SUBSTATION AUTOMATION SCADA SYSTEMSUBSTATION AUTOMATION SCADA SYSTEM
SMART INTEGRATED POWER MONITORING, CONTROL AND DATA ACQUISITION SYSTEM is an
advanced power quality monitoring and events detection system. It is combined with remote
monitoring and control of the Electrical network apparatus, operating under a single and integrated
application software and a state-of-art field data acquisition hardware capable of implementing both
functions internally from a single box. The system is centralized and provides a remote web
monitoring with clients.
The SCADA System configuration:
Main Communication Engineering Operator Operator
Server (MCS) Workstation (EWS) Workstation 1 (OWS1) Workstation 2 (OWS2)
Ll bl Ce
mm Go GS em
The System consists of MCS, EWS, OWS1, OWS2, Network, RTU1, subRTU1, subRTU2, ..., SUBRTUN
RTU2, RTU3, ..., RTUn.SUBSTATION AUTOMATION SCADA SYSTEM
SSSA TumOxolinl Loli -Vai es)
Below is the proposed configuration of the System
OWS1: SCREEN 1 OWS!: SCREEN 2
—S— |=.
EWS: ae ‘ows?
SOW.
+ Main Communication Server (MCS): It includes real time and historical databases and
communication gateway
+ Engineering Workstation (EWS): It includes LabView graphical programming language
to add/modify different parts of the system
+ Operator Workstation! (OWS1): It includes SCADA monitoring and control, basic power
quality monitoring and configuration of settings
+ Operator Workstation2 (OWS2): It includes advanced power quality monitoring
+ RTUs and subRTUs: It includes simultaneous high speed data acquisition from the selected
power channels and streams the waveforms to its local hard drive or directly to a remote PCSUBSTATION AUTOMATION SCADA SYSTEM
Hardware Configuration
> SCADA System
+ Main Communication Server (MCS) computer: IS processor, 4GB RAM, 500GB 7200RPM HDD
+ Engineering Workstation (EWS) computer: 3 processor, 4GB RAM, 500GB HDD
+ Operator Workstation! (OWS1) computer: 13 processor, 4GB RAM, 500GB HDD, two video
outputs with two 42" 1920x1080 (Full HD) resolution monitors
+ Operator Workstation2 (OWS2) computer: 13 processor, 4GB RAM, S00GB HDD, 22” 1920x1080
(Full HD) resolution monitor
+ RTU’s and subRTU’s configuration depends on I/O's quantity
Detailed hardware requirements are prov 1 separate documentSUBSTATION AUTOMATION SCADA SYSTEM
The main features of proposed system are:
>
>
The System Presnet the complete SCADA System.
The system is integrated, providing both the power quality analysis and remote monitoring and
control from a single field data acquisition hardware (in a given location) and a single software
package (control center)
The smart RTU acts as an RTU for remote monitoring and control and also computes power
quality analysis without the need to acquire the information from third party power quality
analyzers.
The automatic monitoring and control units (RTU) of substations are implemented on NI cRIO
platform.
The specialized control software is implemented in LabView graphical programming language
The software visualizes the virtual operating diagrams (single line diagram) of the substations.
It allows interactive monitoring and control over any existing apparatus.
The system is centralized and provides a remote web monitoring with clients.SUBSTATION AUTOMATION SCADA SYSTEM
Operator Workstation 1 (OWS1)
> SCADA Control > Settings Configuration
+ Switch breaker control (open/close) + Local settings (per RTU/Site)
1. Data scaling
> SCADA Monitoring 2. Data deadbanding
+ Switch breaker connectivity status 3. Alarm handling
(disconnected/connected) + Analog signals
+ Switch breaker rack in/out status + Digital signals
+ Live monitoring and historical + Global settings
trending of all alarms and events 1. Watchdog listening rate
+ RTU health status + User settings
+ Power parameters
1. Basic analysis (voltage RMS, > Web Interface
current RMS, frequency) + Monitroing OWS1 using the Internet
2. Power analysis Explorer
(active/reactive/apparent powers,
power factor, vector diagram for
voltage and current)SUBSTATION AUTOMATION SCADA SYSTEM
Operator Workstation 2 (OWS2)
> Waveform analysis + Harmonic analysis
+ Real time voltage and current 1. Basic
waveform monitoring + Voltage and current THD
+ Ability to log the waveforms for specific + Up to the 64th harmonics for
timeframe and further analyzing using voltage and current
Diadem™ + Up to the 63.5th interharmonics
+ Ability to implement transient analysis for voltage and current
(resistive load on/off, motor on/off) 2. Advanced
+ Harmonics per second for
voltage and current
> Non waveform analysis
(All below mentioned parameters are available in Real Time + Harmonics per cycle for voltage
Monitoring and Historieal Trending options. The historical
trending ie implemented with Diadem) and current
+ Basic analysis (voltage RMS, current + Active power harmonics
RMS, frequency) + Advanced Analysis
+ Power analysis 1, Unbalances and events
(active/reactive/apparent powers, + Unbalances
power factor, vector diagram for + Voltage events
voltage and current) 2. Flicker
+ Load impedance