Vous êtes sur la page 1sur 2

Version 7.

9 / 41842 (07/14)

www.emersonclimate.eu

20 October 2014

Copeland Selection Software


REFRIGERANT

R407C Dew Point

Operating Conditions:
Evaporating Temperature:
Condensing Temperature:
Liquid subcooling:
Suction Superheat:

11.0C
51.0C
10.0K
10.0K

Required Capacity:
Compressor Selected:

35.0 kW
ZR81KCE-TFD

PERFORMANCE AT SPECIFIED OPERATING POINT


ZR81KCE-TFD Data at 50 Hz
Capacity kW
Power Input kW
COP
Current 400V, A
Mass Flow g/s
Heating Capacity kW

23.10
5.46
4.23
10.38
136.50
28.30

COMPRESSOR MECHANICAL AND PHYSICAL DATA


Length/Width, mm 242/242
Net Weight, kg 39
Rotalock Suction, inch 1 1/4
Stub Discharge, inch 3/4
Sound Power (HT), dBA 72
Internal Free Volume, l 4.2
Low Side PS, bar(g) 20
Displacement @ 50 Hz, cu.m/h 18.8
Rotalock Discharge, inch 1 1/4
Base mounting (hole dia), mm 190 x 190 (8.5)
Sound Pressure @ 1m (HT), dBA 61

Height, mm 443
Gross Weight, kg 45
Stub Suction, inch 7/8
Oil Quantity, l 1.77
PED Category 1
High Side PS, bar(g) 29.5
Low Side TS Max., C 50

COMPRESSOR ELECTRICAL DATA (380/420V - 3~ - 50Hz)


Locked Rotor Current, A 101
Maximum Operating Current, A 15
Winding Resistance, ohm 1.79
Default Enclosure Class IP 21 (IEC 34)

ACCESSORIES INCLUDED
Discharge Temperature Protection
Mounting Grommets

Internal Thermodisk
Standard

ACCESSORIES OPTIONAL
Crankcase Heater

70 W External