 M0173 M0174 M0175 M0176 M0177 M0178 M0179 M0180 M0181 M0182 M0183 M0184 M0185 M0186 M0187 M0188 M0189 M0190 M0191 Name Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 212 -

QT108300

Coils number 00769 to 00896(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 00769 00770 00771 00772 00773 00774 00775 00776 00777 00778 00779 00780 00781 00782 00783 00784 00785 00786 00787 00788 00789 00790 00791 00792 00793 00794 00795 00796 00797 00798 00799 00800 00801 00802 00803 00804 00805 00806 00807 00808 00809 00810 00811 00812 00813 00814 00815 00816 00817 00818 00819 00820 00821 00822 00823 00824 00825 00826 00827 00828 00829 00830 00831 00832 00833 00834 00835 00836 00837 00838 00839 00840 00841 00842 00843 00844 00845 00846 00847 00848 00849 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0192 M0193 M0194 M0195 M0196 M0197 M0198 M0199 M0200 M0201 M0202 M0203 M0204 M0205 M0206 M0207 M0208 M0209 M0210 M0211 M0212 M0213 M0214 M0215 M0216 M0217 M0218 M0219 M0220 M0221 M0222 M0223 M0224 M0225 M0226 M0227 M0228 M0229 M0230 M0231 M0232 M0233 M0234 M0235 M0236 M0237 M0238 M0239 M0240 M0241 M0242 M0243 M0244 M0245 M0246 M0247 M0248 M0249 M0250 M0251 M0252 M0253 M0254 M0255 M0256 M0257 M0258 M0259 M0260 M0261 M0262 M0263 M0264 M0265 M0266 M0267 M0268 M0269 M0270 M0271 M0272 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 213 -

QT108300

(continued)
Coil Number 00850 00851 00852 00853 00854 00855 00856 00857 00858 00859 00860 00861 00862 00863 00864 00865 00866 00867 00868 00869 00870 00871 00872 00873 00874 00875 00876 00877 00878 00879 00880 00881 00882 00883 00884 00885 00886 00887 00888 00889 00890 00891 00892 00893 00894 00895 00896 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0273 M0274 M0275 M0276 M0277 M0278 M0279 M0280 M0281 M0282 M0283 M0284 M0285 M0286 M0287 M0288 M0289 M0290 M0291 M0292 M0293 M0294 M0295 M0296 M0297 M0298 M0299 M0300 M0301 M0302 M0303 M0304 M0305 M0306 M0307 M0308 M0309 M0310 M0311 M0312 M0313 M0314 M0315 M0316 M0317 M0318 M0319 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 214 -

QT108300

Coils number 00897 to 01024(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 00897 00898 00899 00900 00901 00902 00903 00904 00905 00906 00907 00908 00909 00910 00911 00912 00913 00914 00915 00916 00917 00918 00919 00920 00921 00922 00923 00924 00925 00926 00927 00928 00929 00930 00931 00932 00933 00934 00935 00936 00937 00938 00939 00940 00941 00942 00943 00944 00945 00946 00947 00948 00949 00950 00951 00952 00953 00954 00955 00956 00957 00958 00959 00960 00961 00962 00963 00964 00965 00966 00967 00968 00969 00970 00971 00972 00973 00974 00975 00976 00977 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0320 M0321 M0322 M0323 M0324 M0325 M0326 M0327 M0328 M0329 M0330 M0331 M0332 M0333 M0334 M0335 M0336 M0337 M0338 M0339 M0340 M0341 M0342 M0343 M0344 M0345 M0346 M0347 M0348 M0349 M0350 M0351 M0352 M0353 M0354 M0355 M0356 M0357 M0358 M0359 M0360 M0361 M0362 M0363 M0364 M0365 M0366 M0367 M0368 M0369 M0370 M0371 M0372 M0373 M0374 M0375 M0376 M0377 M0378 M0379 M0380 M0381 M0382 M0383 M0384 M0385 M0386 M0387 M0388 M0389 M0390 M0391 M0392 M0393 M0394 M0395 M0396 M0397 M0398 M0399 M0400 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 215 -

QT108300

(continued)
Coil Number 00978 00979 00980 00981 00982 00983 00984 00985 00986 00987 00988 00989 00990 00991 00992 00993 00994 00995 00996 00997 00998 00999 01000 01001 01002 01003 01004 01005 01006 01007 01008 01009 01010 01011 01012 01013 01014 01015 01016 01017 01018 01019 01020 01021 01022 01023 01024 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0401 M0402 M0403 M0404 M0405 M0406 M0407 M0408 M0409 M0410 M0411 M0412 M0413 M0414 M0415 M0416 M0417 M0418 M0419 M0420 M0421 M0422 M0423 M0424 M0425 M0426 M0427 M0428 M0429 M0430 M0431 M0432 M0433 M0434 M0435 M0436 M0437 M0438 M0439 M0440 M0441 M0442 M0443 M0444 M0445 M0446 M0447 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 216 -

QT108300

Coils number 01025 to 01152(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 01025 01026 01027 01028 01029 01030 01031 01032 01033 01034 01035 01036 01037 01038 01039 01040 01041 01042 01043 01044 01045 01046 01047 01048 01049 01050 01051 01052 01053 01054 01055 01056 01057 01058 01059 01060 01061 01062 01063 01064 01065 01066 01067 01068 01069 01070 01071 01072 01073 01074 01075 01076 01077 01078 01079 01080 01081 01082 01083 01084 01085 01086 01087 01088 01089 01090 01091 01092 01093 01094 01095 01096 01097 01098 01099 01100 01101 01102 01103 01104 01105 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0448 M0449 M0450 M0451 M0452 M0453 M0454 M0455 M0456 M0457 M0458 M0459 M0460 M0461 M0462 M0463 M0464 M0465 M0466 M0467 M0468 M0469 M0470 M0471 M0472 M0473 M0474 M0475 M0476 M0477 M0478 M0479 M0480 M0481 M0482 M0483 M0484 M0485 M0486 M0487 M0488 M0489 M0490 M0491 M0492 M0493 M0494 M0495 M0496 M0497 M0498 M0499 M0500 M0501 M0502 M0503 M0504 M0505 M0506 M0507 M0508 M0509 M0510 M0511 M0512 M0513 M0514 M0515 M0516 M0517 M0518 M0519 M0520 M0521 M0522 M0523 M0524 M0525 M0526 M0527 M0528 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 217 -

