Vous êtes sur la page 1sur 1

API STANDARD 650

STORAGE TANK
DATA SHEET
TANQUE AGUA CONTRA INCENDIO

DATE
BY

25/02/2015
G- Chaves
REV 0

FILE No

CONSTRUCTION DETAILS (TO BE COMPLETED BY MANUFACTURER AND/OR PURCHASER


1

NOMINAL CAPACITY LIQUID

MANUFACTURER
SERVICE

AGUA

ERECTION SITEBOGOTA
PETAR SALITRE

USER

M3

2.081

12.000

Bbl

13.092

ATAT

INTERNAL
C DIAMETER

75,5 FT

0,0435

psig

SHELL TOTAL HEIGHT

16,4 FT

IN H2o

LIQUID TANK HEIGHT

15,1 FT

2600

MTS

VAPOR PRESSURE

108

KMH

INTERNAL PRESSURE DESIGN 0,90


JACKS REQUIREMENTS

TANK SPECIFICATIONS

Jacks capacity

12.000

kg/und

DESING METAL TEMPERATURE 20

No Jacks required

30

und

HEATER REQUIRED

NOT

No hydraulic unids

und

INSULATION REQUIRED

NOT

20

Bbl

1,00

ALTURA MSNM

MAX OPERATING
TEMPERATURE

M3

DESIGN SPECIFIC GRAVITY

DESING WIND SPEED=

TEMPERATURE

NET MAXIMUN CAPACITY TANK

1.908

STANDARD 650 EDITION 11

PAINT AREAS

WEIGHT
137.022

MATERIAL SPECIFICATIONES

62.283

lbs

EXTERNAL UND

INTERNAL

TOTAL

TOTAL

KG

1.239

M2

1.367

SHELL

A 283 Gr C

42.235

lbs

19.198

KG

361

M2

361

STIFFENING RINGS

A 283 Gr C

1.032

LBS

469

KG

15

M2

15

ROOF

ASTM A283 Gr C

34.529

lbs

15.695

KG

416

M2

416

BOTTOM + Anular Bottom plate+skind

ASTM A283 Gr C

47.118

lbs

21.417

KG

414

M2

416

ANCHOR SUPPORTS ,COLUMNS, ROOF


STRUCTURS SUPPORT

ASTM A36

11.788

lbs

5.358

KG

12

M2

159

ANCHOR BOLTS

ASTM A-307

319

LBS

145

KG

M2

MAN HOLE AND NOZZLES

ASTM A106 /A105

lbs

KG

21

M2

LADDER,PLATFORMS, AND
HANDRAILS

ASTM A36

lbs

KG

M2

No SHELLS COURSES- PLATE WIDTHS AND THICKNESSES ( Including Corrosion Allowance)


widths

thicknesses

widths

thicknesses

widths

thicknesses

72

in

0,25

in

0,00

in

72

in

0,25

in

0,00

in

72

in

0,25

in

0,00

in
in

0
0

10

ANCHOR BOLTS

TANK BOTTOM
PLATE THICKNESS

0,25

SLOPE

2,00

IN

MINIMUM WIDTH ANNULAR PLATES

Intermedium Stiffening
ring inercia Module

MINIMUN 24 IN

BOLT CIRCULE
DIAMETER
BOLT DIAMETER

IN
THICKNESS OF BOTTOM ANNULAR PLATES

El tanque es estructuralmente estable

in3

3,02

in3

16,29

intermedium stiffening ring Not required

UND

BOLT QUANTITY 23

29,99

upper Stiffening ring


inercia Module

LAP

WELDING BOTTOM

ROOF TO SHELL DETAILS

tank, need anchor bolt for wind

65,46

FTS

SUPPORTED

Yes

22,23

mm

SELF SUPPORTED

Not

BOLT MATERIAL

ASTM A-307

0,25

FLOTING SEAL

not

SPECIFICATION

ROOF TYPE

Conial

THICKNESS OF ROOF PLATES

0,19

ROOF PLATES AND FRAMES

ASTM A -36

ROOF

ROOF
Roof diameter

130

in

CORROSION ALLOWANCE
BOTTOM

DEAD LOADS OVER ROOF

LBS/FT2

LIVE LOADS OVER ROOF

25

LBS/FT2

FOUNDATION TYPE

SHELL BOTTOM
SHELL

ft

LOADS

EARTHQUAKE DESIGN

0,0625

IN

EARTH

APENDIX E DESIGN

YES

0,0625

IN

CONCRETE RING WALL

SISMIC ZONE

2A

CONCRETE RING WALL WITH


YES
ANCHOR BOLTS

ZONE FACTOR(TABLE E2 )

0,15

IMPORTANCE FACTOR

SITE COEFFICIENTE
( TABLE E-3)

1,5

OTHERS

El tanque es estructuralmente estable

INSPECTIONS
INSPECTION PLACE

SHOP

FIELD

WELD EXAMINATION

RADIOGRAFIA

LIQ

ULTRASONID

/PENETR

Vous aimerez peut-être aussi