Project Administration /
Exercises

Training

DIGSI 4
Power System Protection
Function

Device Parameterization

CFC / Display / Control


4

CFC-Exercises

CFC-Function Modules

Commissioning and Test


Functions

Settings of Communication
interfaces

Siemens Power Academy


Siemens AG

10

Process Data Analysis

Siemens Power Academy

Dr. M.R. Ganjavi


PTD SE PTI NC Erlangen
Tel: +49 9131 733854
Fax: +49 9131 735017
Mohammad-reza.ganjavi@siemens.com

Version: B 5_Page 1

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - History
PC-OperatingSystem

DOS

DIGSI
Symbol

DIGSI
Version

Delivery

V2

1991

V3.3

1998

Windows 3.x
Windows 95
Win. NT 4.0
OS/2 Warp
Windows 95
Win. NT 4.0

V4.0

1999

V4.8

2008

Windows 98/2000/ME/XP
neu: Windows Vista
-Professional
Version: B 5_Page 2

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy


Targets of DIGSI 4 Basic Course

Using DIGSI 4 efficiently


Using the DIGSI 4 Project Manager in an

optimal way

Proceeding how to do the settings


Interpretation of trip logs
Evaluation of fault records
Engineering of CFC-charts, change of the

I/O-Configuration matrix

To know the opportunities of the default

display editor

Version: B 5_Page 3

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy


Training configuration in DIGSI 4 training course

Instructor

6 x 7SJ63x
SIPROTEC

SIPROTEC

7SC64-0000-ABC

RU N

RU N

C T RL

Lo c a l

Rem ote

RU N

E N TE R

ES C

F2

F3

CT RL

LED

Lo c a l

Re m o t e

F4

No rm a l

+/-

Version: B 5_Page 4

E N TE R

ES C

F2

F3

+/-

F4

No r m a l

RU N

C T RL

LED

Lo c a l

Rem ote

RU N

F3

+/-

F4

No rm a l

E N TE R

ES C

F2

01_A0: Introduction
DIGSI 4 Basic

C T RL

LED

Lo c a l

Rem ote

RU N

F2

F3

+/-

F4

No rm a l

E N TE R

ES C

ERROR

M EN U

F1

Te s t

7SC64-0000-ABC

ERROR

M EN U

F1

Te s t

SIPROTEC

7SC64-0000-ABC

ERROR

M EN U

F1

Tes t

SIPROTEC

7SC64-0000-ABC

ERROR

M EN U

F1

Te s t

SIPROTEC

7SC64-0000-ABC

ERROR

M EN U

LED

SIPROTEC

7SC64-0000-ABC

ERROR

C T RL

LED

Lo c a l

Rem ote

E N TE R

ES C

F1

F2

F3

+/-

Te s t

F4

No rm a l

M EN U

Energy Sector

C T RL

LED

Lo c a l

Rem ote

No rm a l

E N TE R

ES C

F1

F2

F3

F4

+/-

Te s t

9
6

Siemens AG

Siemens Power Academy

The modular Programm of DIGSI 4


DIGSI 4

Basic - Programm
Project and Device-Manager
- Supports device templates-

Scope of
functionality
Engineering
I/O-Matrix

Operation &
Control

Commissioning,
Test Mode

IEC,
PROFIBUS,
MODBUS,
DNP, ...

Visualization of
fault records

Additional programms
Display Editor to create and
edit the default and control
displays
DIGSI Remote
central- remote operation
using modems

Version: B 5_Page 5

01_A0: Introduction
DIGSI 4 Basic

SIGRA to visualize and


evaluate fault records

Graphic-Tools
trip characteristics
Impedance diagrams
SIMATIC CFC 4
Logic editor

Energy Sector

Siemens AG

Siemens Power Academy

Versions of DIGSI 4
Order-Code.

DIGSI 4 Variants
Basic
with License for up to 10 PCs
Professional
Complete version with all options
incl. SIGRA and Remote
Basis Upgrade DIGSI 3->4

7XS5400-0AA00
7XS5402-0AA00

7XS5405-0AA00
7XS5406-0AA00

Professional Upgrade DIGSI 3->4

Version: B 5_Page 6

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Versions of DIGSI 4
Variants

Order-Code.

SIGRA 4

7XS5410-0AA00

Evaluation of fault records


Option for DIGSI 4
DIGSI 4 Remote

7XS5440-0AA00

Software for remote operation


Option for DIGSI 4
DIGSI 4 Demo

7XS5401-0AA00

Multimedia presentation

Version: B 5_Page 7

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy


PC- Hardware-Requirements for DIGSI 4

Minimum PC-requirements

Recommended PC-HW

Pentium with 800 MHz

Pentium 1,6 GHz

128 MB RAM
700 MB on harddisk

256 MB RAM

700MB on harddisk

1 serial Port

1 serial Port
CD-ROM drive
Win95 or Win 98
WIN NT4.0, Win 2000/ME/XP-Prof.
Explorer 6.0

CD-ROM drive
Win 95 or Win 98

WIN NT4.0, Win 2000/ME/XP-Professional


Explorer 6.0

Version: B 5_Page 8

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy


DIGSI 4 operating program

Configuration matrix

Parameterization

Change relay display

Fault
evaluation

Test

Logic Editor

Version: B 5_Page 9

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - The manager that keeps order

Easy management of relays in projects


Selection of relays from a catalog
Archiving, export, and import
Variation management
Plug and play
Reading out process data with singlekeystroke operation

Work like in MS Windows Explorer


Any station topologies
Same platform as for SICAM Substation
Automation System

Version: B 5_Page 10

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - A single DIGSI for every version of every relay

Uniqu
e !!!

Version: B 5_Page 11

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - The function tree with a pivotal function

Function tree has a pivotal


function in operation

"What you see is what you


need

Graphic visualization of the


tripping characteristic

Comparison of parameters
Structured tab card dialogs
Version: B 5_Page 12

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - The allocation matrix, a clear overview

Routing of indications,
measured/metered values,
commands to
inputs/outputs, LEDs, CFC,
buffers, system interface,
feeder control diagram

Matrix instead of nested


operating sequences

Popup menus provide the


options

Overview using filter,


hiding/showing
Version: B 5_Page 13

No
incorrect
input possible
01_A0:
Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - Test functions, decisive for commissioning

Testing and diagnostic functions


Quick and problem-free testing of
wiring

Output of indications via the system


interface

Opening and closing of relays


...

Version: B 5_Page 14

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - Fault analysis with SIGRA


Time-signal curves, circle
diagrams, vector
diagrams, barcharts

Calculation of positivesequence impedances,


rms values, symmetrical
components, vectors,
and much more

Quick and easy


measurement using two
cursors

Adding further fault


recordings (e.g. from the
remote end of a line)

Synchronization of fault
recordings

Also for fault recordings


of relays from other
manufacturers
Version: B 5_Page 15

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - Programming SIPROTEC with CFC

PLC integrated into the SIPROTEC 4 relays


Fully graphic, no progamming skills required
Libraries with standard blocks
Dragging blocks from the catalog into the chart,
then linking with a mouse click

Connecting block inputs and outputs with


information items (measured values,
indications, circuit breaker positions, ...)

