Software Change Note

Application:
Application Name:
Manual:

APFIF131
Line Synchronization application
(Super Soft Starter)
ud01177

APFIF131V130
Replaced Application:
APFIF131V128
System Software requirement: NXPV180
Used in production:
2011.8.25
Changes in new application:
F83 Voltage Error OPT-D7 can be selected as fault.

APFIF131V128
Replaced Application:
APFIF131V127
System Software requirement: NXPV180
Used in production:
2011.2.21
Changes in new application:
If OPT-AF is used drive will open and lock all contactor when
Safe Torque Off is active
Run status will stay high if any of the DOL contactors are
closed.

APFIF131V127
Replaced Application:
APFIF131V124
System Software requirement: NXPV180
Used in production:
2010.12.16
Changes in new application:
Added DOL conflict monitoring function, if control and status
are opposite for DOL contactor response can be selected.
Emergency stop will open all relays and will be open until all
DOL relays are commanded open.
1
21.8.2012

APFIF131V124
Replaced Application:
APFIF131V123
System Software requirement: NXPV177
Used in production:
Not in Production
Changes in new application:
Rising edge start command was reset from NET contactor
control signal, preventing use of coasting stop delay. Drive
was stopped immediately after delay to close time has
passed. V124 version is fixed so that coasting stop delay is
effective also when rising edge start command is used.
Field update:
It is recommended to update the application if the above-mentioned
functions are needed.
NOTE!
Earlier version parameter files may not work same way in new version. See
compatibility note from manual and latest parameter descriptions from
NCDrive.

2
21.8.2012