Vous êtes sur la page 1sur 2

Self-supporting cable bundle 0,6/1 kV with

XLPE-insulation

JUS-mark: X00-A, X00/0-A


Alternative name: ABC (aerial bundled conductors)
Elkaleks
standards: HRN HD 626 S1
DIN VDE 0276 part 626

Self-supporting cable
bundles

07

NFA2X

Technical data
Temperature range:
during installation: -5 C
operating temperature: -30 C up to +80 C
at short circuit of max. 5 s: 130 C
Nominal voltage: U0 /U = 0,6/1kV
Test voltage: 4 kV
Minimal inner bending radius: 12D
(D = external cable diameter)

Construction
1. Phase conductor: round Al conductor, multi wire
stranded compacted (RM), class 2 acc. to HRN HD 383, of
cross-section 16, 25, 35, 50 and 70 mm2
phase conductors are marked with longitudinal
protrusions (one, two or three)
2. Neutral (supporting) conductor: round conductor,
multi wire stranded compacted (RM), class 2 acc. to HRN
HD 383, of aluminium alloy:
a) AlMg 1 (1% magnesium) of nominal cross-section 71,5 mm2, or
b) AlMgSi of nominal cross-section 70 mm2
3. Insulation: XLPE (cross-linked polyethylene, recent mark:
PE-X) compound TIX-2 or TIX-5 acc. to HD 626 S1
insulation colour: black
concentrically stranded conductors
For house connections (X00-A):
two-core bundle (for single-phase systems) - phase and
neutral conductor; all Al, of cross-section 16 or 25 mm2, or
f our-core bundle (for three-phase systems) - three phase
and neutral conductor; all Al, of cross-section 16 or 25 mm2
For electric power distribution in metropolitan
network (X00/0-A):
four-core bundle with additional cores for public lighting:
three phase Al conductors of cross-section
25, 35, 50 or 70 mm2
neutral conductor of cross-section 71,5 or 70 mm2
one or two cores for public lighting, Al conductor
of cross-section 16 or 25 mm2

Application
Self-supporting overhead cable bundle, applied for electric power distribution in low voltage metropolitan, suburban and rural
networks, for public lighting and house connections.
Laid on pillars, consoles and house fronts.

124

TK_group07.indd 124

1/3/11 3:43 PM

07
Dimensions - nominal
cross-section

Number of cores

External diameter of rope

mm2

Conductor resistance
at 20oC

Insulation thickness

Diameter with insulation

min.

max.

max.

nominal

min.

max.

mm

mm

/km

mm

mm

mm

Phase conductor

16
25
35
50
70

7
7
7
7
19

4,6
5,8
6,8
7,9
9,7

5,1
6,3
7,3
8,4
10,2

1,91
1,2
0,868
0,641
0,443

1,2
1,4
1,6
1,6
1,8

7
8,6
10
11,1
13,3

7,8
9,4
10,9
12
14,2

7
7

10,2
10

10,6
10,2

0,47
0,5

1,8
1,6

12,9

14,6
13,6

Self-supporting cable
bundles

Phase conductors and neutral conductor

Neutral conductor

71,5 AlMg 1
70 AlMgSi

Bundle
Construction of bundle

Lay of stranding

N x mm
2x16
4x16
2x25
4x25
3x25 + 70
3x25 + 70 + 1x16
3x25 + 70 + 2x16
3x35 + 70
3x35 + 70 + 1x16
3x35 + 70 + 2x16
3x50 + 70
3x50 + 70 + 1x16
3x50 + 70 + 2x16
3x70 + 70
3x70 + 70 + 1x16
3x70 + 70 + 2x16
3x70 + 70 + 2x25

mm

Bundle diameter

Al weight

mm
300
350
350
430
700
700
700
760
760
760
850
850
850
980
980
980
980

Bundle weight

kg/km
15
18
18,4
22,2
26,6
26,6
29,6
29,8
29,8
29,8
33,1
33,1
33,1
38,6
38,6
38,6
38,6

kg/km
93
186
145
290
421
467
513
509
555
602
639
685
732
813
860
907
958

137
270
214
431
569
672
739
688
759
825
809
879
945
1044
1114
1181
1253

125

TK_group07.indd 125

1/3/11 3:43 PM