QT108300

(continued)
Coil Number 01106 01107 01108 01109 01110 01111 01112 01113 01114 01115 01116 01117 01118 01119 01120 01121 01122 01123 01124 01125 01126 01127 01128 01129 01130 01131 01132 01133 01134 01135 01136 01137 01138 01139 01140 01141 01142 01143 01144 01145 01146 01147 01148 01149 01150 01151 01152 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0529 M0530 M0531 M0532 M0533 M0534 M0535 M0536 M0537 M0538 M0539 M0540 M0541 M0542 M0543 M0544 M0545 M0546 M0547 M0548 M0549 M0550 M0551 M0552 M0553 M0554 M0555 M0556 M0557 M0558 M0559 M0560 M0561 M0562 M0563 M0564 M0565 M0566 M0567 M0568 M0569 M0570 M0571 M0572 M0573 M0574 M0575 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 218 -

QT108300

Coils number 01153 to 01280(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 01153 01154 01155 01156 01157 01158 01159 01160 01161 01162 01163 01164 01165 01166 01167 01168 01169 01170 01171 01172 01173 01174 01175 01176 01177 01178 01179 01180 01181 01182 01183 01184 01185 01186 01187 01188 01189 01190 01191 01192 01193 01194 01195 01196 01197 01198 01199 01200 01201 01202 01203 01204 01205 01206 01207 01208 01209 01210 01211 01212 01213 01214 01215 01216 01217 01218 01219 01220 01221 01222 01223 01224 01225 01226 01227 01228 01229 01230 01231 01232 01233 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0576 M0577 M0578 M0579 M0580 M0581 M0582 M0583 M0584 M0585 M0586 M0587 M0588 M0589 M0590 M0591 M0592 M0593 M0594 M0595 M0596 M0597 M0598 M0599 M0600 M0601 M0602 M0603 M0604 M0605 M0606 M0607 M0608 M0609 M0610 M0611 M0612 M0613 M0614 M0615 M0616 M0617 M0618 M0619 M0620 M0621 M0622 M0623 M0624 M0625 M0626 M0627 M0628 M0629 M0630 M0631 M0632 M0633 M0634 M0635 M0636 M0637 M0638 M0639 M0640 M0641 M0642 M0643 M0644 M0645 M0646 M0647 M0648 M0649 M0650 M0651 M0652 M0653 M0654 M0655 M0656 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 219 -

QT108300

(continued)
Coil Number 01234 01235 01236 01237 01238 01239 01240 01241 01242 01243 01244 01245 01246 01247 01248 01249 01250 01251 01252 01253 01254 01255 01256 01257 01258 01259 01260 01261 01262 01263 01264 01265 01266 01267 01268 01269 01270 01271 01272 01273 01274 01275 01276 01277 01278 01279 01280 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0657 M0658 M0659 M0660 M0661 M0662 M0663 M0664 M0665 M0666 M0667 M0668 M0669 M0670 M0671 M0672 M0673 M0674 M0675 M0676 M0677 M0678 M0679 M0680 M0681 M0682 M0683 M0684 M0685 M0686 M0687 M0688 M0689 M0690 M0691 M0692 M0693 M0694 M0695 M0696 M0697 M0698 M0699 M0700 M0701 M0702 M0703 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 220 -

QT108300

Coils number 01281 to 01408(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 01281 01282 01283 01284 01285 01286 01287 01288 01289 01290 01291 01292 01293 01294 01295 01296 01297 01298 01299 01300 01301 01302 01303 01304 01305 01306 01307 01308 01309 01310 01311 01312 01313 01314 01315 01316 01317 01318 01319 01320 01321 01322 01323 01324 01325 01326 01327 01328 01329 01330 01331 01332 01333 01334 01335 01336 01337 01338 01339 01340 01341 01342 01343 01344 01345 01346 01347 01348 01349 01350 01351 01352 01353 01354 01355 01356 01357 01358 01359 01360 01361 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0704 M0705 M0706 M0707 M0708 M0709 M0710 M0711 M0712 M0713 M0714 M0715 M0716 M0717 M0718 M0719 M0720 M0721 M0722 M0723 M0724 M0725 M0726 M0727 M0728 M0729 M0730 M0731 M0732 M0733 M0734 M0735 M0736 M0737 M0738 M0739 M0740 M0741 M0742 M0743 M0744 M0745 M0746 M0747 M0748 M0749 M0750 M0751 M0752 M0753 M0754 M0755 M0756 M0757 M0758 M0759 M0760 M0761 M0762 M0763 M0764 M0765 M0766 M0767 M0768 M0769 M0770 M0771 M0772 M0773 M0774 M0775 M0776 M0777 M0778 M0779 M0780 M0781 M0782 M0783 M0784 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 221 -

QT108300

(continued)
Coil Number 01362 01363 01364 01365 01366 01367 01368 01369 01370 01371 01372 01373 01374 01375 01376 01377 01378 01379 01380 01381 01382 01383 01384 01385 01386 01387 01388 01389 01390 01391 01392 01393 01394 01395 01396 01397 01398 01399 01400 01401 01402 01403 01404 01405 01406 01407 01408 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0785 M0786 M0787 M0788 M0789 M0790 M0791 M0792 M0793 M0794 M0795 M0796 M0797 M0798 M0799 M0800 M0801 M0802 M0803 M0804 M0805 M0806 M0807 M0808 M0809 M0810 M0811 M0812 M0813 M0814 M0815 M0816 M0817 M0818 M0819 M0820 M0821 M0822 M0823 M0824 M0825 M0826 M0827 M0828 M0829 M0830 M0831 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 222 -

