Vous êtes sur la page 1sur 1

Southwire Company

NEXTERA ENERGY RESOURCES LLC


MAMMOTH PLAINS
795 DRAKE ACSR
Conductor:

3 # 8 Alumoweld

Area = 0.0389 Sq. in


Diameter = 0.277 in
Data from Chart No. 1-1218
English Units
Limits and Outputs in Average Tensions.
Span = 1000.0 Feet
Creep is NOT a Factor
Design Points
Temp
Ice
Wind
F
in
psf
0.0
0.50
4.00
32.0
0.50
0.00
32.0
1.00R
0.00
60.0
0.00
21.00
60.0
0.00
6.00
-20.0
0.00
0.00
0.0
0.00
0.00
30.0
0.00
0.00
60.0
0.00
0.00
90.0
0.00
0.00
120.0
0.00
0.00
167.0
0.00
0.00
212.0
0.00
0.00
* Design Condition
R

Weight = 0.112 lb/ft

RTS = 7206 lb

Special Load Zone

K
lb/ft
0.30
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Rime Ice/Wet Snow Density of

Weight
lb/ft
1.032
0.595
1.226
0.498
0.178
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112

Sag
Ft
39.57
34.48
42.46
33.68
26.65
20.67
21.65
23.09
24.49
25.85
27.18
29.18
31.01

Final
Tension
lb
3279
2168
3637
1855
838
678
648
608
573
543
517
481
453

Initial
Tension
lb
3315*
2270
3637
1961
948
830
785
726
675
632
595
546
508

Sag
Ft
39.14
32.92
42.46
31.84
23.55
16.88
17.85
19.31
20.76
22.19
23.59
25.71
27.66

40.0 lb/ft^3

Certain information such as the data, opinions or recommendations set


forth herein or given by Southwire representatives, is intended as a general
guide only. Each installation of overhead electrical conductor,
underground electrical conductor, and/or conductor accessories involves
special conditions creating problems that require individual solutions
and, therefore, the recipient of this information has the sole
responsibility in connection with the use of the information. Southwire does
not assume any liability in connection with such information.