TABLA A1.1.16.

b: CAPACIDAD DE DISTRIBUCIN (kVA-m) PARA CIRCUITOS


TRIFSICOS CON CABLES MONOPOLARES DE COBRE (EUROPEOS) EN DUCTOS PARA
INSTALACIONES INTERIORES.
kVA-m (1%)
CALIBRE
2
(mm )
1.5
2.5
4
8
10
16
25
35
50
70
95
120
150
185
240
300
400

70C
Cosq=0,9
208Y120V 480Y277V
30
160
50
266
80
427
120
637
204
1,089
319
1,699
489
2,601
675
3,597
944
5,026
1,269
6,758
1,612
8,584
1,999
10,645
2,374
12,642
2,739
14,587
3,331
17,737
3,887
20,699
4,579
24,388

Cosq=0,8
208Y120V 480Y277V
34
180
56
298
90
478
133
711
227
1,208
352
1,872
533
2,841
731
3,891
1,008
5,368
1,333
7,101
1,666
8,870
2,033
10,827
2,372
12,632
2,691
14,328
3,196
17,021
3,656
19,471
4,186
22,291

90C
Cosq=0,9
Cosq=0,8
208Y120V 480Y277V 208Y120V 480Y277V
28
150
32
169
47
250
53
280
75
402
84
449
113
599
126
669
192
1,024
214
1,137
300
1,599
331
1,765
460
2,452
504
2,682
637
3,394
691
3,679
892
4,749
955
5,086
1,201
6,398
1,267
6,746
1,529
8,143
1,587
8,449
1,900
10,117
1,942
10,340
2,261
12,043
2,272
12,097
2,615
13,926
2,583
13,758
3,189
16,984
3,080
16,401
3,732
19,873
3,534
18,818
4,414
23,508
4,062
21,633

NOTAS:
1.- Se tomaron las condiciones de instalacin ms desfavorables para la capacidad de distribucin que
corresponden a cables monopolares.
2.- Para la mayoria de las aplicaciones se utiliza valores para 90 C.
3.- Valores calculados en base a frmula: kVA.m = 104 x(V%) x (kV)2 / (RcosQ + XsenQ).
4.- Valores base R y X tomados del Catlogo de Cables para Baja Tensin de Pirelli y ajustados para la temperatura
y frecuencia de operacin.