QT108300

Coils number 01409 to 01536(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 01409 01410 01411 01412 01413 01414 01415 01416 01417 01418 01419 01420 01421 01422 01423 01424 01425 01426 01427 01428 01429 01430 01431 01432 01433 01434 01435 01436 01437 01438 01439 01440 01441 01442 01443 01444 01445 01446 01447 01448 01449 01450 01451 01452 01453 01454 01455 01456 01457 01458 01459 01460 01461 01462 01463 01464 01465 01466 01467 01468 01469 01470 01471 01472 01473 01474 01475 01476 01477 01478 01479 01480 01481 01482 01483 01484 01485 01486 01487 01488 01489 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0832 M0833 M0834 M0835 M0836 M0837 M0838 M0839 M0840 M0841 M0842 M0843 M0844 M0845 M0846 M0847 M0848 M0849 M0850 M0851 M0852 M0853 M0854 M0855 M0856 M0857 M0858 M0859 M0860 M0861 M0862 M0863 M0864 M0865 M0866 M0867 M0868 M0869 M0870 M0871 M0872 M0873 M0874 M0875 M0876 M0877 M0878 M0879 M0880 M0881 M0882 M0883 M0884 M0885 M0886 M0887 M0888 M0889 M0890 M0891 M0892 M0893 M0894 M0895 M0896 M0897 M0898 M0899 M0900 M0901 M0902 M0903 M0904 M0905 M0906 M0907 M0908 M0909 M0910 M0911 M0912 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 223 -

QT108300

(continued)
Coil Number 01490 01491 01492 01493 01494 01495 01496 01497 01498 01499 01500 01501 01502 01503 01504 01505 01506 01507 01508 01509 01510 01511 01512 01513 01514 01515 01516 01517 01518 01519 01520 01521 01522 01523 01524 01525 01526 01527 01528 01529 01530 01531 01532 01533 01534 01535 01536 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0913 M0914 M0915 M0916 M0917 M0918 M0919 M0920 M0921 M0922 M0923 M0924 M0925 M0926 M0927 M0928 M0929 M0930 M0931 M0932 M0933 M0934 M0935 M0936 M0937 M0938 M0939 M0940 M0941 M0942 M0943 M0944 M0945 M0946 M0947 M0948 M0949 M0950 M0951 M0952 M0953 M0954 M0955 M0956 M0957 M0958 M0959 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

- 224 -

QT108300

Coils number 01537 to 01664(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 01537 01538 01539 01540 01541 01542 01543 01544 01545 01546 01547 01548 01549 01550 01551 01552 01553 01554 01555 01556 01557 01558 01559 01560 01561 01562 01563 01564 01565 01566 01567 01568 01569 01570 01571 01572 01573 01574 01575 01576 01577 01578 01579 01580 01581 01582 01583 01584 01585 01586 01587 01588 01589 01590 01591 01592 01593 01594 01595 01596 01597 01598 01599 01600 01601 01602 01603 01604 01605 01606 01607 01608 01609 01610 01611 01612 01613 01614 01615 01616 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device M0960 M0961 M0962 M0963 M0964 M0965 M0966 M0967 M0968 M0969 M0970 M0971 M0972 M0973 M0974 M0975 M0976 M0977 M0978 M0979 M0980 M0981 M0982 M0983 M0984 M0985 M0986 M0987 M0988 M0989 M0990 M0991 M0992 M0993 M0994 M0995 M0996 M0997 M0998 M0999 M1000 M1001 M1002 M1003 M1004 M1005 M1006 M1007 M1008 M1009 M1010 M1011 M1012 M1013 M1014 M1015 M1016 M1017 M1018 M1019 M1020 M1021 M1022 M1023 L1024 L1025 L1026 L1027 L1028 L1029 L1030 L1031 L1032 L1033 L1034 L1035 L1036 L1037 L1038 L1039 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Always ON Only The First Scan ON Zero Point Five Second Cycle Clock One Second Cycle Clock Two Seconds Cycle Clock Date Change Pulse Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Note

Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched

- 225 -

QT108300

(continued)
Coil Number 01617 01618 01619 01620 01621 01622 01623 01624 01625 01626 01627 01628 01629 01630 01631 01632 01633 01634 01635 01636 01637 01638 01639 01640 01641 01642 01643 01644 01645 01646 01647 01648 01649 01650 01651 01652 01653 01654 01655 01656 01657 01658 01659 01660 01661 01662 01663 01664 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1040 L1041 L1042 L1043 L1044 L1045 L1046 L1047 L1048 L1049 L1050 L1051 L1052 L1053 L1054 L1055 L1056 L1057 L1058 L1059 L1060 L1061 L1062 L1063 L1064 L1065 L1066 L1067 L1068 L1069 L1070 L1071 L1072 L1073 L1074 L1075 L1076 L1077 L1078 L1079 L1080 L1081 L1082 L1083 L1084 L1085 L1086 L1087 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 226 -

