Site tests to be conducted on the 75MVA transformer
S. No. As per tech spec
As per O&M manual of ABB
General practice for our Wind projects
1 Insulation resistance test
2 Ratio and polarity test on all taps 3 Open circuit and short circuit test
Insulation resistance test on transformer & BCT
Megger or insulation resistance test terminals Ratio test on all taps Ratio and polarity test on all taps vector group Open circuit and short circuit test
Operation test of protection devices
4 and interlocks
Functional checks
Operation test of protection devices and
interlocks
Measurement of winding resistance at Measurement of winding resistance
5 all taps at all taps Measurement of winding resistance at all taps 6 Insulation dielectric test for oil quality Oil water content and BDV
Insulation dielectric test for oil quality
Capacitance and Tan Delta test on
7 bushings and windings 8 -9 --
Polarity of BCT ---
Capacitance and Tan Delta test on bushings and
windings Low voltage SC & OC test Operation test on OLTC