MV consumer substation; Two MV ratings: 20 kV and 6 kV; T he main MV switchboard f ed at 20 kV can be backed up by a set of four generators. It f eeds: An MV 20 kV network in a loop system comprising three secondary switchboards MV4, MV5 and MV6; Two 20 kV/6kV transformers in a single line supply system; T he MV main switchboard is made up two bus sections f ed at 6 kV by two sources with coupler; It f eeds three MV secondary switchboards and two 6 kV/LV transf ormers in a single line supply system; the secondary switchboard MV2 is f ed by two sources with coupler and is made up of two bus sections. It f eeds two 6 kV motors and two 6 kV/LV transf ormers in a single line supply system; the secondary switchboards MV1 and MV3 are f ed by a single source. Each f eeds a 6 kV/LV transf ormer and a 6 kV motor; the main low voltage switchboard MLVS1 can be backed up by a generator; the main low voltage switchboard MLVS2 is f ed by two sources with coupler; the main low voltage switchboard MLVS3 is f ed by a single source; the motor control centers 1 and 3 are f ed by a single source; the motor control center 2 is f ed by 2 sources with no coupler. Reference: Protection of Electrical Networks - Christophe Prv