QT108300

Coils number 01665 to 01792(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 01665 01666 01667 01668 01669 01670 01671 01672 01673 01674 01675 01676 01677 01678 01679 01680 01681 01682 01683 01684 01685 01686 01687 01688 01689 01690 01691 01692 01693 01694 01695 01696 01697 01698 01699 01700 01701 01702 01703 01704 01705 01706 01707 01708 01709 01710 01711 01712 01713 01714 01715 01716 01717 01718 01719 01720 01721 01722 01723 01724 01725 01726 01727 01728 01729 01730 01731 01732 01733 01734 01735 01736 01737 01738 01739 01740 01741 01742 01743 01744 01745 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1088 L1089 L1090 L1091 L1092 L1093 L1094 L1095 L1096 L1097 L1098 L1099 L1100 L1101 L1102 L1103 L1104 L1105 L1106 L1107 L1108 L1109 L1110 L1111 L1112 L1113 L1114 L1115 L1116 L1117 L1118 L1119 L1120 L1121 L1122 L1123 L1124 L1125 L1126 L1127 L1128 L1129 L1130 L1131 L1132 L1133 L1134 L1135 L1136 L1137 L1138 L1139 L1140 L1141 L1142 L1143 L1144 L1145 L1146 L1147 L1148 L1149 L1150 L1151 L1152 L1153 L1154 L1155 L1156 L1157 L1158 L1159 L1160 L1161 L1162 L1163 L1164 L1165 L1166 L1167 L1168 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 227 -

QT108300

(continued)
Coil Number 01746 01747 01748 01749 01750 01751 01752 01753 01754 01755 01756 01757 01758 01759 01760 01761 01762 01763 01764 01765 01766 01767 01768 01769 01770 01771 01772 01773 01774 01775 01776 01777 01778 01779 01780 01781 01782 01783 01784 01785 01786 01787 01788 01789 01790 01791 01792 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1169 L1170 L1171 L1172 L1173 L1174 L1175 L1176 L1177 L1178 L1179 L1180 L1181 L1182 L1183 L1184 L1185 L1186 L1187 L1188 L1189 L1190 L1191 L1192 L1193 L1194 L1195 L1196 L1197 L1198 L1199 L1200 L1201 L1202 L1203 L1204 L1205 L1206 L1207 L1208 L1209 L1210 L1211 L1212 L1213 L1214 L1215 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 228 -

QT108300

Coils number 01793 to 01920(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 01793 01794 01795 01796 01797 01798 01799 01800 01801 01802 01803 01804 01805 01806 01807 01808 01809 01810 01811 01812 01813 01814 01815 01816 01817 01818 01819 01820 01821 01822 01823 01824 01825 01826 01827 01828 01829 01830 01831 01832 01833 01834 01835 01836 01837 01838 01839 01840 01841 01842 01843 01844 01845 01846 01847 01848 01849 01850 01851 01852 01853 01854 01855 01856 01857 01858 01859 01860 01861 01862 01863 01864 01865 01866 01867 01868 01869 01870 01871 01872 01873 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1216 L1217 L1218 L1219 L1220 L1221 L1222 L1223 L1224 L1225 L1226 L1227 L1228 L1229 L1230 L1231 L1232 L1233 L1234 L1235 L1236 L1237 L1238 L1239 L1240 L1241 L1242 L1243 L1244 L1245 L1246 L1247 L1248 L1249 L1250 L1251 L1252 L1253 L1254 L1255 L1256 L1257 L1258 L1259 L1260 L1261 L1262 L1263 L1264 L1265 L1266 L1267 L1268 L1269 L1270 L1271 L1272 L1273 L1274 L1275 L1276 L1277 L1278 L1279 L1280 L1281 L1282 L1283 L1284 L1285 L1286 L1287 L1288 L1289 L1290 L1291 L1292 L1293 L1294 L1295 L1296 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 229 -

QT108300

(continued)
Coil Number 01874 01875 01876 01877 01878 01879 01880 01881 01882 01883 01884 01885 01886 01887 01888 01889 01890 01891 01892 01893 01894 01895 01896 01897 01898 01899 01900 01901 01902 01903 01904 01905 01906 01907 01908 01909 01910 01911 01912 01913 01914 01915 01916 01917 01918 01919 01920 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1297 L1298 L1299 L1300 L1301 L1302 L1303 L1304 L1305 L1306 L1307 L1308 L1309 L1310 L1311 L1312 L1313 L1314 L1315 L1316 L1317 L1318 L1319 L1320 L1321 L1322 L1323 L1324 L1325 L1326 L1327 L1328 L1329 L1330 L1331 L1332 L1333 L1334 L1335 L1336 L1337 L1338 L1339 L1340 L1341 L1342 L1343 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 230 -

QT108300

Coils number 01921 to 02048(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 01921 01922 01923 01924 01925 01926 01927 01928 01929 01930 01931 01932 01933 01934 01935 01936 01937 01938 01939 01940 01941 01942 01943 01944 01945 01946 01947 01948 01949 01950 01951 01952 01953 01954 01955 01956 01957 01958 01959 01960 01961 01962 01963 01964 01965 01966 01967 01968 01969 01970 01971 01972 01973 01974 01975 01976 01977 01978 01979 01980 01981 01982 01983 01984 01985 01986 01987 01988 01989 01990 01991 01992 01993 01994 01995 01996 01997 01998 01999 02000 02001 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1344 L1345 L1346 L1347 L1348 L1349 L1350 L1351 L1352 L1353 L1354 L1355 L1356 L1357 L1358 L1359 L1360 L1361 L1362 L1363 L1364 L1365 L1366 L1367 L1368 L1369 L1370 L1371 L1372 L1373 L1374 L1375 L1376 L1377 L1378 L1379 L1380 L1381 L1382 L1383 L1384 L1385 L1386 L1387 L1388 L1389 L1390 L1391 L1392 L1393 L1394 L1395 L1396 L1397 L1398 L1399 L1400 L1401 L1402 L1403 L1404 L1405 L1406 L1407 L1408 L1409 L1410 L1411 L1412 L1413 L1414 L1415 L1416 L1417 L1418 L1419 L1420 L1421 L1422 L1423 L1424 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 231 -

