I1 = Float Charger mode current rating = Continuous load current requirement + Float Charging current of Battery (=1.5mA per AH of Battery) 24.73 ++ ( (125 = 132.14 .0015x0.0015) x 1600) =
24.73 +
24.92
0.1875 Amp.
With 25% design margin, required rating of Float Charger shall be
= 31.15
Amps
REQUIRED FLOAT CHARGER MODE RATING = 32 A
Boost Charger mode rating = Float charger rating or 15% of Battery AH capacity+ 25 % design Margin ( Whichever is higher) = (125 x 0.15) x 1.25 =