BATTERY CAPACITY CALCULATIONS ( 2V Standby range)

Example

Considerations :
System rating : 200 KVA
Inverter efficiency : 96 %
*No of cells : 192 nos. ( 384V DC bus voltage)
End cell voltage : 1.75 VPC ,ie., 336 V
Back up required : 30 mins
Operating temp. : 15 DegC
Load pattern : Constant

* In typical cases, the no. of cells can be arrived at


by dividing the max charger voltage / max. recommended float voltage.

Capacity calculation for VRLA type (NMST) 2 V cells:


Max. discharge Current = KVA(UPS rating) X 1000 X power factor
ECV X Inverter Efficiency X No of cells
=

200 X 1000 X 0.8


1.75 X 0.96 X 192
= 496 Amps
Capacty factor for 30mins backup to ECV of 1.75 Volts = 1.389 ( from capacity factor table )
Hence Calculated capacity = 496 X 1.389
= 689 AH
Final Capacity =((Calculated capacity) x Kt x KD)/A.F
where Kt = Temperature correction factor
KD = Design margin
A.F = ageing factor
Kt = 1 + ((27 - op.temp) x CT)/100, where CT is temperature correction factor at C-10, which is 0.43 for standby range
KD = Design Margin (minimum of 10%)
A.F = Ageing factor of 0.8 ( For Plante' , this is 1)
Hence final capacity = (689 x (1+(12x0.43)/100) x 1.1) / 0.8
= 996.26 Ah
NMST 1000Ah capacity can be recommended

Capacity calculation for Tubular type 2 V cells:


Max discharge current remains same as above , i.e., 496 Amps
Capacity factor for 30 mins back up to 1.75 end cell voltage = 1.46 (refer capacity factor table)
Calculated capacity= 496 X 1.46
= 724 Ah approx.
The Final capacity can eb derived the same way mentioned above by
applying temperature correction, design margin & ageing factor.

Capacity calculation for Plante type 2 V cells:


Again the max discharge current is 496 Amps.
Capacity factor for 30 minutes (refer capacity factor table) is 1.16
Hence calculated capacity = 496 X 1.16 = 575 Ah
The Final capacity can eb derived the same way mentioned above by
applying temperature correction, design margin , except that the ageing factor.
for plante' should be considered as 1.

at voltage.

BATTERY CAPACITY CALCULATIONS ( 12V monobloc range)


Example

Considerations :
System rating : 20 KVA
Inverter efficiency : 96 %
No of cells : 192 nos( 384V DC bus voltage)
End cell voltage : 1.70 VPC
Back up required : 1 hr
Load pattern : Constant

Capacity calculation for VRLA 12 V monobloc (EP - Powersafe):


Max. discharge Current = KVA(UPS rating) X 1000 X power factor
ECV X Inverter Efficiency X No of cells
=

20 X 1000 X 0.8
1.70 X 0.96 X 192
= 51.06 Amps
Capacty factor for 1 hr backup to ECV of 1.70 Volts = 1.49 ( from capacity factor table )
So Capacity required

= 51.06 X 1.49
= 76.08 Ah

HENCE EP80-12 CAN BE RECOMMENDED

Capacity calculation for vented type 12 V monobloc (EL tubular):


Max discharge current remains same as above , I.E., 51.06 Amps
Capacty factor for 1 hr backup to ECV of 1.75 Volts = 2 ( from capacity factor table )
So Capacity required = 51.06 X 2
= 102.12 AH (approximately)

HENCE,nearest type, 6EL100 CAN BE RECOMMENDED


Note : In both the above cases , the temperature correction has not been considered. It can be
calculated the same way it is shown for 2V standby batteries.

Capacity Calculations for multiple load pattern


Assumptions
Battery required = VRLA
Cut-off voltage = 1.85Vpc
Load Pattern
I3 = 60A

Current A

I1 = 40A

I2 = 20A

t1 = 30 min

Time t
t2 = 120 min
t3 = 30 min

Operating Temp = 20 Deg C


Design Margin required = 20%
A.F = Ageing factor (0.8 for VRLA)

Capacity =(( I1 x F1 + (I2-I1) x F2 + (I3 - I2) x F3) x Kt x KD) / A.F


Where
T 1 = t1 + t2 + t 3 / T 2 = t2 + t3 / T 3 = t3
F1 = Cap factor for T1 / F2 = Cap factor for T2 / F3 = Cap factor for T3
Kt = 1 + ((27 - 20) x CT)/100, where CT is temperature correction factor at C-10, which is 0.43
KD = Design Margin of 10%