QT108300

(continued)
Coil Number 02002 02003 02004 02005 02006 02007 02008 02009 02010 02011 02012 02013 02014 02015 02016 02017 02018 02019 02020 02021 02022 02023 02024 02025 02026 02027 02028 02029 02030 02031 02032 02033 02034 02035 02036 02037 02038 02039 02040 02041 02042 02043 02044 02045 02046 02047 02048 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1425 L1426 L1427 L1428 L1429 L1430 L1431 L1432 L1433 L1434 L1435 L1436 L1437 L1438 L1439 L1440 L1441 L1442 L1443 L1444 L1445 L1446 L1447 L1448 L1449 L1450 L1451 L1452 L1453 L1454 L1455 L1456 L1457 L1458 L1459 L1460 L1461 L1462 L1463 L1464 L1465 L1466 L1467 L1468 L1469 L1470 L1471 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 232 -

QT108300

Coils number 02049 to 02176(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 02049 02050 02051 02052 02053 02054 02055 02056 02057 02058 02059 02060 02061 02062 02063 02064 02065 02066 02067 02068 02069 02070 02071 02072 02073 02074 02075 02076 02077 02078 02079 02080 02081 02082 02083 02084 02085 02086 02087 02088 02089 02090 02091 02092 02093 02094 02095 02096 02097 02098 02099 02100 02101 02102 02103 02104 02105 02106 02107 02108 02109 02110 02111 02112 02113 02114 02115 02116 02117 02118 02119 02120 02121 02122 02123 02124 02125 02126 02127 02128 02129 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1472 L1473 L1474 L1475 L1476 L1477 L1478 L1479 L1480 L1481 L1482 L1483 L1484 L1485 L1486 L1487 L1488 L1489 L1490 L1491 L1492 L1493 L1494 L1495 L1496 L1497 L1498 L1499 L1500 L1501 L1502 L1503 L1504 L1505 L1506 L1507 L1508 L1509 L1510 L1511 L1512 L1513 L1514 L1515 L1516 L1517 L1518 L1519 L1520 L1521 L1522 L1523 L1524 L1525 L1526 L1527 L1528 L1529 L1530 L1531 L1532 L1533 L1534 L1535 L1536 L1537 L1538 L1539 L1540 L1541 L1542 L1543 L1544 L1545 L1546 L1547 L1548 L1549 L1550 L1551 L1552 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 233 -

QT108300

(continued)
Coil Number 02130 02131 02132 02133 02134 02135 02136 02137 02138 02139 02140 02141 02142 02143 02144 02145 02146 02147 02148 02149 02150 02151 02152 02153 02154 02155 02156 02157 02158 02159 02160 02161 02162 02163 02164 02165 02166 02167 02168 02169 02170 02171 02172 02173 02174 02175 02176 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1553 L1554 L1555 L1556 L1557 L1558 L1559 L1560 L1561 L1562 L1563 L1564 L1565 L1566 L1567 L1568 L1569 L1570 L1571 L1572 L1573 L1574 L1575 L1576 L1577 L1578 L1579 L1580 L1581 L1582 L1583 L1584 L1585 L1586 L1587 L1588 L1589 L1590 L1591 L1592 L1593 L1594 L1595 L1596 L1597 L1598 L1599 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 234 -

QT108300

Coils number 02177 to 02304(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 02177 02178 02179 02180 02181 02182 02183 02184 02185 02186 02187 02188 02189 02190 02191 02192 02193 02194 02195 02196 02197 02198 02199 02200 02201 02202 02203 02204 02205 02206 02207 02208 02209 02210 02211 02212 02213 02214 02215 02216 02217 02218 02219 02220 02221 02222 02223 02224 02225 02226 02227 02228 02229 02230 02231 02232 02233 02234 02235 02236 02237 02238 02239 02240 02241 02242 02243 02244 02245 02246 02247 02248 02249 02250 02251 02252 02253 02254 02255 02256 02257 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1600 L1601 L1602 L1603 L1604 L1605 L1606 L1607 L1608 L1609 L1610 L1611 L1612 L1613 L1614 L1615 L1616 L1617 L1618 L1619 L1620 L1621 L1622 L1623 L1624 L1625 L1626 L1627 L1628 L1629 L1630 L1631 L1632 L1633 L1634 L1635 L1636 L1637 L1638 L1639 L1640 L1641 L1642 L1643 L1644 L1645 L1646 L1647 L1648 L1649 L1650 L1651 L1652 L1653 L1654 L1655 L1656 L1657 L1658 L1659 L1660 L1661 L1662 L1663 L1664 L1665 L1666 L1667 L1668 L1669 L1670 L1671 L1672 L1673 L1674 L1675 L1676 L1677 L1678 L1679 L1680 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 235 -

QT108300

(continued)
Coil Number 02258 02259 02260 02261 02262 02263 02264 02265 02266 02267 02268 02269 02270 02271 02272 02273 02274 02275 02276 02277 02278 02279 02280 02281 02282 02283 02284 02285 02286 02287 02288 02289 02290 02291 02292 02293 02294 02295 02296 02297 02298 02299 02300 02301 02302 02303 02304 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1681 L1682 L1683 L1684 L1685 L1686 L1687 L1688 L1689 L1690 L1691 L1692 L1693 L1694 L1695 L1696 L1697 L1698 L1699 L1700 L1701 L1702 L1703 L1704 L1705 L1706 L1707 L1708 L1709 L1710 L1711 L1712 L1713 L1714 L1715 L1716 L1717 L1718 L1719 L1720 L1721 L1722 L1723 L1724 L1725 L1726 L1727 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 236 -

