Vous êtes sur la page 1sur 3

Sheet

1/3

Test Record

Surge Arrester
Field Test Report

TEST PERFORMED:
INSULATION RESISTANCE TEST (5kV DC for 1min.)
INSULATION POWER FACTOR TEST
HIGH POTENTIAL TEST

Customer
NGCP - Cruz-Na-Daan Substation
Supplier
SIEMENS

Project
100MVA,230/69-13.8kV TESTING & COMMISSIONING
Site
Cruz-Na-Daan, San Rafael, Bulacan

Test Record

Sheet
2/3

Description

Cont
3

SURGE ARRESTER (@230kV Line) TEST REPORT

1.0 General Data and Information:

2.0 Visual Inspection

3.0 Electrical Routine Tests


3.1 Insulation Resistance Test: (with 2500V; 200,000M
PHASE

Reading in Giga-Ohms

Test Point

10kV

20kV

30kV

40kV

50kV

Okay
Okay
Okay
Specimen
Current
0.193mA
0.195mA
0.197mA

Dissipation
Capacitance
Power
3.792mW
51.37pF
3.847mW
51.65pF
4.056mW
52.23pF
LEAKAGE
CURRENT

TEST POINT

0.0
0.0
0.0
0.0
0.0
0.0
0.2
0.0
0.0
0.3
0.1
0.1
0.4
0.4
0.3

A-Gnd
B-Gnd
C-Gnd
A-Gnd
B-Gnd
C-Gnd
A-Gnd
B-Gnd
C-Gnd
A-Gnd
B-Gnd
C-Gnd
A-Gnd
B-Gnd
C-Gnd

Customer
NGCP - Cruz-Na-Daan Substation
Supplier
SIEMENS
Done by:

Approved by:

Engr. Michael P. Gregas

Engr. Jimwel C. Capillo

Remarks

@1Min.

Line - Ground
A
Line - Ground
B
Line - Ground
C
3.2 Insulation Power Factor Test:
TEST
TEST
PHASE
MODE VOLTAGE
10kV
A
GST
10kV
B
GST
10kV
C
GST

TEST VOLTAGE

Range)

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A

%PF
0.196%
0.198%
0.206%

REMARKS
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay

Project
100MVA, 230/69-13.8kV TESTING & COMMISSIONING
Site
Cruz-Na-Daan, San Rafael, Bulacan
Dept.:
Testing
Service

Date:
03/28/12

Customer Witness:

Dept.:

Date:

Test Record

Sheet
3/3

Description

Cont
--

SURGE ARRESTER (@69kV Line) TEST REPORT

1.0 General Data and Information:

2.0 Visual Inspection

3.0 Electrical Routine Tests


3.1 Insulation Resistance Test: (with 2500V; 200,000M
PHASE

Range)

Reading in Giga-Ohms

Test Point

Remarks

@1Min.

Line - Ground
684G
A
Line - Ground
B
Line - Ground
762G
C
3.2 Insulation Power Factor Test:
TEST
TEST
Specimen Dissipation
PHASE
Capacitance
Power
MODE VOLTAGE Current
39.8pF
150.0 A 4.111mW
10kV
A
GST
42.7pF
161.0 A 4.539mW
10kV
B
GST
48.3pF
182.1 A 5.572mW
10kV
C
GST

TEST VOLTAGE

10kV

15kV

20kV

25kV

30kV

LEAKAGE
CURRENT

TEST POINT

0.0
0.0
0.0
0.0
0.0
0.0
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.2
0.2

A-Gnd
B-Gnd
C-Gnd
A-Gnd
B-Gnd
C-Gnd
A-Gnd
B-Gnd
C-Gnd
A-Gnd
B-Gnd
C-Gnd
A-Gnd
B-Gnd
C-Gnd

Customer
NGCP - Cruz-Na-Daan Substation
Supplier
Meidensha Electric Mfg. Co., Ltd
Done by:

Approved by:

Engr. Michael P. Gregas

Engr. Jimwel C. Capillo

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A

Okay
Okay
Okay
%PF
0.274%
0.282%
0.306%

REMARKS
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay
Okay

Project
100MVA, 230/69-13.8kV TESTING & COMMISSIONING
Site
Cruz-Na-Daan, San Rafael, Bulacan
Dept.:
Testing
Service

Date:
05/02/12

Customer Witness:

Dept.:

Date:

Vous aimerez peut-être aussi