Capacity = ((40 x 4.219 + (-20 x 2.703) + 20 x 1.760) x 1.05 x 1.2) / 0.8


= 236.09 Ah
Nearest available capacity is EPST240 Ah

Capacity factor for VRLA 2V type


Final volt
v/cell
1.85
1.80
1.75
1.70
1.65
1.60

1 min

0.417
0.412
0.408
0.398

5 mins

0.625
0.609
0.592
0.572

15 mins

30 mins

1.490
1.241
1.110
1.020
0.960
0.920

1.760
1.499
1.389
1.311
1.258
1.225

60 mins
2.110
1.812
1.661
1.570
1.511
1.471

90 mins
2.703
2.342
2.179
2.070
2.008
1.969

2 hrs
3.195
2.809
2.653
2.538
2.457
2.398

3 hrs
4.219
3.731
3.521
3.401
3.268
3.185

4 hrs
5.181
4.630
4.386
4.237
4.132
4.000

5 hrs
6.173
5.556
5.319
5.128
4.975
4.831

6 hrs
7.194
6.494
6.173
5.952
5.814
5.650

8 hrs
9.009
8.197
7.937
7.692
7.463
7.299

10 hrs
10.753
10.000
9.615
9.259
9.091
8.929

Capacity factor for Vented 2V tubular type (NDP)


Final volt
v/cell
1.85
1.80
1.75
1.70
1.65
1.60

1 min

5 mins

15 mins

20 mins

30 mins

45 mins

1 hr

2 hrs

3 hrs

4 hrs

5 hrs

6 hrs

7 hrs

8 hrs

9 hrs

10 hrs

1.60
1.10
0.86
0.68
0.58
0.53

1.65
1.20
0.95
0.77
0.67
0.60

1.95
1.34
1.09
1.03
0.91
0.72

2.10
1.54
1.30
1.12
1.00
0.92

2.35
1.74
1.46
1.28
1.17
1.10

2.50
2.02
1.77
1.61
1.50
1.44

2.85
2.31
2.00

3.55
3.25

4.50
4.18

5.25

6.10

6.85

7.80

8.55

9.30

10.00

Capacity factor for Vented 2V tubular type (HDP)


Final volt
v/cell
1.85
1.80
1.75
1.70
1.65
1.60

1 min

5 mins

10 mins

20 mins

30 mins

45 mins

1 hr

2 hrs

3 hrs

4 hrs

5 hrs

6 hrs

7 hrs

8 hrs

9 hrs

10 hrs

1.38
0.96
0.74
0.60
0.51
0.46

1.44
1.04
0.82
0.68
0.58
0.52

1.54
1.16
0.96
0.80
0.70
0.63

1.74
1.34
1.13
0.98
0.87
0.80

2.04
1.62
1.37
1.20
1.10
1.03

2.12
1.87
1.65
1.51
1.41
1.35

2.50
2.02
1.67

3.30
2.81

4.15
3.70

5.05

5.92

6.75

7.70

8.48

9.25

10.00

Capacity factor for Vented 2V Plante type cells


Final volt
v/cell
1.85
1.80
1.75
1.70
1.65
1.60

1 min

5 mins

10 mins

15 mins

20 mins

30 mins

45 mins

1 hr

2 hrs

3 hrs

4 hrs

5 hrs

6 hrs

7 hrs

8 hrs

9 hrs

1.18
0.94
0.75
0.63
0.52
0.46

1.28
1.00
0.82
0.68
0.58
0.50

1.30
1.04
0.86
0.72
0.63
0.56

1.38
1.10
0.92
0.80
0.70
0.64

1.48
1.20
1.00
0.86
0.77
0.72

1.62
1.34
1.16
1.04
0.94
0.88

1.74
1.48
1.32
1.22
1.15
1.10

1.80
1.60
1.54

2.80
2.67

3.80
3.59

4.65

5.60

6.50

7.45

8.25

9.10

Capacity factor for VRLA 12 Volt monobloc.


Final volt
v/cell
1.80
1.70
1.65
1.60

30 secs

1 min

2 mins

3 mins

4 mins

5 mins

7 mins

10 mins

15 mins

20 mins

30 mins

1 Hr

90 mins

2 Hrs

0.25
0.18
0.15
0.13

0.26
0.20
0.17
0.15

0.26
0.20
0.19
0.18

0.27
0.23
0.22
0.20

0.29
0.25
0.24
0.23

0.31
0.28
0.26
0.25

0.36
0.33
0.31
0.30

0.43
0.40
0.37
0.36

0.56
0.53
0.50
0.48

0.67
0.63
0.61
0.59

0.91
0.87
0.83
0.80

1.56
1.49
1.45
1.43

2.38
2.08
2.00
1.96

2.78
2.50
2.44
2.38

Capacity factor for Tubular 12 Volt monobloc.


Final volt
v/cell

1 hr
1.8

1.75

2 hrs

3 hrs

4 hrs

5 hrs

6 hrs

7 hrs

8 hrs

9 hrs

10 hrs

3.16

4.14

5.13

6.02

6.82

7.61

8.42

9.18

10

10 hrs
10.00

Vous aimerez peut-être aussi