Consistency check with guarantee of


effectiveness of the protection
Version: B 5_Page 16

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - Typical CFC applications


Extension of the release condition for a switching command
(e.g. by the position of a further disconnector and the information item "spring charged")

Display of an application-specific group indication in an LED


(single indications logically combined with operators, such as AND, OR, NOT)

Display of a new dynamic symbol for an item of equipment in the


display
(various states calculated by the CFC logic)

Switchover of the parameter group


(on phase currents dropping below a limit value)

Blinking alarm LED if the switching authority is set to "LOCAL"


Implementation of a protection function not offered in the relay
(e.g. "Reverse power protection" or "Efficiency monitoring")

Forced sequence switching after pressing a function key on the


relay
(e.g. automatic grounding)

Step-by-step load shedding on power deficit


(calculation of suitable feeders by the CFC logic)

...

Version: B 5_Page 17

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - Adapting the relay display with the


Display Editor

Changing the basic displays and feeder


control diagrams preconfigured in the
factory

Operation like with a conventional


image editor

Libraries with static and dynamic


symbols, including user symbols

Linking of the dynamic symbol with the


associated item of equipment,
measured value, ...

Typical diagrams can be stored as


templates
Version: B 5_Page 18

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI - Station configuration for busbar protection

Busbar protection 7SS52 now also


operable with DIGSI 4 (V4.30)

Operation like the Display Editor


Libraries with static and dynamic
symbols, including user symbols

Linking of dynamic symbols with the


associated item of equipment,
measured value, ...

Typical diagrams can be stored as


templates

On-line visualization (HMI)


Version: B 5_Page 19

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy


DIGSI - Some advantages
1 program
for all tasks

1 program
for all relays

User
friendly

Standardized
over the bay and
station control levels
Version: B 5_Page 20

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy


DIGSI - Requirements

Minimum PC requirements

Recommended PC hardware

Pentium from 800 MHz

Pentium from 1,6GHz


256 MB RAM

128 MB RAM

700 MB memory space on

700 MB memory space on


harddisk

harddisk
1 serial port

1 serial port

CD-ROM drive

CD-ROM drive

MS Windows 95/98/ME

MS Windows 95/98/ME
NT4/2000/XP Prof.
Version: B 5_Page 21

NT4/2000/XP Prof.

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy


DIGSI - Order structure
Product description

Variant

Order No.

DIGSI 4
Software for configuring and
operating protection units from
SIEMENS
MS Windows program, executable
under MS Windows NT 4 / 95 / 98 /
2000 / ME
Incl. device templates,
Comtrade Viewer, characteristic
visualization,
manual in electronic form

Basic
With license for 10 computers
On CD-ROM
Authorization by license number
Demo
Multimedia presentation with operating
videos for demonstration and training
In addition: Demo version of
DIGSI 4 Basic (without communication
with unit)
On CD-ROM and on Demo-CD-ROM
Professional
Complete version: Basic and all optional
packages
On CD-ROM
Authorization by license number
Basic Upgrade
Contains the packages Basic and
SIGRA.
Full version with license for 10
computers
For licensed users of previous versions
On CD-ROM
Authorization by license number
Professional Upgrade
Complete version: Basic and all optional
packages
With a license for 10 computers
For licensed users of previous versions
On CD-ROM

7XS5400 - 0 AA00

Version: B 5_Page 22

01_A0: Introduction
DIGSI 4 Basic

7XS5401 - 0 AA00

7XS5402 - 0 AA00

7XS5405 - 0 AA00

7XS5406 - 0 AA00

Energy Sector

Siemens AG

Siemens Power Academy


DIGSI - We support you

Demo programs (on CD-ROM)


DIGSI 4 DEMO
SIGRA 4 TRIAL & DEMO

Training
www.siemens.com/power-academy-td
In German and English, in Nuremberg,
but also "locally" anywhere in the world

Energy Customer Support Center


www.siprotec.com in Service or Contact tab

Phone: +49 1805 247 000


eMail: support.energy@siemens.com
FAQ: www.siemens.com/energy-support

Newsletter
www.siprotec.com in Software/DIGSI4 tab
3-4 times a year: information about products,
hints & tricks, solutions, coming training dates

Internet
www.digsi.com

Soon: On-line forms for product registration, hotline


queries, software order configuration as a service
Version: B 5_Page 23

01_A0: Introduction
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 System and Device Management


Installing DIGSI 4
Managing Projects
Working with the Devices
Optimizing Parameterization

Version: B 5_Page 1

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Install - Uninstall


Installation from CD Rom:
ADMINISTRATOR-rights are required
DIGSI 4 components
device drivers for SIPROTEC 4
Sequence:
start Windows
Insert CD ROM - Autostart of Installation
insert licence number of product card
selection of components
Deinstallation:
via system settings remove Software...
(only that procedure will delete the entries in the registry-file)

Version: B 5_Page 2

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - The Structure of Projects in the DIGSI 4


Manager
System component hierarchy at your convenience
Project
System
Station
Feeder
Device
Modems
Phone Book

Version: B 5_Page 3

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - New Project

Select the corresponding


dialog box
Enter project name
Define storage location

Version: B 5_Page 4

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Folders
Basic structure

Folders can contain the following objects


Further folders
SIPROTEC 4 devices
V3/V2 devices
SIPROTEC 4 versions
Modem connections

Version: B 5_Page 5

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Project Structure

Version: B 5_Page 6

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise:
Create & structure project - Part I
Create a new project (Project 1).
Insert the folders (hierarchy levels) like in
the shown structure with the according
names.

Version: B 5_Page 7

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Insert Device

Open device catalog


Select device
Drag & Drop the device in
the project structure

Version: B 5_Page 8

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Specification

Properties

Version: B 5_Page 9

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise:
Create & structure project - Part II
Insert the following SIPROTEC 4 relays:

Region North:
Relay on the table
Substation 1: 7SJ610 V4.4

Feeder 1:
Feeder 2:

Version: B 5_Page 10

7SJ622 V4.6
7SJ631 V4.6
Modem connection

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Administrate V2/V3 Device

In DIGSI 4 Manager
SIPROTEC relays of
recent releases (V2,
V3) can be
administrated:
Before inserting
they have to be
generated in DIGSI V3.

Version: B 5_Page 11

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Administration of V3-Projects

In DIGSI 4 Manager projects of recent releases (V3 DIGSI-projects) can be


administrated:
Before inserting they have to be generated in DIGSI V3.
Version: B 5_Page 12

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise:
Create & structure project - Part III
Insert an older relay into the folder
Feeder 6th Avenue.

