Vous êtes sur la page 1sur 1

Unit 614, 6th Floor, East Tower Philippine Stock Exchange Center(Tektite)

Exchange Road, Ortigas Center, Pasig City 1605


Tel : +63 2 667 3422, +63 2 576 3390Fax : +63 2 654 2539

Supervisor Mobilization Record


Project name : LSEP4

Ref No.

LSEP4-MUN-SMR-01

Substation Muntinlupa

Site Engineer :

Edciel G. Ebuen

Start date

Completion date2015.01.24

Service type

2015.01.24
Commission process service

Final commission service After-sale service

Item Maker : NANTONG HYOSUNG


Service Item : Correction Works for the Conservator Bag Buchholz Alarm
Service Work Description: (including all the working details)
1. Correction of flow switch orientation or position the transformer oil pump
2. Run the transformer oil pump to see if the flow switch will function correctly

The Remaining and Solutions:


a. Configuration of the variable frequency drive of transformer oil pump
b. Replacement of the defective butterfly valve connecting the radiator and the transformer
oil pump
c. Possible oil tapping for the lacking oil of transformer (can be verified after replacement of
butterfly valve.

Supervisors Name: Mr. Hong Jun Ji

HYOSUNG Staffs Name: Edciel G. Ebuen

Signature :

Signature :