Vous êtes sur la page 1sur 1

Multicore PVC-Insulated Cables (Non Armoured, Copper Conductors)

6242Y to BS 6004
6243Y to BS 6346
Ambient temperature: 30
o
C
Conductor operating temperature: 70
o
C
PVC Cables
CURRENT - CARRYING CAPACITY (Amperes)
PVC Singles
6491X to BS6004
PVC Flexes BUTYL
CURRENT - CARRYING CAPACITY (Amperes)
BS 6141
BS 6500
CURRENT - CARRYING CAPACITY (Amperes) BS 6883
Ambient temperature: 30C Conductor operating temperature: 70C
Reference method
Clipped direct
1 Two-core cable
single phase AC or DC
1 Three-core cable
or 1 Four-core cable
three phase AC
1 Two-core cable
single phase AC or DC
1 Three-core cable
or 1 four-core cable,
three phase AC
CURRENT - CARRYING CAPACITY (Amperes)
Reference method
Enclosed in an insulated
wall etc.
Conductor
cross-sectional area
Reference method
Enclosed in conduit on a wall or ceiling or in trunking
mm
2
1.0
1.5
2.5
4.0
6.0
10.0
16.0
25.0
35.0
50.0
70.0
95.0
120.0
150.0
185.0
240.0
300.0
A
10
13
17.5
23
29
39
52
68
83
99
125
150
172
196
223
261
298
A
13
16.5
23
30
38
52
69
90
111
133
168
201
232
258
294
344
394
A
11.5
15
20
27
34
46
62
80
99
118
149
179
206
225
255
297
339
A
15
19.5
27
36
46
63
85
112
138
168
213
258
299
344
392
461
530
Size
Conductor
cross-sectional area
Reference method
Enclosed in
conduit or trunking surface
Reference method
Enclosed in conduit or trunking
Buried in thermally insulated wall
mm
2
1.5
2.5
4.0
6.0
10.0
16.0
25.0
35.0
50.0
70.0
95.0
120.0
A
17
24
32
41
57
76
101
125
151
192
232
269
A
14
19
26
34
46
61
80
99
119
151
182
210
A
13
18
24
31
42
56
73
89
108
136
164
188
S/Phase AC S/Phase AC T/Phase AC
Conductor
cross-sectional area
Conductor
cross-sectional
area
Single Phase AC Three Phase AC
mm
2
0.5
0.75
1.0
1.25
1.5
2.5
4.0
A
3
6
10
13
16
25
32
A
3
6
10
-
16
20
25
Conductor
cross-sectional
area
Reference method
enclosed in conduit or trunking
1 Three or four-core cable
three-phase AC
1 Two-core
cable single
phase AC or
DC
mm
2
1.0
1.5
2.5
4.0
6.0
A
14.5
18.5
25
33
43
A
18
23
32
43
55
Reference method
clipped direct
A
16
20
28
37
48
1 Three or
four-core
cable three-
phase AC
WA R N I N G
Current ratings are
dependent on the
type of installation
and those shown
are for guidance
only. For precise
cable ratings
for a parti cul ar
installation refer to
the current edition
of the IEE Wiring
Regulations.
No liability can be accepted for the data below which is given for guidance only.

Vous aimerez peut-être aussi