Troubleshooting by Error Code

6.26 Compressor Lock


Remote
Controller
Display

E6

Outdoor
Unit LED
Display

Aj 1h 2i 3i 4h 5h
(LED1 ~ LED5 are for multi outdoor unit.)

Method of
Malfunction
Detection

A compressor lock is detected by checking the


compressor running condition through the position
detection circuit.

Malfunction
Decision
Conditions

Operation stops due to overcurrent.


A compressor lock is detected by the current
waveform generated when applying high-frequency
voltage to the motor.
If the error repeats, the system is shut down
Reset condition: Continuous run for about 5 ~ 11
minutes (depending on the model) without any other
error

Supposed
Causes

Compressor locked
Compressor harness disconnected

Service Diagnosis

173

Troubleshooting by Error Code

Troubleshooting

Si10-417_C

Be sure to turn off the power switch before connecting or


Caution disconnecting connectors, or parts may be damaged.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.

Check No.15
Refer to
P.240

Turn off the power.


Disconnect the harnesses U,
V, and W.
Check No.15
Check with the inverter
checker ().

Normal?

Inverter checker
Part No.: 1225477

NO

YES

Correct the power


supply or replace the
outdoor unit PCB.

Turn off the power and


reconnect the harnesses.
Turn on the power again and
restart the system.

Emergency stop
without compressor
running?

YES

Replace the
compressor.

NO
System
shut down after errors
repeated several
times?
YES

NO

Check and replace the


outdoor electronic
expansion valve coil
as required.
Replace the
compressor.
(R15272)

174

Service Diagnosis