Vous êtes sur la page 1sur 1

Klingenburg Crossflow Plate Heat Exchanger

Tel.:
+49 (0) 20 43/96 36-0
Fax:
+49 (0) 20 43/7 23 62
E-Mail: klingenburg@klingenburg.de
Internet: www.klingenburg.de

Klingenburg GmbH
Boystrasse 115
D - 45968 Gladbeck
Germany
Notes:

Condensation!

Type: PWT 10 / 2000 / 3000 - 14,0


Supply air

Exhaust air

Inlet condition

Standard air volume


Air volume
Temperature
relative humidity
absolute humidity
Enthalpy

41883
40441
10,0
88,2
6,72
27,0

37876
51009
75,0
85,0
297,30
860,6

m/h
m/h
C
%
g/kg
kJ/kg

Outlet condition

Air volume
Temperature
relative humidity
absolute humidity
Enthalpy

46756
54,2
7,1
6,72
72,1

49205
70,9
95,9
275,33
796,3

m/h
C
%
g/kg
kJ/kg

Face air velocity


Pressure drop
Pressure drop (Standard density)

1,87
126
120

2,36 m/s
131 Pa
100 Pa

Exchange efficiency dry


Exchange efficiency wet

57,3
68,0

53,4 %
6,3 %

526,2
624,4

-526,2 kW
-624,4 kW

Heat recovery dry


Heat recovery wet

-21,97 g/kg
-768,90 kg/h

Condensation

Calculation based on
Air pressure
Altitude

1013 mbar
0 m

Dimensions

Edge dimension

2000 mm

Height (H)
Width (B)
Depth (T)

2798 mm
3000 mm
2798 mm

Weight

477,0 kg

H
B

Version 4.2, 03/10