Test Record
Grounding System
Test Report
TEST PERFORMED:
ROD TO ROD RESISTANCE TEST
GROUND INTEGRITY TEST
Customer
NGCP - Cruz-Na-Daan Substation
Supplier
Project
100MVA, 230/69-13.8kV TESTING & COMMISSIONING
Site
Cruz-Na-Daan, San Rafael, Bulacan
Test Record
Sheet
2/3
Description
Cont
3
Remarks
Ground
Resistance
1.683m
1.659m
2.317m
2.296m
2.945m
2.770m
3.462m
3.627m
Voltage Drop
Measured Leads
1.32V
0.47V
1.33V
0.47V
1.40V
0.51V
1.39V
0.51V
1.46V
0.54V
1.47V
0.54V
1.53V
0.56V
1.52V
0.56V
Measured Current
Reference
Ground
Test
Ground
52A
54A
61A
61A
68A
70A
78A
76A
272A
276A
284A
281A
290A
292A
304A
302A
Customer
NGCP - Cruz-Na-Daan Substation
Supplier
Done by:
Approved by:
Impressed
Current
10.80A
10.80A
10.80A
10.80A
10.80A
10.80A
10.80A
10.80A
Grid
0.85V
0.86V
0.89V
0.88V
0.92V
0.93V
0.97V
0.96V
Project
100MVA, 230/69-13.8kV TESTING & COMMISSIONING
Site
Cruz-Na-Daan, San Rafael, Bulacan
Dept.:
Testing
Service
Date:
05/02/12
Customer Witness:
Dept.:
Date:
Test Record
Sheet
3/3
Description
Cont
--
SST
COMPACT
TOWER
POST
SWGR.
NOTATION:
P8
L.A.
D.S.
C.V.T.
P6
P4
P2
POWER
TRANSFORMER
P1
P5
P3
Ground Rod
Ground Interconnection
COMPACT
TOWER
POST
P7
Customer
NGCP - Cruz-Na-Daan Substation
Supplier
Done by:
Approved by:
Project
100MVA, 230/69-13.8kV TESTING & COMMISSIONING
Site
Cruz-Na-Daan, San Rafael, Bulacan
Dept.:
Testing
Service
Date:
05/02/12
Customer Witness:
Dept.:
Date: