Octagon Engineering Corporation

Plant Conversion
Project 2314. 1994 Update

4/1/2006

Relief Valve - Two Phase Liquid - Known flow


Tag number

2PhNonConD14

Input data
Sizing code
Valve type
Rupture disk
Calc type
Fluid
Mass flow rate
Relief temperature
Valve set pressure
Total back pressure
Vapor mass fraction
Ratio of specific heats
System spec vol @ PRV inlet
Liquid spec vol @ PRV inlet
Vapor spec vol @ PRV inlet
Vap/gas spec vol @ PRV inlet
Latent heat of vapor @ PRV
Liquid specific heat @ PRV
Saturation press @ relief temp
Noncon gas partial press @ PRV
Percent overpressure
Valve discharge coefficient
Selected valve area

ASME Sect 8 single valve


Standard valve
Not required
Flashing and noncond gas norm boil rge<150F
153830 lb/h
150 degF
200 psig
5.784 psig
.5596
1
.1549 ft3/lb
.02 ft3/lb
.2 ft3/lb
.2462 ft3/lb
99.9999 btu/lb
.7 btu/lb/degF
200 psig
310 psig
10
.85
4.34 in2

Output data
Calculated valve area
Relief pressure
Valve capacity
Max back pressure
Valve orifice designation
Atmos reaction force
Selection based on Varec Model 2000
Notes
InstruCalc 6
BB
AA

By SWT
App PT

4.231 in2
220 psig
157797 lb/h
47.61 psig
4N6
6223 lb