Version: B 5_Page 13

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Object Properties

SIPROTEC 4
Device
properties

Version: B 5_Page 14

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Object properties of V2/V3 relays

V2/V3 Device
Properties

Version: B 5_Page 15

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Save Project / Close

Save project
Save as...

- with / without rearrangement


- define storage location
Save

Close project

Version: B 5_Page 16

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise: DIGSI 4 - Save / copy / delete

Create a new project (Project 2)


Copy the folder Substation 2 from the first project (Project 1) into the new
project.
Insert a new folder with the name 110 kV in the folder
substation 2.
Copy the folders Feeder 1 and Feeder 2 from the first project (Project 1).
Move the relay 7SJ631 V4.1 from Feeder 2 to Feeder 1
Delete the relay 7SJ622 in Feeder 2.
Insert a new relay of the type 7SJ610 V4.0.
Specificate the order number MLFB and look at the object properties.

Version: B 5_Page 17

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Open Projects


Menu item File Open
Automatic presetting
after Program start
(global default setting)
Latest edited projects
Hidden / moved

Version: B 5_Page 18

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Archiving / Retrieving of Projects

Project archiving - first steps


Make basic settings
- Select the archiving program of your choice
- Set folder to archiving / retrieving

Configuration of archiving program


- Archive beyond floppy disk
- Consistency check
- Overwriting of objects with identical names
- Automatic creation of archive path

Version: B 5_Page 19

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Archiving / Retrieving of Projects

Basic settings
Archiving
Retrieving

Version: B 5_Page 20

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Project Archiving

Project archiving

Version: B 5_Page 21

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Retrieving Projects

Retrieving projects
Select archive/source
Select a destination

Version: B 5_Page 22

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Delete / Reorganize Projects

Delete projects
individual
several

Reorganize projects

Version: B 5_Page 23

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise:
Archive/Delete/Retrieve
Archive the project Project 1 into the file system (C:\Floppy).
Delete the Project Project 1
Close the project Project 2 and reopen it.
Retrieve the archived project Project 1 from the file system.

Version: B 5_Page 24

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Optimization and Parameterization


Use of functions beyond the projects:
Copy
Move
Model parameterization

for objects
Project
Folder
Device

Version: B 5_Page 25

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Generate Copies/Variants


A selected relay can be copied:
Edit > Copy and Edit > Paste
The new relay comes up
Note: The new relay has a new internal address. Original and copy are
different.
For a selected relay a variant can be generated:
Edit > Create variant
The new relay variant comes up.
Note: The variant has the same address like the original relay. Original and
variant are not different!

Version: B 5_Page 26

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Copy versus variant


A relay must be copied, when there are two or more
relays of the same type and the parameters should be
copied.
In this case the new relay must be initialized first (to
get a new internal address).
For a relay a variant must be created, when there are
multiple parameter settings are required for one relay.
The relay has to be initialized only once, because the
variants have all the same address.

Version: B 5_Page 27

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device variants - Import and Export


Original: scheduled set

Export

from the Project Department

Version: IBS set


from the Commissioning Department

Import

Version: operator set


from the Operations Department

Version: B 5_Page 28

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device variants


A device variant is generated as follows
Generate a variant of an existing
SIPROTEC 4 device
Import device data
Plug & Play connection to a
SIPROTEC 4 device

Version: B 5_Page 29

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Export Device Data


Open dialog box
Define destination
Start exporting procedure

Version: B 5_Page 30

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Importing Device Data


Import device data as SIPROTEC 4 variant
Open dialog box
Select Import File
Start the import procedure

Version: B 5_Page 31

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Importing Device Data


Import device data as SIPROTEC 4 device
Open dialog box
Select Import File
Start importing procedure

Version: B 5_Page 32

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Working with variants


Create a new variant of your relay (in Region North): My relay 1. Change
one parameter.
Export the variant into the file system (Myrelay1.dex on C:\Floppy).
a) Import the exported file as a SIPROTEC 4 variant: My relay 2.
Change the parameterization of the original relay.
b) Import the exported file directly as SIPROTEC 4 device and replace the
original relay.

Version: B 5_Page 33

02_A0: Project Administration


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Parameterization and Configuration

Overview
Device parameterization and configuration in the Offline mode
Configuration of information
CFC logical functions
DIGSI 4 Editor for default and control display
Settings transfer to device
Settings change in the Offline mode
Save settings change in the Offline mode
Exercises

Version: B 5_Page 1

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Setting Block

Possible storage locations for a device setting block:


Data structure of the DIGSI 4 settings computer
Memory of the SIPROTEC 4 device
External storage medium (for ex. floppy disks)

Version: B 5_Page 2

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device in the Offline Mode

Working with SIPROTEC 4


data in the Offline mode

Version: B 5_Page 3

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Settings

Open device
Open tree view
Select Settings

Version: B 5_Page 4

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Configuration

Selecting the
device configuration

Version: B 5_Page 5

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Setting Groups

Editing
Display activated group
Switching
Copy
Reset
Export protection settings

Version: B 5_Page 6

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Setting Group Definition

Define Setting Group

Version: B 5_Page 7

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Changing Setting Group

Direct selection
in the DIGSI 4
Dialog
Binary input
Telegram
(IEC60870-5-103)

Version: B 5_Page 8

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Editing of Device Settings

Cross group
settings
defintion

Version: B 5_Page 9

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Editing System Data

Higher-level
device data
definition

Version: B 5_Page 10

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Defining Interfaces

Definition of the
PC Interface
Settings

Version: B 5_Page 11

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Time Synchronization

Setting of the
device time
synchronization

Version: B 5_Page 12

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Password Protection

Password
assignment

Version: B 5_Page 13

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Password Protection

Password
Definition
Change

Version: B 5_Page 14

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Password Protection

Password
Deactivation
Activation

Version: B 5_Page 15

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Password Protection

Reset all passwords

Version: B 5_Page 16

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Parameterization

Configuration of information
Configuration of CFC functions
Configuration of default and control displays (ASB)

Version: B 5_Page 17

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Configuration of Information

Version: B 5_Page 18

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Configuration of Information

Structure of the matrix


Information
Source
Destination
Information blocks
- general
- protection functions
- indications, measured values, statistics
- functional scope related
- user-defined

Version: B 5_Page 19

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Configuration of Information

Working with the matrix


Configuration
Insertion of information
Change of view
- expanding / collapsing of groups and columns

Filtering
- as to information
- as to type of configuration

Version: B 5_Page 20

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Object Properties

Single Point
Indication SP

Version: B 5_Page 21

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Graphical Display

Default display
- Not operator-controllable

- Indication of operational statuses, measured values, texts

Control display
- Release of switching operations

- Indication of operational statuses, measured values, texts

Version: B 5_Page 22

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Default and Control Display

Version: B 5_Page 23

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Configuration of CFC Functions

