Equipment Type 415V

Working Distance 18 in (455mm)


Arc Flash Boundary(AFB) 26 in
Incident Energy @ AFB 1.20 cal/cm^2
Incident Energy @ Working Distance 2.34 cal/cm^2
Hazard Level 1
Equipment name MCC & Panels
Shock Hazard voltage level 415V
Limited Approach 42 inches
Restricted Approach 12 inches
Prohibited Approach 1 inches
Glove class 00
Approach Boundary Limits For Arc Flash & Shock Protection
Based on NFPA 70E & IEEE 1584
Equipment Type 415V
Working Distance 18 in (455mm)
Arc Flash Boundary(AFB) 150 in
Incident Energy @ AFB 1.20 cal/cm^2
Incident Energy @ Working Distance 28.43 cal/cm^2
Hazard Level 4
Equipment name Switchgears
Shock Hazard voltage level 415V
Limited Approach 42 inches
Restricted Approach 12 inches
Prohibited Approach 1 inches
Glove class 00
Approach Boundary Limits For Arc Flash & Shock Protection
Based on NFPA 70E & IEEE 1584