Vous êtes sur la page 1sur 1

Short-circuit Coordination

Starter Type:
Motor Protection Circuit Breaker (MPCB):
Contactor:
Overload Relay:
Rated Operational Voltage:
Test voltage:
Rated Conditional S.C. Current (Iq):
Level of S.C. Coordination:

Motor

Circuit Breaker

Rated
Operational
Current I e
[kW]
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
63
63
75
75
90
90
110
132
160
200
250
315
355

Direct-On-Line & Reversing, Trip Class 10


140M-C, D, F, I, J, L
100-C, 100-K, 100-D
--400 V, 50 Hz
436 V, 50Hz
65 kA (rms sym.)
Type ''2'' (Type "1") per IEC 60947-4-1

[A] 1)
0.20
0.30
0.44
0.60
0.85
1.1
1.5
1.9
2.7
3.6
4.9
6.5
8.5
11.5
15.5
22
29
35
41
55
66
80
97
113
113
132
132
160
160
195
230
280
350
430
540
610

Catalog
Number

140M-C2E-A25
140M-C2E-A40
140M-C2E-A63
140M-C2E-A63
140M-C2E-B10
140M-C2E-B16
140M-C2E-B16
140M-C2E-B25
140M-D8E-B40
140M-D8E-B40
140M-D8E-B63
140M-D8E-C10
140M-D8E-C10
140M-D8E-C16
140M-D8E-C20
140M-D8E-C25
140M-D8E-C32
140M-F8E-C45
140M-F8E-C45
140M-I8E-C80E
140M-I8E-C80E
140M-I8E-C80E
140M-I8E-D10E
140M-J8E-D16
140M-I8E-D16E
140M-J8E-D16
140M-I8E-D16E
140M-J8E-D25
140M-J8E-D25
140M-J8E-D25
140M-J8E-D25
140M-L8E-D40
140M-L8E-D40
140M-L8E-D63
140M-L8E-D63
140M-L8E-D63

S.C. Coordination

Contactor

Thermal
Setting
Range

Magnetic
Trip Current

Catalog
Number

[A]

[A]

2)

0.16 - 0.25
0.25 - 0.40
0.40 - 0.63
0.40 - 0.63
0.63 - 1.00
1.0 - 1.6
1.0 - 1.6
1.6 - 2.5
2.5 - 4.0
2.5 - 4.0
4.0 - 6.3
6.3 - 10
6.3 - 10
10 - 16
14.5 - 20
18 - 25
27 - 32
32 - 45
32 - 45
40 - 80
40 - 80
40 - 80
80 - 100
64 - 160
100 - 160
64 - 160
100 - 160
100 - 250
100 - 250
100 - 250
100 - 250
160 - 400
160 - 400
250 - 630
250 - 630
250 - 630

3.3
5.2
8.2
8.2
13
21
21
33
52
52
82
130
130
208
260
325
448
585
585
1200
1200
1200
1500
2240
2400
2240
2400
3500
3500
3500
3500
4800
4800
7580
7580
7580

100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C09...
100-C12...
100-C16...
100-C23...
100-C30...
100-C37...
100-C43...
100-C60...
100-C72...
100-C85...
100-C97...
100-D210...
100-D115...
100-D210...
100-D140...
100-D210...
100-D180...
100-D210...
100-D300...
100-D300...
100-D420...
100-D630...
100-D630...
100-D630...

Coordination
Type

Test
Summary
Letter

3)

Type "2"

TS-1200-1A

Type "2"

TS-1200-1A

Type "2"
Type "1"
Type "2"
Type "1"
Type "2"
Type "1"

TS-1200-2A

Type "2"
Type "1"

Type "1"

E125316

1)

Typical motor currents according IEC 60947-4-1 Table G.1


Incomplete catalog number, add coil and auxiliary contact codes
3)
100-K05 can also be taken
4)
Tested at 42 kA short circuit current
2)

Note: This data is subject to change by Rockwell Automation without notice. Go to www.rockwellautomation.com/products/certifcation for latest information.

File: SCCR-1200A 07-2012 PH

400V_65_MPCB

Remark

4)

Vous aimerez peut-être aussi