Generic phase directional relay I>dir, I>>dir (IOC, UMZ) Relay

Its a generic relay model providing two directional controlled phase short circuit protection functions
(67, IOC).
The unit I>dir starts the directional measurement. The directional measurement check the directional
and is sending a forward and a reverse signal to the over current units I>dir and I>>dir. For each
over current unit it is possible to setup the direction option:
a) None : for non-directional tripping
b) Forward: for forward directional tripping
c) Reverse: for reverse directional tripping
Further its possible to set the max. torque angle, see Directional slot, page: Voltage Polarizing
The angle is entered as leading MTA angle -> the voltage phasor is shifted by the entered MTA
angle.
The nominal current and nominal voltage can be set in the Measure slot (1A or 5A e.g. 100,110 or
120V ). All current settings are defined in p.u. ( x In ). The delay can be set in the corresponding units
(I>dir,I>>dir) in seconds.

U + MTA

= angle( U, shifted by MTA) angle(I)


The directional unit detects a forward fault if | | < 90 and a reverse fault if | | > 90