CFC blocks to link information


- creating group indications
- defining interlocking checks

Configuration steps
- starting CFC
- inserting chart
- inserting module
- defining order of execution
- interconnecting blocks

Version: B 5_Page 24

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Configuration of CFC Functions

Starting of CFC

Version: B 5_Page 25

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Configuration of CFC Functions

Version: B 5_Page 26

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Configuration of CFC Functions

Version: B 5_Page 27

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4

Load settings to the device


Change and save settings in the Online mode

Version: B 5_Page 28

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - The Online Mode

Loading of the settings


Change of individual settings
Indications, measured values, retrieval of fault records
Device control
Execute test functions
Device reset and resume
Setting of clock and date

Version: B 5_Page 29

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Interfaces

User interface
- DIGSI 4 direct connection

Service interface
- DIGSI 4 modem connection

System interface (e.g. IEC61850, PROFIBUS)


- connection to control center

Version: B 5_Page 30

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Initialization

The online mode

Version: B 5_Page 31

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Setting up of Device Connection

Open device
Parameterize connection

Version: B 5_Page 32

03_A0: Device Parameterization


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Saving Settings

hard disk

Version: B 5_Page 33

DIGSI 4
computer

03_A0: Device Parameterization


DIGSI 4 Basic

SIPROTEC 4 device

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information and Interfaces

Definition of Information
Device Information Model
Types of Information
Information Type: Annunciation
Information Type: Control without Feedback
Information Type: Control with Feedback
Information Type: Measurement & Power Meter

Version: B 5_Page 1

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Definition of Information

An information is an event, value, or command that has meaning for device


and should be processed in the protection device and/or control system.
Example:
Information:
Value
:
Example:
Information:
Value
:
Example:

Circuit breaker door position is closed


CLOSED / OPEN
Circuit breaker position
ON / OFF / INTERMIDIATE / ERROR

Information: Indicate phase A current (IL1=) in primary value


Value

: 250.0 A

Version: B 5_Page 2

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Model

(Configuration Matrix)
Output
Resources

Communication Resources

Front panel Interface (Port A, local service interface)


System Interface (Port B, system interface to substation control)
Service Interface (Port C , remote service interface DIGSI/Modem)
Add. Serial Interfaces (Port D&E, Inter-Relay Interface )
e.g. RTD-Box, Remote differential or distance relays
Input Resources

SIPROTEC 4 device

Binary Input #m

Source
Version: B 5_Page 3

LED #q
CFC #r
Buffers #t
Display #s

Function Key #n
CFC #k

Binary Output #p

Control Menu
Information Xn

Information
03_A0: Device Information and Interface
DIGSI 4 Basic

(Controllable on the Display)

Destination
Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Model (Configuration Matrix)

Version: B 5_Page 4

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Model (Configuration Matrix)

Version: B 5_Page 5

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Encoding

Source
U-

Bit n

U+
Logic 1: Active High
(on voltage presence)

Single Point Information


(One bit encoded information)

Bit n

meaning

Logic 0
Logic 1

OFF / Open
ON / Close

Destination

Logic 1: Active Low


(on voltage absence)

Example
Binary input #8
Logic 1: Active High

CB Door Is Closed

LED #5
(Lits when Open)

Version: B 5_Page 6

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Encoding

Source

Double Point Information


(Two bit encoded information)
Bit n+1
(52a)

Bit n

U+
U-

Bit n+1

U+
Circuit
X

Breaker

Logic
Logic
Logic
Logic

0
0
1
1

Destination

Bit n meaning
(52b)
0
1
0
1

Intermediate/Error
OFF
ON
Error

Example
Binary input #9 #8

Version: B 5_Page 7

Disconnector Status

03_A0: Device Information and Interface


DIGSI 4 Basic

Interlocking
CFC logic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Types

Annunciations

Source

Destination
SP outgoing information to:
Binary Outputs

YES

LEDs

YES

CFCs

YES

SP or DP incoming information from:

System Interface

YES

Binary Inputs

YES

NO

Buffers

YES

Function Keys

YES

NO

Display

YES

CFCs

YES

NO

Control Menu

YES

System Interface

NO

YES
DP outgoing information to:

(only IEC 61850)

Version: B 5_Page 8

03_A0: Device Information and Interface


DIGSI 4 Basic

Binary Outputs

NO

LEDs

NO

CFCs

YES

System Interface

YES

Buffers

YES

Display

YES

Control Menu

YES

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Types

Annunciations

Source

Destination
SP outgoing information to:
Binary Outputs

YES

LEDs

YES

SP or DP Internal information from:

CFCs

YES

Binary Inputs

NO

System Interface

YES

Function Keys

YES

Buffers

YES

CFCs

YES

Display

YES

System Interface

NO

Control Menu

YES

DP outgoing information to:

Version: B 5_Page 9

03_A0: Device Information and Interface


DIGSI 4 Basic

Binary Outputs

NO

LEDs

NO

CFCs

YES

System Interface

YES

Buffers

YES

Display

YES

Control Menu

YES

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Types

Annunciations

Source

Destination

Note: Two or more binary inputs define


the position number of the transformer
tap changer.
e.g. 4 binary input for 16 tap positions
SP outgoing information to:
Incoming information from:

Binary Outputs

NO

LEDs

NO

Binary Inputs

YES

CFCs

NO

Function Keys

NO

System Interface

NO

CFCs

NO

Buffers

YES

System Interface

NO

Display

YES

Control Menu

YES

Version: B 5_Page 10

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Types

Annunciations

Source

Destination
SP outgoing information to:
Binary Outputs

YES

LEDs

YES

SP Internal information from:

CFCs

YES

Binary Inputs

NO

System Interface

YES

Function Keys

YES

Buffers

YES

CFCs

YES

Display

YES

System Interface

NO

Control Menu

NO

VI outgoing information to:


VI Internal information from:
Analog Inputs, Internal calculation
Note: source and information
are fixed and can not be
selected/deleted in the
configuration matrix.

Version: B 5_Page 11

03_A0: Device Information and Interface


DIGSI 4 Basic

Binary Outputs

NO

LEDs

NO

CFCs

YES

System Interface

YES

Buffers

YES

Display

YES

Control Menu

NO

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Types

Source

Annunciations

Destination

Measured/Metered Value
External Measured Value

Information to:

Information from:
Measured Value Window NO
CFCs

YES

CFCs

YES

System Interface

YES

System Interface

YES

Metered Value Window

YES

Display

YES

(only IEC 61850)

Version: B 5_Page 12

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Control Circuits


Single Control

Double Control

Double Control

Double Control

Double Control

(S)

(D2)

(D4)

(D12)

(D3)

U+

U+

Trip

U+

U+

U+

U+

U+

U+

U+

Trip

Close

Trip

Close

Trip

Close

Trip

Close

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

&
Close
Coils U-

U-

U-

U-

Started

U-

Interlock

U-

52b

Control U+

Command

U-

52a

U+

Feedback
SP indication
or

Check

U-

U-

DP indication

Command

Chatter

Executed

Blocking

Circuit Breaker
X
Version: B 5_Page 13

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Types

Commands
Without Feedback

Source

Destination
SP outgoing information to:

Command information from:

Binary Outputs

YES

LEDs

NO

CFCs

YES

CFCs

YES

System Interface

NO

System Interface

YES

Buffers

YES

Display

YES

Control Menu

YES

Version: B 5_Page 14

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Types

Commands
With Feedback

Source

Destination
SP outgoing information to:

Command information from:

Binary Outputs

YES

LEDs

NO

CFCs

YES

CFCs

YES

System Interface

NO

System Interface

YES

Buffers

YES

Display

YES

Control Menu

YES

Feedback information from:


One binary input as SP indication
or
Two binary inputs as DP indication.