QT108300

Coils number 02305 to 02432(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 02305 02306 02307 02308 02309 02310 02311 02312 02313 02314 02315 02316 02317 02318 02319 02320 02321 02322 02323 02324 02325 02326 02327 02328 02329 02330 02331 02332 02333 02334 02335 02336 02337 02338 02339 02340 02341 02342 02343 02344 02345 02346 02347 02348 02349 02350 02351 02352 02353 02354 02355 02356 02357 02358 02359 02360 02361 02362 02363 02364 02365 02366 02367 02368 02369 02370 02371 02372 02373 02374 02375 02376 02377 02378 02379 02380 02381 02382 02383 02384 02385 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1728 L1729 L1730 L1731 L1732 L1733 L1734 L1735 L1736 L1737 L1738 L1739 L1740 L1741 L1742 L1743 L1744 L1745 L1746 L1747 L1748 L1749 L1750 L1751 L1752 L1753 L1754 L1755 L1756 L1757 L1758 L1759 L1760 L1761 L1762 L1763 L1764 L1765 L1766 L1767 L1768 L1769 L1770 L1771 L1772 L1773 L1774 L1775 L1776 L1777 L1778 L1779 L1780 L1781 L1782 L1783 L1784 L1785 L1786 L1787 L1788 L1789 L1790 L1791 L1792 L1793 L1794 L1795 L1796 L1797 L1798 L1799 L1800 L1801 L1802 L1803 L1804 L1805 L1806 L1807 L1808 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 237 -

QT108300

(continued)
Coil Number 02386 02387 02388 02389 02390 02391 02392 02393 02394 02395 02396 02397 02398 02399 02400 02401 02402 02403 02404 02405 02406 02407 02408 02409 02410 02411 02412 02413 02414 02415 02416 02417 02418 02419 02420 02421 02422 02423 02424 02425 02426 02427 02428 02429 02430 02431 02432 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1809 L1810 L1811 L1812 L1813 L1814 L1815 L1816 L1817 L1818 L1819 L1820 L1821 L1822 L1823 L1824 L1825 L1826 L1827 L1828 L1829 L1830 L1831 L1832 L1833 L1834 L1835 L1836 L1837 L1838 L1839 L1840 L1841 L1842 L1843 L1844 L1845 L1846 L1847 L1848 L1849 L1850 L1851 L1852 L1853 L1854 L1855 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 238 -

QT108300

Coils number 02433 to 02560(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 02433 02434 02435 02436 02437 02438 02439 02440 02441 02442 02443 02444 02445 02446 02447 02448 02449 02450 02451 02452 02453 02454 02455 02456 02457 02458 02459 02460 02461 02462 02463 02464 02465 02466 02467 02468 02469 02470 02471 02472 02473 02474 02475 02476 02477 02478 02479 02480 02481 02482 02483 02484 02485 02486 02487 02488 02489 02490 02491 02492 02493 02494 02495 02496 02497 02498 02499 02500 02501 02502 02503 02504 02505 02506 02507 02508 02509 02510 02511 02512 02513 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1856 L1857 L1858 L1859 L1860 L1861 L1862 L1863 L1864 L1865 L1866 L1867 L1868 L1869 L1870 L1871 L1872 L1873 L1874 L1875 L1876 L1877 L1878 L1879 L1880 L1881 L1882 L1883 L1884 L1885 L1886 L1887 L1888 L1889 L1890 L1891 L1892 L1893 L1894 L1895 L1896 L1897 L1898 L1899 L1900 L1901 L1902 L1903 L1904 L1905 L1906 L1907 L1908 L1909 L1910 L1911 L1912 L1913 L1914 L1915 L1916 L1917 L1918 L1919 L1920 L1921 L1922 L1923 L1924 L1925 L1926 L1927 L1928 L1929 L1930 L1931 L1932 L1933 L1934 L1935 L1936 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 239 -

QT108300

(continued)
Coil Number 02514 02515 02516 02517 02518 02519 02520 02521 02522 02523 02524 02525 02526 02527 02528 02529 02530 02531 02532 02533 02534 02535 02536 02537 02538 02539 02540 02541 02542 02543 02544 02545 02546 02547 02548 02549 02550 02551 02552 02553 02554 02555 02556 02557 02558 02559 02560 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1937 L1938 L1939 L1940 L1941 L1942 L1943 L1944 L1945 L1946 L1947 L1948 L1949 L1950 L1951 L1952 L1953 L1954 L1955 L1956 L1957 L1958 L1959 L1960 L1961 L1962 L1963 L1964 L1965 L1966 L1967 L1968 L1969 L1970 L1971 L1972 L1973 L1974 L1975 L1976 L1977 L1978 L1979 L1980 L1981 L1982 L1983 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 240 -

QT108300

Coils number 02561 to 02624(Internal Bit Device can be monitored on F7: DIAGNOSTIC>9.READ BIT.)
Coil Number 02561 02562 02563 02564 02565 02566 02567 02568 02569 02570 02571 02572 02573 02574 02575 02576 02577 02578 02579 02580 02581 02582 02583 02584 02585 02586 02587 02588 02589 02590 02591 02592 02593 02594 02595 02596 02597 02598 02599 02600 02601 02602 02603 02604 02605 02606 02607 02608 02609 02610 02611 02612 02613 02614 02615 02616 02617 02618 02619 02620 02621 02622 02623 02624 Attribute Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Internal Bit Device L1984 L1985 L1986 L1987 L1988 L1989 L1990 L1991 L1992 L1993 L1994 L1995 L1996 L1997 L1998 L1999 L2000 L2001 L2002 L2003 L2004 L2005 L2006 L2007 L2008 L2009 L2010 L2011 L2012 L2013 L2014 L2015 L2016 L2017 L2018 L2019 L2020 L2021 L2022 L2023 L2024 L2025 L2026 L2027 L2028 L2029 L2030 L2031 L2032 L2033 L2034 L2035 L2036 L2037 L2038 L2039 L2040 L2041 L2042 L2043 L2044 L2045 L2046 L2047 Name Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Category Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Pseudo Relay Sub Category Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Note

