Vous êtes sur la page 1sur 24

1

What a Generator looks like


Generator Protection

Theory

Show Generator Theory General Overview and


Typical System from Training CD

Generator Protection
System
Ground
Stator
Ground
Exciter

The
"Wild"
Power
System

Stator
Phase
System
Phase

Internal and External Short Circuits


10

Generator Protection Review


Abnormal Operating Conditions

Loss of Synchronism
Abnormal Frequency
Overexcitation
Field Loss
Inadvertent Energizing
Breaker Failure
Loss of Prime Mover Power
Blown VT Fuses
Open Circuits

11

Generator Protection
Over
Power

Overexcitation
Loss of Field

Open
Circuits

Loss of Field
Overexcitation

Overexcitation

The
"Wild"
Power
System

Exciter

G
Abnormal
Frequency
Reverse
Power

Inadvertent
Energizing,
Pole Flashover
Breaker
Failure

Abnormal
Frequency

Loss of
Synchronism

Abnormal Operating Conditions


12

13

Small Machine Protection


IEEE Buff Book

32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
49 Thermal Overload
51V voltage restraint
51G Ground overcurrent
64 Ground Relay
87 Differential

Large up to 50 MW

14

Large Machine Protection


IEEE C37.102
Unit Connected,
High Z
Grounded
32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
49 Thermal Overload
51V voltage restraint
51G Ground overcurrent
64 Ground Relay
87 Differential

15

Generator Protection with GSU Wrap


PTs on Low Side

16

Generator Protection with GSU Wrap


PTs on High Side

17

Generator Protection
PTs on Low Side

18

Desirable Attributes - Generator


Reverse Power (32)
Should be sensitive to 0.05 pu to properly detect motoring in large steam turbines
Existing E/M and Static relays not sensitive enough
May cause shutdown difficulties

Negative Sequence (46)


Should be sensitive to low values to detect open poles/conductors on system after GSU
Existing E/M and Static relays not sensitive enough

Long time low level events may cause excessive rotor heating, thermal tripping and
damage rotor

100% Stator Ground (59N / 59D)


Protects all of the stator winding
Existing schemes typically only see 90%
Stop low level fault near neutral from degrading into a high level fault and causing large
amounts of damage
Very secure

19

Desirable Attributes - Generator

Inadvertent Energizing (50/27)


High speed tripping of unit after breaker accidentally closed on dead
machine, also pole flashover prior to syncing
Most existing schemes do not incorporate

Many schemes fail due to complexity (reliance on breaker auxiliary


switches, yard distance relays, etc.
If breaker is not tripped rapidly, mechanical and electric damage can
occur to machine in fractions of a second!
Pole flashovers must be cleared by high speed breaker failure, as the
breaker is open!

20

Protection Functions
Generator Stator Differential
Stator Phase Differential
Dual Slope Percent Restraint Operating
Characteristic
Directional Supervision under saturation
conditions

Distance Backup Protection


2 or 3 Zone Mho Distance Protection
Backup for primary line protection

Dual Slope Phase Differential

Configurable Reach and Angle Distance


Characteristic

100% Stator Ground Protection


95% Fundamental OverVoltage
15% Third Harmonic UnderVoltage
Two Zone Distance Backup

21

Protection Functions
Voltage Protection

Phase Overvoltage
Phase Undervoltage
Neutral Overvoltage (fundamental)
Neutral Undervoltage (3rd Harmonic)
Voltage Phase Reversal

Current Protection

Voltage Restraint Overcurrent

Phase, Ground and Negative Sequence


Overcurrent Tripping
IEC, ANSI , IAC and Customizable
Overcurrent Curves
Voltage Restraint increasing sensitivity
under
low voltage conditions

Frequency Protection
Overfrequency
Underfrequency

Undervoltage Trip Curves

22

Protection Functions
Thermal Protection
Generator Thermal Model
RTD Alarming and Tripping
RTD Biased Thermal Model

Inadvertent Energization
Prevents Accidentally Closing a Stopped
Generator onto a Live Line
Armed when Generator is Offline and
Voltage is
below a pre-set level

Loss of Excitation

Thermal Model Voltage


Dependant
Overload Curves

(show Training CD)

Uses Impedance Circle for loss of excitation


detection
2 Zones for fault detection and control

Volt/Hertz (Overexcitation)
Detects changes in the Volts/Hertz ratio
of the
generator or associated
transformer

Loss of Excitation

23

24

Vous aimerez peut-être aussi