Version: B 5_Page 15

03_A0: Device Information and Interface


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Device Information Types

Measurement

Source

Destination
Measured, Limit Value
Information to:

Measured and Limit Value


Information from:

Measured Value Window

YES

CFCs

YES

CFCs
Analog Inputs

YES YES YES


Yes NO YES

System Interface

YES

System Interface

NO

Metered Value Window

NO

Display

YES

YES NO

(only IEC 61850)

Power metered Value

Power metered Value

Information to:

Information from:
Measured Value

YES

Binary Inputs

NO

Measured Value Window NO

NO
YES

Version: B 5_Page 16

03_A0: Device Information and Interface


DIGSI 4 Basic

CFCs

YES

System Interface

YES

Metered Value Window

YES

Display

YES

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 1: Change the setting - group in dependence


of the current
Setting group B becomes active if all line currents drop below 5% of the rated
nominal current.
Otherwise, setting group A is active.

Version: B 5_Page 1

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 1: Enable the Setting Group Change Option
Enable the Setting Group Change Option in the Device Configuration.

Version: B 5_Page 2

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 2: Configure the Setting Group Change Option
Open the Setting Group Change Option (double-click).
Set parameter 0302 to binary input.

Version: B 5_Page 3

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 3: Allocation
Open the Configuration Matrix (Masking I/O).

Bit 1
0

Bit 0

Assign the information item >Set Group Bit 0


to C (source CFC !)

Only >Set Group


Bit 0 changes
between A and B

Version: B 5_Page 4

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 4: Allocation
Assign the currents to C (destination CFC !)

Version: B 5_Page 5

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 1: Change the setting group dependend on the


current
Step 5: Build the CFC program
Use the following function blocks:
Lower Setpoint: Q = Val < Limit
This function block outputs a signal when the
measured value Val drops below the specified limit
value Limit. It can only be applied in the
MW_BEARB priority class for measured values.

X1

AND: Y = X1 * X2

X2

(+)
Y

X1
Y
X2

Version: B 5_Page 6

04_A0: CFC-Exercises
DIGSI 4 Basic

&

X1

X2

0
1
0
1

0
0
1
1

0
0
0
1

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 1: Change the setting group dependend on


current
Step 5: Build the CFC program

Version: B 5_Page 7

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


After pressing the F1 key setting group B is active during the first 10 seconds.
Then, setting group A gets active again.

Version: B 5_Page 8

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 9

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 10

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 1: Allocation of informations
Insert a new information item of the type Internal Single-Point Indication (Tagging)
in the matrix and assign it to the F1 function key and to CFC (destination CFC).

Version: B 5_Page 11

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 12

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 13

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 2: Save the allocated information
Save the allocated information.

Version: B 5_Page 14

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 15

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 16

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 3: Insert a new CFC chart
Open the folder named CFC, insert a new CFC chart, give it a good name and
open it.

Version: B 5_Page 17

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 18

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 19

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 4: Draw a CFC chart
The TI
MER ru

Use the TIMER block.

R => Timer Reset


S => Timer Start

ns onl
y

in PLC

or PLC

1!

Q=(S+T2) * T1 * R
QT1= T1 * R
QT2= T2 * R

S
Q

QT1

T1

QT2

T1
T2

T1 and T2 timer function


Version: B 5_Page 20

T2

Delay
Q is delayed by T1
04_A0: CFC-Exercises
DIGSI 4 Basic

Prolongation
Q corresponds to S prolonged by T2
Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 4: Draw a CFC chart
Insert a TIMER
block via
Drag & Drop.

Version: B 5_Page 21

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 4: Draw a CFC chart
Connect the input S (Start TIMER)
to the information Start (configured to F1)

Version: B 5_Page 22

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 4: Draw a CFC chart
Set the value for the timer T1 to 10000 ms.

Version: B 5_Page 23

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 4: Draw a CFC chart
Connect the output QT1 (HIGH applies for as long as the T1 timer is running)
to the information >Set Group Bit 0

Version: B 5_Page 24

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 25

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 26

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

CFC - Continuous Function Chart


(IEC Standard 1131 = High Flexibility)
4 priority classes for various tasks
PLC (Fast PLC)
Blocking protection functions
Few modules only
Automatic start after change-of-state at the input
PLC1 (Slow PLC)
Most frequent priority class (e.g. for TIMER applications)
Automatic start after change-of-state at the input
SFS (Switchgear interlocking)
Verifying the switchgear interlocking
Automatic start like PLC plus when activating a control command
MW (Measured value processing)
Configuring and comparing measured values
Implementing additional protection functions such as Reverse power (ANSI
32) and Power factor (ANSI 55)
Automatic start every 600 ms

Version: B 5_Page 27

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 5: Shift chart in the proper priority class
Open the Run-time Editor
To change the priority class: Grab your good name folder (by left mouse
key) and drag & drop it into the desired priority-class folder p menu (Shift
+ F11).
If you want to prepare
the NEXT CFC chart
inserted to run under
another priority class
then first select the
desired priority class
then click on edit
then predecessor for
insert position and
then ok

Version: B 5_Page 28

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 29

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 30

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 6: Let the system verify the run sequence

Obviously, you dont have to change the run


sequence as the TIMER is the only block
running in the chart.

Changes must, however, be made if several function blocks are


placed and some of them are maybe in the wrong order

Version: B 5_Page 31

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 6: Let the system verify the run sequence
In this case, the run sequence must be changed
as the TIMER has the number 2 in the chart, i.e.
it will be executed after the OR block.

In this case, click on


Options and then on
optimize run sequence.

Version: B 5_Page 32

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 33

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 34

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dep. on the time


Step 7: Compile the CFC chart
Compile the chart.

Version: B 5_Page 35

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 36

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 37

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 2: Change the setting group dependend on time


Step 8: Save the parameter set
Close the chart and save the parameter set.

Version: B 5_Page 38

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 39

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Follow the CFC standard procedure!

1.
2.
3.
4.

Allocate necessary informations to CFC


Save the Configuration Matrix
Insert and name a new CFC chart
Draw the chart

5.
6.
7.
8.