- 241 -

QT108300

List of Replaceable Parts


Parts Name CP4 CPU Board Assembly CP4 Analog Input Board Assembly-1 CP4 Analog Input Board Assembly-2 CP4 UV-EPROM Board Assembly CP4 LCD Interface Board Assembly CP4 KeyPad Board Assembly CP4 Extension Digital Input/Output Base Board Assembly CP4 Extension A/D Converter Board Assembly CP4 Extension Communication Board Assembly CP4 Extension Analog Output Board Assembly CP4 Digital I/O Board(10 Output/6 Input) Assembly CP4 Digital Input/Output 4ch. Driver Board Assembly CP4 Digital Input/Output 4ch. Driver Board Assembly CP4 Digital Output 2ch./Digital Input 2ch. Driver Board Assembly CP4 Ext. Digital Input/Output Board(14 Output/2 Input) Assembly CP4 PR01/J21-DB01/J12 DC Cable Harness CP4 PR01/J22-AD01/J2 DC Cable Harness CP4 PR01/J4-RS01/J2 DC Cable Harness CP4 DC12V-LI01/J2 PR01/J1 DC Cable Harness CP4 DC12V 24V-PR01/J5 DA01/J2 DC Cable Harness CP4 DC24V-AI01/J2 DC Cable Harness CP4 AI11/J2-AI01/J2 DC Cable Harness CP4 LI01-PR01/J3 Cable Harness, Ribbon CP4 KP01-PR01/J10 Cable Harness, Ribbon CP4 PR01-AI01/AI11 Cable Harness, Ribbon CP4 PR01- DIO Cable Harness, Ribbon CP4 LI01-LCD Inverter Cable Harness CP4 LI01-LCD Signal Cable Harness CP4 LCD Panel CP4 LCD Inverter Noise Filter CP4 Lamp Holder Set for LCD CP4 Front Panel CP4 Main Chassis CP4 LCD Chassis CP4 Gasket (Right and Left) CP4 Gasket (Top and Bottom) CP4 Thumb Screw (4pcs) CP4 Overlay (Embossed) CP4 Acrylic Resin Window Mechanical Relay for Digital Input/Output Board Solid State Relay for Digital Input/Output Board Battery for CPU Board CP4 ROM Model REF-CX100-PR01 REF-CX100-AI01 REF-CX100-AI11 REF-CX100-RM01 REF-CX100-LI01 REF-CX100-KP01 REF-CX100-DB01 REF-CX100-AD01 REF-CX100-RS01 REF-CX100-DA01 REF-MCS200-OIA0 REF-MCS200-SO3 REF-MCS200-SI3 REF-MCS200-SC23 REF-MCS200-OIE0 REF-CX100-C0100-U REF-CX100-C0100-U REF-CX100-C0100-U REF-CX100-C0312-U REF-CX100-C0322-U REF-CX100-C0401-U REF-CX100-C0501-U REF-CX100-C0901-U REF-CX100-C1000-U REF-CX100-C1201-U REF-CX100-C1301-U REF-CX100-C1401-U REF-CX100-C1501-U NL6448BC33-59 104PW191 NAC-06-472-D 104LHS43 Front Panel 294-22-1 Main Chassis 294-22-4 LCD Chassis 294-22-5 CR Gasket 400x9xt3 CR Gasket 378x9xt3 A176-S-6 CP4 LEXAN8B35 CG(P) 223x169xt2 G6B-1114P-US, DC12V G3S-201PL-PD-US, DC12V CR2032 CP4 ROM-U mAYEKAWA Code No. EAD-02000 EAD-02001 EAD-02002 EAD-02003 EAD-02004 EAD-02005 EAD-02006 EAD-02007 EAD-02008 EAD-02009 EAD-02010 EAD-02011 EAD-02012 EAD-02013 EAD-02014 EAD-02020 EAD-02021 EAD-02022 EAD-02023 EAD-02024 EAD-02025 EAD-02026 EAD-02027 EAD-02028 EAD-02029 EAD-02030 EAD-02031 EAD-02032 EAD-02040 EAD-02041 EAD-02103 EAD-02043 EAD-02050 EAD-02051 EAD-02052 EAD-02053 EAD-02054 EAD-02055 EAD-02056 EAD-02057 EAD-02060 EAD-02061 EAD-02062 EAD-02063

Components other than the above are not available as replacement parts.

