PAK ELEKTRON LIMITED

TRANSFORMER ENGINEERING DEPARTMENT

TECHNICAL DATA SHEET OF TRANSFORMER


M/s Reon Energy Solutions

Customer

Date:

August 8, 2014

Ref # :

TE/08-14/06-L

SPECIFICATION
Rated kVA
Voltage Ratio
Frequency / Phases
Vector Group
Type of Cooling
Insulation Class
Ambient Temperature
Temperature Rise at Rated kVA

1875
315 / 11000 Y Volts
50 Hz /
3

YNd 11
ONAN
A
40 0C
Top Oil
Winding Average

LV LI
AC 3
MV LI 75 AC 28
+ 2.5, 5.0, 7.5
Tapping Voltages (%)
- 2.5, 5.0
MV Terminals with Arcing Horns
4
LV Terminals
3
Service Altitude Above Sea Level
Upto 1000 meter
Basic Insulation Level
(BIL)

60 0C
65 0C

Type of Tank

Conservator

Type

Indoor / Outdoor

PERFORMANCE
No Load Losses at Principle Tap Position

2.5 kW

Load Losses at Principle Tap Position & Rated Current

21.5 kW

Impedance

6.0 %

Regulation at Unity Power Factor & Rated Current

1.32 %

Regulation at 0.8 Power Factor & Rated Current

4.53 %

Efficiency at Unity Power Factor & 100% Rated Current

98.74 %

Efficiency at Unity Power Factor & 50% Rated Current

99.17 %

COMPONENTS & ACCESSORIES


Off Circuit Tap Changer
Oil Conservator
Silicagel Breather
Oil Filling Hole and Plug
Oil Level Indicator
Oil Drain Valve
Lifting Lugs
Transport Eyes
Earthing Terminals
Bi-Directional Roller Wheels
Rating & Diagram Plate (Stainless Steel)

Pressure Relief Device (without contacts) (Elmek, Turkey)


Dial Type Thermometer for Oil Temperature with maximum
Temperature Indicator (with contacts) (Elmek, Turkey)
Double Float Buchholz Relay (Elmek, Turkey)

Remarks :
1) Transformer shall be offered with first filling of oil. Transformer Oil shall be in accordance with IEC-60296
2) Transformer shall be manufactured and tested as per IEC 600-76 Standard.

Transformer Engineering Department