Shift the chart in the proper priority class


Let the system verify the run sequence
Compile the chart
Save and download the parameter set

Version: B 5_Page 40

04_A0: CFC-Exercises
DIGSI 4 Basic

;
;
;
;
;
;
;
;

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 3: Change the setting group dep. on the time


and the current
Normally, group A is active.
Group B is active:
during the first 10 seconds after pressing the F1 key
or
if all phase currents drop below 5% of the rated nominal
current.
Combine the solution from exercise 1 with that from exercise
2 by using the following block:

OR: Y = X1 + X2

X1
(+)

X2

X1
X2

Version: B 5_Page 41

04_A0: CFC-Exercises
DIGSI 4 Basic

X1

X2

0
1
0
1

0
0
1
1

0
1
1
1

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 3: Change the settings group


Solution - Allocation
Connect the two charts via an additional internal single-point indication:
Chart I < 5: Priority class MW_BEARB

Chart 10s after start: Priority class PLC1_BEARB

Source
CFC
Destination
CFC

Matrix

Insert a new internal


single-point indication
in the matrix and
allocate it to CFC
(destination and
source!)
Version: B 5_Page 42

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 3: Change the settings group


Solution - CFC
1

Chart I < 5 (priority class MW_BEARB):

Chart 10s after start (priority class PLC1_BEARB):

Version: B 5_Page 43

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 4: Time control 1 (2) Simple switching


sequence
When F1 is pressed, LED1 is lit for 5 seconds.
Then LED2 is lit for 15 seconds.

Version: B 5_Page 44

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 4: Time control 1 (2) Simple switching


sequence
Solution
1

Priority class: PLC1 (slow PLC)

Version: B 5_Page 45

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 5: Time control 2 (2) - Flashing


A LED flashes when F1 is pressed.
It goes off when F2 is applied.

Version: B 5_Page 46

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 5: Time control 2 (2) - Flashing


Solution
1

Priority class: PLC1 (slow PLC)

OR

Version: B 5_Page 47

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 6: Power Direction


A new dynamic symbol (arrow) on the default display of the device is to
indicate the power direction.

Version: B 5_Page 48

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 6: Power Direction


Solution - Allocation
Allocate the required measured value P= (power) to the destination CFC.

Create an internal double-point indication required


to indicate the power direction on the default
display.

Version: B 5_Page 49

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 6: Power Direction


Solution - CFC
Evaluate the power direction by using the blocks UPPER_SETPOINT and
LOWER_SETPOINT.
Use BUILD_DI to create the previously defined double-point indication Pdirection.

Version: B 5_Page 50

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 6: Power Direction


Solution - Display Editor
Create 3 static symbols to visualise
the states shown below.

Create a dynamic symbol of the


type Symbol to be filled with the 3
static symbols.

Place the dynamic symbol on the


default display and connect it to the
new double-point indication.
Version: B 5_Page 51

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 7: Interlocking expansion


Expand the default interlocking conditions:

The switch commands for the circuit breaker, isolating switch and
grounding switch are only admitted if
no SF6-Loss indication is present

Version: B 5_Page 52

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 7: Interlocking expansion


Solution
1

Allocate SF6-Loss to CFC as destination.

Version: B 5_Page 53

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 7: Interlocking expansion


Solution
Feedback of devices:

Interlock conditions:

2
Breaker DP

Disc.Swit. DP

AND
EarthSwit. DP
52 Close IntSP
AND
52 Open IntSP
AND

You have to expand the


already existing chart in
the priority class SFS
(Interlocking).

Disc.Close IntSP
AND
Disc.Open IntSP
AND
E Sw Open IntSP
E Sw Close IntSP

Version: B 5_Page 54

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 7: Interlocking expansion


Solution
2a

Modify the interlock condition 52 Close on the page A1:

52 Close IntSP

SF6-Loss SP

2b

No SF6-Loss
to the other interlock
conditions

Modify the interlock condition 52 Open on the page A2:


52 Open IntSP
No SF6-Loss

2c

Modify the interlock condition Disc.Close on the page A2:


Disc.Close IntSP

No SF6-Loss
Version: B 5_Page 55

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 7: Interlocking expansion


Solution
2d

Modify the interlock condition Disc.Open on the page A2:

Disc.Open IntSP

No SF6-Loss
2e

Modify the interlock condition E Sw Close/E Sw Open on the page A2:

E Sw Close IntSP
E Sw Open IntSP

No SF6-Loss

Version: B 5_Page 56

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 8: Create new interlocking conditions


Create the new interlocking conditions for closing the...
Breaker: Disconnector=ON AND Earth switch=OFF
Disconnector: Breaker=OFF AND Earth switch=OFF
Earth switch: Breaker=OFF AND Disconnector=OFF
Opening the switches should be possible in non-interlocked state!

Version: B 5_Page 57

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 8: Create new interlocking conditions


Solution - Allocation
1

Version: B 5_Page 58

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 8: Create new interlocking conditions


Solution - Assign a release condition
2

Version: B 5_Page 59

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 8: Create new interlocking conditions


Solution - CFC
Use the following block to evaluate the feedback information (double-point indication)
of a command:

DI to BOOL: Y = VAL = IS_ON & IS_OFF

This block checks a double-point indication for the


states ON, OFF, 00 or 11 and produces a signal
as the result.

VAL IS_OFF IS_ON

y = 1, if ...

Version: B 5_Page 60

04_A0: CFC-Exercises
DIGSI 4 Basic

00
01
10
11

0
1
0
1

0
0
1
1

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 8: Create new interlocking conditions


Solution - CFC
This module issues a HIGH
signal at the output y if the
disconnector is closed.

Release conditions for tripping


the circuit breaker:
Disconnector=CLOSE AND
Ground switch=OPEN

This module issues a HIGH


signal at the output y if the
ground switch is open.

Version: B 5_Page 61

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 9: Controlling via the function keys


The circuit breaker (2-pole CLOSE, 1-pole OPEN) is to be
controlled via the function keys: F1=Close, F2=Trip.
Use the following blocks to create a command and a doublepoint indication:

Close
Trip

BOOL_TO_CO

The switch command is specified via the parameters


ORIGIN, PROP, VAL and TIME and is tripped via a signal
at the Trig input.
ORIGIN
origin of the cause
PROP
general command properties
TIME
output time for the command
VAL
switching direction (ON or OFF)

BUILD_DI

This module transforms two input signals into one


double-point indication. The double-point indication
consists of the 2 bits VAL_OFF and VAL_ON.
TYP_DP_I defines the type of the double-point
indication: with distinction of 00 and 11 or without.

Version: B 5_Page 62

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 9: Controlling via the function keys


Solution
1

2
F2 Trip IntSP
F1 Close IntSP

Version: B 5_Page 63

Q0 F-Key CF_D12

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 10: Controlling via a single function key


Expand exercise 9 so that closing and tripping is initiated alternately via the
same function key (F1).