- 242 -

QT108300

Software Revision Record 1


Software Version Ver.0.98 Ver.0.99 Ver.100.100 Ver.102.101 Ver.102.102 Ver.103.103 (Ver.104.104) Ver.104.105 Ver.105.106 Ver.106.107 Ver.106.108 (Ver.106.109) Ver.107.109 Ver.107.110 Ver.108.111 Ver.109.112 Ver.110.113 Ver.110.114 Ver.111.115 Ver.112.115 Ver.113.116 Ver.113.117 Ver.114.118 Ver.115.119 Ver.116.120 Ver.117.121 Ver.118.121 Ver.119.122 Ver.120.122 Ver.121.123 Ver.122.124 Ver.123.125 Ver.123.126 Ver.124.128 Ver.125.129 Ver.125.130 Ver.126.131 Ver.127.131 Date 2005.09.15 2005.10.27 2005.11.25 2005.12.14 2005.12.24 2006.01.31 (2006.02) 2006.02.21 2006.02.22 2006.03.03 2006.03.15 (2006.03) 2006.04.07 2006.05.02 2006.05.25 2006.07.03 2006.08.04 2006.08.31 2006.09.27 2006.10.06 2006.10.10 2006.10.10 2006.12.13 2006.12.22 2007.02.02 2007.02.15 2007.02.16 2007.02.28 2007.03.02 2007.03.13 2007.03.27 2007.04.06 2007.05.17 2007.08.10 2007.08.29 2007.09.27 2007.11.08 2008.02.20 Revision First edition Internal timer added Auto-Vi added, Password Level changed, and version expression method changed VFD Control changed, and communication negative pressure expression corrected Refrigerant (R290 Propane) added Graphics added, and problems in selection of Economizer w/o Sensor corrected Auto Reset at change of ANALOG INPUT SCALING added, and RTC operation changed, etc. AUTO STAGE function corrected, etc. CONDENSER CONTROL function corrected, etc. Display problems corrected, etc. Password changed, and graphics changed, etc. Refrigerant (R744 CO2) added, graphic colors added, 400 series supported, cache used etc. OPTION ANALOG INPUT added, initial values changed, ALARM backlight ON added etc. COM0 MODEM support function added, No PUMP OUT added etc. Capacity control by communication, time change, and CLEAR ALARM functions added etc. Modified so that optional analog input can be assigned dynamically, etc. Modified so that D/O TEST OPERATION can output Comp. Run (Y0), [STOP] key operation changed, etc. WDT operation at initialization changed, etc. TREND LOG format added, 2-path chiller control supported, OVER RANGE added, etc. Modified so that no capacity control command is issued during Vi operation AUTO-Vi operation and device corrected, etc. COMMUNICATION PROTOCOL display corrected AUTO-Vi operation, CONDENSER CONTROL option names, and AUTO STAGE prioritization method changed, etc. CONDENSER VFD CONTROL option names changed, set point switchover added, etc. CHILLER PUMP MODE NOT USE supported, mask time at start of overcurrent changed (60 sec), etc. MVH during VFD control limiter operation added, etc. Incorrect MV values during VFD COMPRESSOR limiter operation corrected Intermediate pressure control modified Intermediate pressure control modified, and limiter added COMPOUND-2 ECONOMIZER/INTER COOLER liquid supply SV control changed to intermediate pressure and high-stage capacity The need for pressing the [START] key after reset in OPERATION AUTO mode eliminated AUTO-Vi SLIDE ALARM added Absolute pressure conversion at psi display selection corrected SINGLE J1 support added (Ver. XXX.127 unpublicized) Countermeasures for [STOP] key used to stop AUTO STAGE MASTER station added The problem that programs cannot be started when the SRAM content is undefined corrected Level regulator added, and DEAD BAND setting item added to capacity control PID regulator Specifications modified to prevent the ANTI CYCLE timer from being reset when the CPU is reset The problem that MV is fixed to 0% when EXPASION VALVES CONTROL is SH ONLY corrected This problem occurs in VERSION 125.130 and 126.131. Control of two oil pumps added Specifications modified so that TOTAL RUN TIME and PASSWORD initialization is not performed by SPECIAL BOOT[1] REMOTE CAPACITY CONTROL:DIGITAL control added to VFD COMPRESSOR:USE Positioner malfunction corrected Assignment of initialization keys [1] to [4] on the SPECIAL BOOT initial screen changed

Ver.128.132 Ver.129.133 Ver.129.134

2008.03.27 2008.04.10 2008.04.14

- 243 -

QT108300 Software Version Ver.130.135 Ver.130.136 Ver.130.137 Ver.130.138 Ver.132.140 Ver.132.141 Date 2008.06.26 2008.07.14 2008.07.17 2008.07.17 2008.11.07 2008.11.14 Revision Capacity and VFD COMPRESSOR SV write problems corrected AUTO STAGE capacity and VFD COMPRESSOR regulator PV switching failure corrected The problem that FM160 can be selected in F6:SETUP>1.SYSTEM SETUP>COMPRESSOR corrected Programs modified so that SYSTEM SUCTION PRESSURE can be selected in TARGET (CAPACITY CONTROL) HIGH ST ALARM/FAILURE added (Ver. 131.139 is unpublicized.) DEAD BAND setup added to all PID regulators

Software Revision Record 2


Software Version Ver.132.142 Ver.133.143 Ver.134.144 Ver.135.145 Ver.135.146 Ver.136.147 Ver.136.148 Ver.137.149 Ver.138.150 Ver.139.151 Ver.140.151 Ver.141.152 Ver.142.153 Date 2008.12.11 2009.04.14 2009.05.08 2009.07.02 2009.07.28 2009.08.27 2009.09.15 2009.10.01 2009.12.28 2010.01.29 2010.02.02 2010.03.09 2010.05.10 Revision PID regulator MV 0% write at occurrence of FAILURE stopped (for CONDENSER FAN control) 170J supported Problem caused when PRE LUB is selected in COMPOUND-2 (2016 & HIGHER) collected FM160 supported Indicator, F4:LOGS>SHIFT1.TREND GRAPH, SHIFT2.GRAPH ASSIGNMENT added Portuguese and Spanish added for display In PARTIAL LUBE J series, LOW OP alarms during oil pump operation disabled Russian added for display HIGH & LOW added to OPTION ANALOG INPUT ALARM/FAILURE SYSTEM DISCHARGE PRESSURE added to slide valve capacity control targets CUT IN/OUT: SYSTEM SUCTION PRESSURE to COMPRESSOR: SINGLE J German added for display, and Portuguese display corrected COMPUND-2 START FAILURE and OIL DRAIN SV operation in NORTH AMERICA modified COMPUND-2 RE-START ALARM and OIL DRAIN SV operation in NORTH AMERICA modified Failure to implement auto recovery from AUTO STAGE communication error corrected Occurrence of OP LOW FAILURE when COMPRESSOR is J and PARTIAL LUBE is selected eliminated Countermeasures of INTERMEDIATE PRESSURE UNDER RANGE FAILURE caused when 0.05 MPa or less during operation Slide valve position indicator lower-stage/high-stage position selection function added

- 244 -

Instruction Manual Revision Record


DateVersion First EditionMarch XX, 2011First edition (for Version 142.153)

INSTRUCTION MANUAL FOR SCREW COMPRESSOR UNIT CONTROLLER MYPRO-CPIV


March XX, 2011First edition

Corporate office: 3-14-15, Botan, Koto-ku, Tokyo 135-8482, Japan Moriya Plant: 2000, Tatsuzawa, Moriya-shi, Ibaraki-ken 302-0118, Japan URL: http://www.mayekawa.com

Tel: +81-3-3642-8181 Fax: +81-3-3643-7094 Tel: +81-297-48-1593 Fax: +81-297-45-2781

Mayekawa Mfg. Co., Ltd. Reserves the right to change design and specifications.

Vous aimerez peut-être aussi