Minutes of the meeting.

Date:
Project:
Venue:

April 18, 2015


18, Gulshan Avenue, Dhaka.
SHL Corporate office, Shanta Western Tower, Dhaka.

Participants:
1. Engr. Md.Shamsuzzoha, Sr. DGM, SHL
2. Engr. N A Patwary, DGM, SHL
3. Engr. K H M Monzurul Haque, DPM, SHL
4. Mohammad Mohsin, APM, SHL
5. Architect Bhuiyan A R M Tareque, Project Architect, EKAR.
Sl No

Discussions & Decision taken

Pit location will be remain as per previous observation made by EME


of Shanta Holdings Ltd. Architect will incorporate that in drawing.

Fan room location proposed by architect is okay. Only one parking


may be lost at basement-1 due to avoid the duct.

3
4
5

Exhaust air and fresh air ventilation duct details in basement 1 will be
incorporated by architect.
Toilet at basement may be increased. Toilet vertical ventilation will
be incorporated.
Fireman lift/Service lift provision: Decision required from Principal
Architect.

Partition in cold water reservoir: which may be at 60:40 ratio.

Septic tank vent pipe position required.

Fuel tank will be around 6000 litre and located any convenient
location at outside of ground floor.

9
10

Pump room outside at basement 4 is preferred to be open.


Provision for shaft at stair room.

Remarks
Done
Don't want to loose any parking.
Fan can be located beside the
column at grid 1-F
Done
Done
Not possible at basement 1
capacity of the reservoirs are 36
m3 & 55 m3
incorporated with main sanitary
shaft
will be located at ground level
beside the loading & unloading
space
will have brick partition