NEG: Y= X1
X1

D-Flipflop

Version: B 5_Page 64

(+)

X1
Y

The signal at the input D is


issued at the output Q, if a rising
edge is recognised at the input
Clk.

04_A0: CFC-Exercises
DIGSI 4 Basic

X1

0
1

1
0

Clk

0
1
0
1

0
0
1
1

0
0
0
1

Energy Sector

Siemens AG

Siemens Power Academy

Exercise 10: Controlling via a single function key


Solution
1

Priority class: PLC1 (Slow PLC)

F1 Switch IntSP
Trip
Close

Version: B 5_Page 65

04_A0: CFC-Exercises
DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Selection Guide for Function Modules and Task Levels

Version: B 5_Page 1

05_A0: CFC-Function Modules


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Version: B 5_Page 2

05_A0: CFC-Function Modules


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Version: B 5_Page 3

05_A0: CFC-Function Modules


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Version: B 5_Page 4

05_A0: CFC-Function Modules


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Online Mode

Open Device in Online Mode

Plug & Play (First the device has to be initialized)

Hardware Test

Version: B 5_Page 1

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Online Mode

Open Device in Online Mode

Version: B 5_Page 2

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Plug & Play

Version: B 5_Page 3

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Plug & Play

Version: B 5_Page 4

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Parameter Comparison


Offline-/Offline and Online-/Offline

Version: B 5_Page 5

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Parameter Comparison


Offline-/Offline and Online-/Offline

Version: B 5_Page 6

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Change / Transmission of single parameters in


online mode

Version: B 5_Page 7

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Control of switching devices

Version: B 5_Page 8

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Hardware Test

Version: B 5_Page 9

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Hardware Test

Version: B 5_Page 10

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Hardware Test

Version: B 5_Page 11

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Hardware Test

Version: B 5_Page 12

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Hardware Test

Version: B 5_Page 13

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Hardware Test


Exercise
Parametrize the IEC103-protocol as system interface and insert
any communication address
Initialize your device on the table
establish the communication to the device
Set the transmission blocking mode
Control the event log with respect to alarms
Start the test mode and simulate a closed circuit-breaker as
well as an open disconnector and earthing switch by way of
addressing the binary inputs
Verify the response of your device by the integrated interface
Deacivate the transmission blocking mode
Change within the test mode to action generate indications
Send the indication >LED Reset
Verify the response of your device by the integrated interface
and reset that indication

Version: B 5_Page 14

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 Test In- and Outputs / Control of devices


Activate the chatter-blocking
Simulate a chattering at the binary inputs of the feedback information of the Q1 and
check the reaction via menu Control
Switch off the earthing switch Q5
Set the acquisition blocking for Q5 via the integral keypad
substitute the position of Q5 to ON (integral keypad)
check the indication via menu `Control

Version: B 5_Page 15

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 Test In- and Outputs / Control of devices


Set the acquisition blocking for CB and simulate a change of the
CB-position OFF/ON via the binary inputs
Check the reaction
Set the output blocking for switching device Q1 and try to control it
Check the indication via Menu Control
Check the reaction and remove the acquisition blocking
as well as the output blocking for all devices

Version: B 5_Page 16

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Commissioning and Test Functions


Test mode
Data Transmission blocking
Process data retrieval
Operational indication
Operational measuring values

Version: B 5_Page 17

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Test Mode

Version: B 5_Page 18

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Data Transmission Blocking

Version: B 5_Page 19

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Retrieval of Process Data

Version: B 5_Page 20

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Event Log

Version: B 5_Page 21

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Event Log

Version: B 5_Page 22

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Measurement of Operational Values

Version: B 5_Page 23

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Event Log

Version: B 5_Page 24

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Event Log

Version: B 5_Page 25

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Event Log

Version: B 5_Page 26

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Event Log

Version: B 5_Page 27

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Process Data


Exercise
Open the device via plug&play
Change e.g. the pick up value for O/C-protection, as well
as one I/O- configuration and save that change only at the device
Do a on-/offline comparison
Save the changes on PC
Create two test records
Save the records and the event Log to retrieve them in
the off-line mode
Copy the logs and records from the plug&play-variant to
the master file of first exercise
Check the presence in the master device file

Version: B 5_Page 28

06_A0: Commissioning and Test Functions


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Which facilities does SIPROTEC 4 offer ?


IEC-Interface

IEC 61850 substation ethernet communication


The "VDEW-interface " is international standard IEC 60870-5-103
(without parameterizing)
According to recommendation of VDEW switching operations are
possible

PROFIBUS-Interface

PROFIBUS FMS is a protocol which includes all functions. Excellent


in conjunction with SICAM
PROFIBUS DP a protocol for simpler applications in conjunction
with automatization systems for industrial application.

Additional interfaces

Modbus
DNP 3
...........

Version: B 5_Page 1

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Which features does SIPROTEC 4 offer

variable interfaces

or electrical

as fibre optics

exchangeable
refittable

Version: B 5_Page 2

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Communication: Setup with IEC 60870-5-103


To load dispatcher

SICAM SCADA

IEC 60870-5-103 e.g. RS 485


IEC 60870-5-103 z.B, point to point

STATION

Version: B 5_Page 3

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Select the communication interfaces

Version: B 5_Page 4

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Set the IEC address

Version: B 5_Page 5

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

IEC Parameter

Version: B 5_Page 6

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Masking with IEC protocol

Version: B 5_Page 7

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Communication: Setup with Profibus FMS


To Load dispatcher

DIGSI 4

Profibus FMS

SICAM

SUB-STATION

Version: B 5_Page 8

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Setting the communication interface

Version: B 5_Page 9

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Setting of the Profibus FMS Addresses

Version: B 5_Page 10

PROFIBUS FMS

(SICAM SAS)

PROFIBUS FMS

(DIGSI 4 via PC)

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

FMS Parameters on PC

Version: B 5_Page 11

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

FMS Parameters at the device

Version: B 5_Page 12

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Masking with FMS Protocol

Version: B 5_Page 13

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Communication: Setup with additional protocols


e.g. Profibus DP
To load dispatcher

e.g Profibus DP

SIMATIC S7

STATION

Version: B 5_Page 14

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Additional protocols e.g. Profibus DP

Version: B 5_Page 15

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Additional Protocols
Select the Mapping-file and Address

Version: B 5_Page 16

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Additional Protocols e.g. Profibus DP


7SJ6-Standardmapping 3-1 bis 3-4

Output
Input

7
29

7
29

8
24

3
5

Double commands
Single commands

7
7
146 114
25 10
6
2
2
1

8
64
21
6
1

3
26
8
2
0

Double annunciations
Single annunciations
Measurement values
counter values
value annunciations

9
100

8
80

2 Bytes Output
28 Bytes Input

9
48

The volume of the data-objects which are offered via Profibus-DP


(Number of the Commands, Annunciations, Measuring values,
Counter values in Output- resp. Input direction) is exclusively
determined by the selection of a Standardmapping.
Version: B 5_Page 17

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Marshalling of Informations

Version: B 5_Page 18

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Scaling of Measuring Values

Version: B 5_Page 19

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Communication: Setup via Service Interface C

Public phone conn.

To Load Dispatcher

DIGSI 4

Office

Modem

Version: B 5_Page 20

IEC 870-5

STATION

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 for Remote communication via Service Interface

Version: B 5_Page 21

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Communication: Setup via Operator Interface


To Load Dispatcher

STATION
DIGSI 4

IEC 870-5

Version: B 5_Page 22

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 via Operator Interface

Version: B 5_Page 23

07_A0: Setting of Communicationinterfaces


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Process Data Analysis

Representation of indications and measured values


Retrieval of fault records with DIGSI 4
The COMTRADE format
Parameterization of fault record representation
Definition of user profile
Angle measuring

Fourier analysis
Impedance calculation
Export of fault records

Version: B 5_Page 1

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Evaluation of Fault record


The following data are used for the evaluation:
Measured values recorded in the device fault record
Characteristics calculated by SIGRA 4, for ex. impedance
Binary signals
Data of other fault records for comparison

Version: B 5_Page 2

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Generation of RIO-File in DIGSI 4 (Part 1)


Only relevant for
distance protection !

Version: B 5_Page 3

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

Generation of RIO-File in DIGSI 4 (Part 2)


Only relevant for
distance protection !
FALSE
TRUE

Version: B 5_Page 4

08_A0: Process Data Analysis


DIGSI 4 Basic

at I(nom) = 1A
at I(nom) = 5A

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Indication / Measured Value Indication


Evaluation of fault record data via the SIGRA 4 views:
Time signal
Vector diagrams
Circle diagram
Harmonic components

Version: B 5_Page 5

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Time Signal View

Version: B 5_Page 6

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Vector Diagram View

Version: B 5_Page 7

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Circle Diagram View

Version: B 5_Page 8

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Harmonic Component View

Version: B 5_Page 9

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Graphical Structure of a Fault Record


The graphical interface of a fault records consists of the following:
Views with as many diagrams as you like
Diagrams with as many signals as you like
Signals of any view and diagram
- analog signals
- binary signals
- status signals

Version: B 5_Page 10

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Diagrams / Signals


Insert / Assign
Copy
Delete
Define Properties

Version: B 5_Page 11

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Object Properties


Diagram properties

Version: B 5_Page 12

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Signal Assignment

Version: B 5_Page 13

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Structure of Fault Records

A fault record has the following components:


*.CFG - COMTRADE configuration file
*.DAT - COMTRADE file (measured values)
*.RIO

- protection settings (optional)

*.DG4 - SIGRA 4 session connection memory

Version: B 5_Page 14

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Exporting of Fault Records

Open Record Object


Select Fault Record
Open Export Dialog
Define Export File
Export Fault in the COMTRADE format

Version: B 5_Page 15

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

DIGSI 4 - Definition of Setting Values for Fault


Records
Open the Fault
Record dialog box
in the settings
mode
Set values
Transfer values
to device

Version: B 5_Page 16

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - The COMTRADE Format

Version: B 5_Page 17

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - The .dat Data File


0000000000,0000000000,-00118,000030,000084,000150,-00108,-00038,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000001,0000001666,-00126,000098,000024,000113,-00162,000052,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000002,0000003332,-00081,000114,-00035,000036,-00142,000110,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000003,0000004998,-00024,000124,-00104,-00057,-00107,000168,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000004,0000006664,000039,000080,-00120,-00115,-00030,000150,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000005,0000008330,000101,000026,-00129,-00168,000054,000117,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0

First set of data

The contents of the .DAT data files


can be viewed in the Text Editor. The
figures are separated by commas.
The data file can be edited in external
programs like Excel.

0000000596,0000992936,000081,-00116,000029,-00039,000146,-00105,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000597,0000994602,000022,-00125,000097,000054,000110,-00161,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000598,0000996268,-00037,-00086,000117,000113,000039,-00147,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000599,0000997934,-00101,-00030,000126,000166,-00050,-00116,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000600,0000999600,-00117,000027,000086,000149,-00104,-00043,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
1. ......

.........

6.1. ..

......

19

Last set of data

Scanning value of the analog


Value of the 19 binary values (0 or 1)
channels (analog channel multiplied
by its factor)
Time scale in ms
Number of the scanning value

Version: B 5_Page 18

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Frequency Analysis


Fourier : A periodic signal can be divided up into its frequency contents.
sig

N-1

Period with scanning values

N/2

N-1

sig =

m=0

k=0

Am * cos

m k + Bm * sin m k

Sum value of N scanning values per supply period


Frequency content (m=0 direct component, m=1 fundamental component, m=2 second harmonic

Version: B 5_Page 19

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Frequency Analysis

direct
component

fundamental
component

2. harmonic

C0

C1

C2

N/2+1

N/2

For N scanning valued per supply period


DIGSI can calculate N/2 spectral lines by
way of the Fourier analysis.
N-1
sig = C0 +

C1 * cos (
k=0

Cm =

Version: B 5_Page 20

Am2 + Bm2

l k+w1) + C2 * cos (

2 k +w2 ) + .........

wl = arctan(Bm / Am)

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Process Data Analysis

Parameterization of fault records


Definition of user profile
Synchronization of fault record

Version: B 5_Page 21

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Measuring a Fault Record

Tools for fault record measuring:


Zoom
Table
- assignment of measured signals
- assignment of times
Cursor behavior
- magnetic (on status signals) pointer
- snapping (on samples) pointer
Status signals

Version: B 5_Page 22

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Parameterization of Fault Record

Parameterize
channels
(Network Nodes)

Version: B 5_Page 23

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Parameterization of Fault Record

Parameterize
Network Nodes

Version: B 5_Page 24

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - User Profiles

Define and save


Use
Define assignment
Delete
Insert device type

Version: B 5_Page 25

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - User Profiles

Define
Save
Use
Delete

Version: B 5_Page 26

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - User Profiles

Assign

Version: B 5_Page 27

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Synchronization Procedure

Insert comparison fault record B


Insert empty diagram in the Time Signal view
Insert signal of fault record A, for ex. phase voltage in short circuit
Insert comparison signal from fault record B
Cursor position

- Cursor 1 on synchronous point signal fault record A


- Cursor 2 on synchronous point signal fault record B
Select Synchronize Fault Records (menu command)
Check synchronous points and displacement
Trigger synchronization

Version: B 5_Page 28

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG

Siemens Power Academy

SIGRA 4 - Dialog Box

Version: B 5_Page 29

08_A0: Process Data Analysis


DIGSI 4 Basic

Energy Sector

Siemens AG